Carrier 17EX Specifications

Browse online or download Specifications for Air compressors Carrier 17EX. Carrier 17EX Specifications User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 120
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Start-Up, Operation, and Maintenance Instructions
SAFETY CONSIDERATIONS
Centrifugal liquid chillers are designed to provide safe
and reliable service when operated within design speci-
fications. When operating this equipment, use good judg-
ment and safety precautions to avoid damage to equip-
ment and property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in the chiller instructions
as well as those listed in this guide.
DO NOT VENT refrigerant relief valves within a building. Outlet
from rupture disc or relief valve must be vented outdoors in ac-
cordance with the latest edition of ASHRAE (American Society of
Heating, Refrigeration, and Air Conditioning Engineers) 15. The
accumulation of refrigerant in an enclosed space can displace oxy-
gen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ASHRAE 15,
especially for enclosed and low overhead spaces. Inhalation of high
concentrations of vapor is harmful and may cause heart irregulari-
ties, unconsciousness, or death. Misuse can be fatal. Vapor is heavier
than air and reduces the amount of oxygen available for breathing.
Product causes eye and skin irritation. Decomposition products are
hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller
for any purpose. Oxygen gas reacts violently with oil, grease, and
other common substances.
NEVER EXCEED specified test pressures, VERIFY the allowable
test pressure by checking the instruction literature and the design
pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry
nitrogen.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and
functioning before operating any machine.
DO NOT WELD OR FLAME CUT any refrigerant line or vessel
until all refrigerant (liquid and vapor) has been removed from chiller.
Traces of vapor should be displaced with dry air or nitrogen and
the work area should be well ventilated. Refrigerant in contact with
an open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig chiller sections or
the entire assembly.
DO NOT work on high-voltage equipment unless you are a quali-
fied electrician.
DO NOT WORK ON electrical components, including control pan-
els, switches, starters, or oil heater until you are sure ALL POWER
IS OFF and no residual voltage can leak from capacitors or solid-
state components.
LOCK OPEN AND TAG electrical circuits during servicing. IF WORK
IS INTERRUPTED, confirm that all circuits are deenergized be-
fore resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the
eyes. USE SAFETY GOGGLES. Wash any spills from the skin
with soap and water. If any enters the eyes, IMMEDIATELY FLUSH
EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant cyl-
inder. Dangerous overpressure can result. When necessary to heat
refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or
attempt to refill them. It is DANGEROUS AND ILLEGAL. When
cylinder is emptied, evacuate remaining gas pressure, loosen
the collar and unscrew and discard the valve stem. DO NOT
INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to
the chiller. The introduction of the wrong refrigerant can cause dam-
age or malfunction to this chiller.
Operation of this equipment with refrigerants other than those
cited herein should comply with ASHRAE-15 (latest edition). Con-
tact Carrier for further information on use of this chiller with other
refrigerants.
DO NOTATTEMPT TO REMOVE fittings, covers, etc., while chiller
is under pressure or while chiller is running. Be sure pressure is at
0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other
relief devices AT LEAST ONCE A YEAR. If chiller operates in a
corrosive atmosphere, inspect the devices at more frequent
intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief
device when corrosion or build-up of foreign material (rust, dirt,
scale, etc.) is found within the valve body or mechanism. Replace
the device.
DO NOT install relief devices in series or backwards.
USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to
act as projectiles.
RUN WATER PUMPS when removing, transferring, or charg-
ing refrigerant.
DO NOT STEP on refrigerant lines. Broken lines can whip about
and cause personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or staging.
Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or
move inspection covers or other heavy components. Even if com-
ponents are light, use such equipment when there is a risk of slip-
ping or losing your balance.
BE AWARE that certain automatic start arrangements CAN EN-
GAGE THE STARTER. Open the disconnect ahead of the starter
in addition to shutting off the machine or pump.
USE only repair or replacement parts that meet the code require-
ments of the original equipment.
DO NOT VENT OR DRAIN waterboxes containing industrial brines,
liquid, gases, or semisolids without permission of your process con-
trol group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has
been completely drained.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or
other items have been removed before rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the
nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for cor-
rosion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pres-
sure relief device to prevent a build-up of condensate or rain
water.
17EX
Externally Geared Centrifugal Liquid Chillers
50/60 Hz
1500 to 2250 Nominal Tons (5280 to 7910 kW)
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
Tab 5d
PC 211 Catalog No. 531-721 Printed in U.S.A. Form 17EX-1SS Pg 1 7-97 Replaces: New
Page view 0
1 2 3 4 5 6 ... 119 120

