Carrier 58PAV Operations Instructions Page 12

  • Download
  • Add to my manuals
  • Print
  • Page
    / 20
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 11
1. Heating mode
When wall thermostat "calls for heat," R-W circuit closes. The
furnace control performs a self-check, verifies pressure switch
contacts are open, and starts inducer motor.
a. Prepurge period—As inducer motor comes up to speed,
pressure switch contacts close to begin a 15-sec prepurge
period.
b. HUM terminal is energized through the pressure switch
circuit. See accessories in the Electrical Connections sec-
tion.
c. Igniter warm-up—At the end of prepurge period, igniter is
energized for a 17-sec igniter warm-up period.
d. Ignition sequence—When igniter warm-up period is com-
pleted, gas valve opens, permitting gas flow to the burners
where it is ignited. After 5 sec, igniter is de-energized and
a 2-sec flame-sensing period begins.
e. Flame-sensing—When burner flame is sensed, the control
begins blower on delay period and continues holding gas
valve open. If burner flame is not sensed, the control closes
gas valve and repeats ignition sequence.
NOTE: Ignition sequence will repeat 3 additional times before a
lockout occurs. Lockout automatically resets after 3 hr, or can be
manually reset by turning 115v off (not at thermostat) for 3 sec
minimum, then on again.
f. Blower on delay—Forty-five sec after burner flame is
proven, blower motor is energized on heating speed.
Simultaneously, electronic air cleaner terminals EAC-1 and
EAC-2 are energized.
g. Blower off delay—When thermostat is satisfied, circuit
between R-W is broken, de-energizing gas valve stopping
gas flow to burners. The blower motor and EAC remain
energized for selected OFF delay.
h. Post-purge—Inducer motor remains energized 5 sec after
burners are extinguished.
2. Cooling mode
When the thermostat "calls for cooling," R-G and R-Y circuits
close. The R-Y circuit starts the outdoor condensing unit and
the combined R-Y and R-G circuits start the furnace blower
motor on cooling speed. The EAC-1 terminal is energized
with 115v when the blower is operating on cooling speed.
When the thermostat is satisfied, R-G and R-Y circuits are
broken. The furnace blower and EAC continue operating on
cooling speed for an additional 90 sec. Cooling OFF delay can
be set to 3 sec by cutting jumper J2. See figure 10.
3. Continuous blower mode
NOTE: EAC-1 terminal is energized with 115v whenever blower
operates.
When the R-G circuit is made, the blower motor operates on
heating speed. During a call for heat, the blower stops,
allowing the furnace heat exchangers to heat up more quickly,
then restarts at the end of the 45-sec blower on delay period.
The blower reverts to continuous operation after the heating
cycle is completed.
When the thermostat "calls for cooling," the blower operates
on cooling speed. When the thermostat is satisfied, the blower
operates for the cooling off-delay before reverting back to
continuous operation on heating speed.
4. Heat pump mode
When installed with a heat pump, the furnace control auto-
matically changes the timing sequence to avoid long blower
off time during demand defrost cycles. When the W-Y or
W-Y-G thermostat inputs are received at the same time, the
control changes the blower to heating speed or starts the
blower if it was off, and begins a heating cycle. The blower
remains on until the end of the prepurge period, then shuts off
until the end of the hot surface igniter warm-up and trial for
ignition periods (a total of 24 sec). The blower then comes
back on at heating speed.
When the W input signal disappears, the control begins the
normal inducer post-purge period and the blower changes to
cooling speed after a 1-sec delay. If the W-Y-G signals
disappear at the same time, the blower remains on for the
selected heating blower off delay period and the inducer goes
through its normal post-purge period. If the W-Y inputs
should disappear, leaving the G signal input, the control goes
into continuous blower and the inducer remains on for the
normal post-purge period.
Anytime the control senses false flame, the control locks out
of the heating mode. This occurs because the control cannot
sense the W input due to the false flame signal, and as a result,
sees only the Y input and goes into cooling mode, blower off
delay. All other control functions remain in standard format.
START-UP PROCEDURES
1. Purge gas lines—After all connections have been made, purge
the lines and check for leaks.
Never purge a gas line into a combustion chamber. Never use
matches, candles, flame, or other sources of ignition for the
purpose of checking leakage. Use a soap-and-water solution
to check for leakage. Failure to follow this warning can cause
fire, explosion, personal injury, or death.
2. Component test—The furnace control allows all components,
except gas valve, to be run for a short period of time.
This feature helps diagnose a system problem in case of a
component failure. To initiate component test procedure, short
(jumper) the TEST 3/16-in. quick connect terminal on control
(behind the Y terminal) and the C
OM-24V terminal on furnace
thermostat connection block for approximately 2 sec. (See Fig.
10.)
NOTE: Component test feature will not operate if any thermostat
signal is present at control.
Component test sequence is as follows.
a. Momentarily jumper TEST and C
OM-24V terminals until
LED goes off.
b. LED will display previous status 4 times.
c. Inducer motor starts and continues to run for entire com-
ponent test.
d. Hot surface igniter is energized for 15 sec, then de-
energized.
e. Blower motor operates on HEAT speed for 10 sec, then
stops.
f. Blower motor operates on COOL speed for 10 sec, then
stops.
g. Inducer motor stops.
3. To operate furnace, follow procedures on operating instruc-
tions label attached to furnace.
4. With furnace operating, set thermostat below room tempera-
ture and observe that furnace goes off. Set thermostat above
room temperature and observe that furnace restarts.
12
Page view 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Comments to this Manuals

No comments