Summary of Contents

Page 1 - 50/60 Hz

Start-Up, Operation, and Maintenance InstructionsSAFETY CONSIDERATIONSCentrifugal liquid chillers are designed to provide safeand reliable service whe

Page 2 - CONTENTS

SHAFT DISPLACEMENT& BRG TEMP. CUTOUTCONNECTIONSCOMPRESSOR OILPRESSURE LEAVINGFILTER LINEJOURNALBEARINGCHECK VALVESIGHTGLASSESOIL PUMP& PRESS.

Page 3

Table 15 — 17EX Heat Exchanger Economizer/Storage Vessel, Piping, and Pumpout Unit Weights*COOLERSIZE†COOLERTOTALWEIGHTCOOLERCHARGEECONOMIZER/STORAGEV

Page 4 - CONTENTS (cont)

Table 17 — Additional Condenser Weights*COMPONENTHEAT EXCHANGERSIZEWATERBOX TYPENUMBER OFPASSESDESIGN MAXIMUMWATER PRESSUREADDITIONALDRY WEIGHTADDITIO

Page 5

Table 20A — Total Motor Weight, English (lb)ENCLOSURETYPEHERTZ VOLTAGE SIZE (HP)Open-Drip Proof(ODP)60 HzFA, FF (1250) FB, FG (1500) FH (1600) FC, FJ

Page 6

Table 21 — Marine Waterbox Cover Weights*HEAT EXCHANGERSIZEDESIGN MAXIMUM WATER PRESSURE COOLER CONDENSERpsi kPa lb kg lb kg45-48150 1034 2236 1015 12

Page 7

Table 24 — Auxiliary Systems, Electrical DataPOWER SOURCE ITEM AVERAGE kWDESIGN CENTERVOLTAGESUPPLYV-PH-HzFLA LRA1Seal LeakagePump0.23 115 115-1-50/60

Page 8

NOTE: Refer to Table 26 for item number references.Fig. 57 — Compressor Fits and Clearances105

Page 9 - STARTERS

Table 26 — Compressor Fits and ClearancesITEM DESCRIPTIONCLEARANCETYPE OFMEASUREMinimum Maximumin. mm in. mm1 1st Stage Impeller to Diaphragm See Tabu

Page 10

Tabulation — Impeller Clearances (Open-Drive Compressors)COMPRESSORSIZESHROUDDIAMCODEIMPELLER DIAMETERDIMENSION*Item 1 Item 3in. mm in. mm in. mm17FX3

Page 11 - Definitions

LEGENDBRG — BearingC—ContactorCB — Circuit BreakerCH — ChannelCOM — CommunicationsCOMP’R — CompressorCOND — CondenserDETR — DetectorDIFF — Differentia

Page 12

LEGENDPH — PhasePRESS. — PressurePSIO — Processor/SensorInput/Output ModuleR—Terminal DesignationSMM — Starter Management ModuleT—Terminalt* — Thermis

Page 13

CONTROLSDefinitionsANALOG SIGNAL — An analog signal varies in propor-tion to the monitored source. It quantifies values betweenoperating limits. (Exampl

Page 14

LEGENDCB — Circuit BreakerCOMM — CommunicationsN.O. — Normally OpenN.C. — Normally ClosedO.L. — OverloadPR — Pilot RelayRLA — Rated Load AmpsSMM — Sta

Page 15

Fig. 59 — Elementary Wiring Diagram for Starter Management Module (SMM) and Control Interface BetweenStarter and Chiller Power Panel (For Low and Medi

Page 16

LEGENDDP—Differential PressureC—ContactorCOMP’R — CompressorG—GroundL—Line TerminalLL — Control Power LineTerminalM—MotorOL’s — OverloadsOS — 3-Phase

Page 17

NOTES FOR FIG. 60I GENERAL1.0 Starters shall be designed and manufactured in accordancewith Carrier Engineering requirement Z-375.1.1 All field-supplie

Page 18

LEGENDEQUIP — EquipmentGND — GroundHGBP — Hot Gas BypassS—SwitchT1-T4 — Power Panel TransformersTS — Terminal StripFig. 61 — Oil Pump and Control Powe

Page 19

INDEXAbbreviations, 5Access the Service Screen, To (Service Operation), 42Accidental Start-Up, To Prevent, 61Accuracy, Check Sensor (CheckingTemperatu

Page 20

INDEX (cont)Control,Auxiliary Compressor Oil Pump, 33Auxiliary Gear Oil Pump, 33Capacity, 32Condenser Pump, 36Entering Chilled Water, 32High Discharge

Page 21 - NOTE: SERVICE TABLES:

INDEX (cont)Initial Start-Up,Before, 45Motor, 58Initiation, Ice Build (Ice Build Control), 40Input Equipment Service Parameters If Necessary, 55Input/

Page 22

INDEX (cont)OCCPC01S, Input the Local Occupied Schedule, 54Occupancy Schedule, 32Occupied Schedule (OCCPC01S), Input the Local, 54Oil,Compressor, 77Ex

Page 23 - Table 2 — LID Display Data

INDEX (cont)Refrigerant Float System, Inspect (ScheduledMaintenance), 78Refrigerant Leak Testing, 67Refrigerant Pressures, Reading, 63Refrigerant Prop

Page 24

PIC System Components — The Product IntegratedControl (PIC) is the control system on the chiller. SeeTable 1. The PIC controls the operation of the ch

Page 25

INDEX (cont)Test,Control (Troubleshooting Guide), 85Perform and Automated Control, 56Standing Vacuum, 49Testing, Refrigerant Leak, 67This Manual (Inst

Page 26

LEGEND13 — Condenser Pressure Transducer14 — Condenser Entering WaterTemperature Sensor15 — Condenser Entering and Leaving WaterTemperature Cable16 —

Page 27

Fig. 6 — 17EX Controls and Sensor Locations (cont)Fig. 7 — Control Sensors (Temperature)Fig. 8 — Control Sensors(Pressure Transducer, Typical)LEGENDLI

Page 28

LEGENDEQUIP GND — Equipment GroundGRD — GroundM—MotorTEWAC — Totally Enclosed Water-to-Air CooledFig. 10 — 17EX Chiller Power Panel and Controls Conne

Page 29

PROCESSOR/SENSOR INPUT/OUTPUT MODULE (PSIO)— This module contains all the operating software neededto control the chiller. The 17EX uses 5 pressure tr

Page 30

NOTE: When an alarm is detected, the LID default screenfreezes (stops updating) at the time of alarm. The freeze en-ables the operator to view the chi

Page 31

3. Press SELECT to view the desired Point Status table.4. On the Point Status table press NEXT orPREVIOUSuntil desired point is displayed on the scree

Page 32 - PIC System Functions

CCNLOCAL RESETMENUDEFAULT SCREENStart Chiller In CCN ControlStart Chiller In Local ControlClear AlarmsSTATUSSCHEDULE SETPOINTSERVICE(SOFTKEYS)Access M

Page 33

CONTENTSPageSAFETY CONSIDERATIONS ...1INTRODUCTION...5ABBREVIATIONS...517E

Page 34 - Carrier Part No. HK06ZC033

NEXTPREVIOUSSELECTEXITSERVICE TABLEDisplay Alarm History(The table holds up to 25 alarmsand alerts with the last alarm atthe top of the screen.)• Auto

Page 35

NEXTPREVIOUSSELECTEXITSERVICE MENU CONTINUEDFROM PREVIOUS PAGEEQUIPMENT SERVICE (See Table 2, Examples 8, 9, and 10)Service Tables: (See Note)• SERVIC

Page 36

6. a. Press INCREASE or DECREASE to change thetime values. Override values are in one-hour incre-ments, up to 4 hours.b. Press ENABLE to select days i

Page 37 - Optional 8-Input Module) —

Table 2 — LID Display DataNOTES:IMPORTANT: The following notes apply to all Table 2examples.1. Only 12 lines of information appear on the LID screen a

Page 38

Table 2 — LID Display Data (cont)EXAMPLE2—STATUS02 DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2. Press STATUS.3. S

Page 39

Table 2 — LID Display Data (cont)EXAMPLE4—STATUS04 DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2. Press STATUS.3. S

Page 40

Table 2 — LID Display Data (cont)EXAMPLE 6 — CONFIGURATION (CONFIG) DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2.

Page 41 - NAME DESCRIPTOR

Table 2 — LID Display Data (cont)EXAMPLE 7 — LEAD/LAG CONFIGURATION DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2.

Page 42

Table 2 — LID Display Data (cont)EXAMPLE 8 — SERVICE1 DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2. Press SERVICE.

Page 43 - Local Start-Up —

Table 2 — LID Display Data (cont)EXAMPLE 9 — SERVICE2 DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2. Press SERVICE.

Page 44

CONTENTSPageInspect Water Piping ...50Check Optional Pumpout Compressor WaterPiping...50Check

Page 45

Table 2 — LID Display Data (cont)EXAMPLE 11 — MAINTENANCE (MAINT01) DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2.

Page 46

Table 2 — LID Display Data (cont)EXAMPLE 13 — MAINTENANCE (MAINT03) DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2.

Page 47

PIC System FunctionsNOTE: In the rest of this manual, words not part of para-graph headings and printed in all capital letters can be viewedon the LID

Page 48

NOTE: This schedule is for illustration only, and is not in-tended to be a recommended schedule for chiller operation.Depending on its operating mode,

Page 49

Table 3 — Protective Safety Limits and Control SettingsMONITORED PARAMETER LIMIT APPLICABLE COMMENTSTEMPERATURE SENSORSOUT OF RANGE–40 to 245 F (–40 t

Page 50 - Inspect Wiring

2. The motor load ramp loading rate is an operator-configuredvalue that limits the rate at which the compressor motorcurrent or compressor motor load

Page 51

Oil Cooler — The oil for the external gear and the com-pressor must be cooled while the compressor is running. Thecompressor oil cooler is a water-coo

Page 52

Water/Brine Reset — Three types of chilled water/brine reset are available, Reset Type 1, Reset Type 2, andReset Type 3. They can be viewed or modified

Page 53 - Check Starter

Surge Protection — Compressor surge can be de-tected by the PIC based on operator configured settings. Surgecauses amperage fluctuations of the compress

Page 54

LEAD/LAG OPERATION — The PIC control has the ca-pability to operate 2 chillers in the lead/lag mode. It also hasthe additional capability to start a d

Page 55

CONTENTS (cont)PageMotor Handling/Rigging ...81Motor Storage...81External Gear Storage...

Page 56 - Pumpout Compressor —

FAULTED CHILLER OPERATION — If the lead chillershuts down because of an alarm (*) condition, it stops com-municating with the lag and standby chillers

Page 57 - Preparation —

TEMPERATURE CONTROL DURING ICE BUILD—During ice build, the capacity control algorithm uses theWATER/BRINE CONTROL POINT minus 5 F (2.7 C) to con-trol

Page 58 - Check Motor Rotation

NOTE: The LID does not automatically re-attach to the PSIOmodule on the chiller. Access the ATTACH TO NETWORKDEVICE table, scroll to LOCAL, and press

Page 59

7. Press SELECT to access the holiday table. The LIDscreen now shows the holiday start month and day, andhow many days the holiday period will last. S

Page 60

If any of these requirements are not met, the PIC abortsthe start and displays the applicable pre-start mode of failureon the LID default screen. A pr

Page 61

Safety Shutdown — A safety shutdown is identical toa manual shutdown with the exception that the LID displaysthe reason for the shutdown, the alarm li

Page 62

The rotation direction of the motor is shown either on themotor nameplate or on the certified drawing. Information onthe required phase rotation of the

Page 63

Fig. 25 — 17EX Leak Test Procedures47

Page 64

Table 5A — HFC-134a Pressure — Temperature (F)TEMPERATURE (F) PRESSURE (psi)0 6.502 7.524 8.606 9.668 10.7910 11.9612 13.1714 14.4216 15.7218 17.0620

Page 65 - REAR VIEW

4. Leak Determination — If an electronic leak detector in-dicates a leak, use a soap bubble solution, if possible, toconfirm it. Total all leak rates f

Page 66

INTRODUCTIONBefore initial start-up of the 17EX unit, those involved inthe start-up, operation, and maintenance should be thor-oughly familiar with th

Page 67

Inspect Water Piping — Refer to the piping diagramsprovided in the certified drawings and the piping instruc-tions in the 17EX Installation Instruction

Page 68 - Vacuum Test —

2. Direct current (as from a welder) can be passed throughthe winding. The total current should not exceed approxi-mately 50% of the rated full load c

Page 69 - Fig. 36 — Contact Seal

Fig. 27 — External Gear Lubrication System52

Page 70

Table 7 — Recommended Compressor andExternal Gear Fastener Tightening TorquesFASTENERDIAMETER (in.)TORQUE*Lb.-Ft. (N•m)UNC Minimum Maximum1⁄47 (9.5) 9

Page 71 - Chiller Alignment

1. Check that all wiring connections are properly termi-nated to the starter.2. Verify that the ground wire to the starter is installed prop-erly and

Page 72

5. After the last digit is changed, the LID goes to theBUS # parameter. Press the EXITsoftkey to leave thescreen, record your password change, and ret

Page 73 - M—Net Misalignment in Inches

If surge prevention occurs too soon or too late, make thefollowing adjustments:LOADSURGE PREVENTION SURGE PREVENTIONOCCURS TOO SOON OCCURS TOO LATEAt

Page 74 - As illustrated in

Table 8 — Control Test Menu FunctionsTESTS TO BE DEVICES TESTEDPERFORMED1. Automated Tests* Operates the second through seventhtests2. PSIO Thermistor

Page 75

3. Chiller is charged with refrigerant and all refrigerant andall oil valves are in their proper operating position.4. Gear oil, compressor oil, and m

Page 76

Under normal conditions, for the self-lubricating bear-ing, the rate of temperature rise should be from 20°to 25° F (11° to 14° C) during the first 10

Page 77

LEGENDNIH — Nozzle-In-Head*Any available cooler size can be combined with any available condenser size.NOTE: For details on motor size designations, s

Page 78

2. Offset and Angular Alignment — Reverse dial indicationor optical methods of alignment (such as lasers) are rec-ommended. A cold alignment and a hot

Page 79

4. General Recommendationsa. Both disc couplings are designed to operate for ex-tended periods without the need for lubrication or main-tenance. Visua

Page 80

Instruct the Operator — Check to be sure that the op-erator(s) understands all operating and maintenance proce-dures. Point out the various chiller pa

Page 81

NOTE: If the chiller fails to stop, in addition to action thatthe PIC initiates, the operator should close the guide vanesby overriding the guide vane

Page 82

REFRIGERATION LOG CARRIER 17EX EXTERNALLY GEARED CENTRIFUGAL CHILLERPlantChiller Serial No.Chiller Model No. Refrigerant TypeREC. 1 REC. 2 REC. 3 REC.

Page 83

NOTE: Location of pumpout compressor may vary depending on ma-chine arrangement.DRIVE ENDCOMPRESSOR ENDREAR VIEWCOOLERISOLATIONVALVE910711CHILLERCHARG

Page 84

2. To determine economizer/storage vessel pressure, attacha 30 in.-0-400 psi (-101-0-2760 kPa) gage to the vessel.3. Refer to Fig. 32 for valve locati

Page 85

Transferring Refrigerant into the Cooler/Condenser/Compressor Section —These steps de-scribe how to transfer refrigerant from the economizer/storage v

Page 86 - ICE BUILD SETPOINT

Refrigerant HFC-134a MUST NOT be mixed with airor oxygen and pressurized for leak testing. In general,this refrigerant should not be allowed to be pre

Page 87 - E. NORMAL OR AUTO.-RESTART

LEGEND1—Lubricating Tube2A — O-Ring2B — O-Ring3—Seal Housing4—Coupling Guard Mounting Ring5—Plain1⁄2-in. Washer (8 Required)6—Hex Head Bolt,1⁄2-13×4lg

Page 88

1 2 3 4 5 6 7 8 9 10 11 12 13 1440393738363515161

Page 89

9. Place a clean, lint-free cloth on a smooth, sturdy worksurface. Place the seal housing assembly on the clothwith the face of the contact sleeve in

Page 90

Chiller AlignmentALIGNMENT METHODS — There are several establishedprocedures for aligning shafts. The dial indicator method ispresented here since it

Page 91 - START DELTA T

2. Parallel in elevation — This alignment is also made withshims, but it cannot be made while there is angular mis-alignment in elevation.3. Angular i

Page 92 - LOCAL DEVICE

If the larger opening remains the same but changes fromside to side, the shafts are in perfect alignment. The changein opening is due entirely to coup

Page 93

4. Loosen all holddown bolts except the pivot bolt. Turn thescrew jack until the rear end of the equipment moves againstthe indicator by the desired a

Page 94

When using brackets, the diameter in the alignment for-mula (see Near Final Alignment, Connecting Angular Mis-alignment section) will be that of the c

Page 95

WEEKLY MAINTENANCECheck the Lubrication System —Mark the oil levelon the compressor reservoir sight glass, and observe the leveleach week while the ch

Page 96 - Notes on Module Operation

5. Open the drain located on the shell of the cooler/filter.Run a hose from the drain to a bucket to catch the oil.6. Once the pressure has been reliev

Page 97

The lubricant should be drained while the gear is at op-erating temperature. The gear drive should be cleaned witha flushing oil. Used lubricant and flu

Page 98

CLEANLINESS — On open ventilated motors, screens andlouvers over the inlet air openings should not be allowed toaccumulate any build-up of dirt, lint,

Page 99 - SCHEMATICS

The chiller compressor continuously draws large quanti-ties of refrigerant vapor from the cooler at a rate determinedby the amount of guide vane openi

Page 100

7. When removing the labyrinth seals, note the position ofthe anti-rotation button located on the inside of the tophalf of the seal. Pull up the garte

Page 101

14. Reinstall the bearing housing split bolts. Before torqu-ing bearing housing cap bolts, rotate the shaft by handwhile bumping the bearing housing w

Page 102

Fill the gear drive to the recommended oil level with heatedShell VSI grade 68 oil or its equivalent, heated between110 and 120 F (43 and 49 C). Do no

Page 103 - NIH — Nozzle-in-Head

Water must be within design flow limits, clean, and treatedto ensure proper chiller performance and reduce the po-tential of tube damage due to corrosi

Page 104

temperature control overrides, hot gas bypass, surge al-gorithm status, and time schedule operation. Refer toFig. 14 and Table 2, Examples 11-14.• The

Page 105

4. A high pressure point can also be calibrated between 240and 260 psig (1655 and 1793 kPa) by attaching a regu-lated 250 psig (1724 kPa) pressure (us

Page 106

LEGEND FOR TABLE 12, A - N1CR AUX — Compressor Start ContactCA P— Compressor CurrentCCN — Carrier Comfort NetworkCDFL — Condenser Water FlowCHIL S S—

Page 107

Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)D. PRE-START ALERTS: These alerts only

Page 108

Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)G. START-UP FAILURES: This is an alarm

Page 109

Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)I. NORMAL RUN WITH RESET, TEMPERATURE,

Page 110

External Gear Lubrication Cycle (Refer to Itemnumbers shown in Fig. 5) —Oil reservoir is con-tained in the gear base. The external gear oil pump is mo

Page 111

Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)L. CHILLER PROTECT LIMIT FAULTSExcessiv

Page 112

Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)L. CHILLER PROTECT LIMIT FAULTS (cont)E

Page 113 - NOTES FOR FIG. 60

Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)N. OTHER PROBLEMS/MALFUNCTIONSDESCRIPTI

Page 114

Table 13 — External Gear Troubleshooting GuidePROBLEM POSSIBLE CAUSE — ITEM NO.s*Excessive Operating Temperature 1,2,3,4,5,6,7,9,12,18,20,21Oil Leakag

Page 115

Table 14A — Thermistor Temperature (F) vs Resistance/Voltage DropTEMPERATURE VOLTAGE RESISTANCE(F) DROP (V) (Ohms)−25.0 4.821 98010−24.0 4.818 94707−2

Page 116 - INDEX (cont)

Table 14B — Thermistor Temperature (C) vs Resistance/Voltage DropTEMPERATURE VOLTAGE RESISTANCE(C) DROP (V) (Ohms)−40 4.896 168 230−39 4.889 157 440−3

Page 117

Control ModulesTurn the controller power off before servicing the con-trols. This ensures safety and prevents damage to thecontroller.The Processor/Se

Page 118

If all modules indicate a communications failure, checkthe communications plug on the PSIO module for properseating. Also check the wiring (CCN bus —

Page 119

Options Modules (8-Input) — The options modulesare optional additions to the PIC, and are used to add tem-perature reset inputs, spare sensor inputs,

Page 120

6. Restore control system power (the LID displays, COM-MUNICATION FAILURE at the bottom of the screen).7. Access the SERVICE menu. Highlight and selec

Comments to this Manuals

No comments