work. The 19XR system conserves this refrigerant and pre-
vents the release of excessive amounts of refrigerant into the
atmosphere. The proper use of this equipment minimizes the
loss of HFCs.
The 19XR PPS system shown in Fig. 1 consists of a pump-
out unit mounted on a storage tank. The pumpout unit is
offered as a free-standing unit that can be used with chillers
that have an existing storage tank or with chillers that have iso-
lation valves that permit built-in refrigerant storage.
The 19XR PPS systems are factory tested and certified to
the American Society of Mechanical Engineers (ASME) pres-
sure vessel code. The tanks are constructed of certified steel
and are pressure rated at 185 psig (1276 kPa). The PPS storage
tank is equipped with dual relief valves for proper venting per
ASHRAE 15 (American Society of Heating, Refrigeration, and
Air Conditioning Engineers) guidelines. An automatic level
switch is prewired to the control circuit to ensure proper stor-
age levels.
The 19XR pumpout unit is a complete, hermetic, compact
unit that consists of:
a hermetic reciprocating compressor with a direct-drive
motor
a water-cooled refrigerant condenser
an oil separator
suction and discharge valves to control refrigerant flow
prewired safety and control devices.
INSTALLATION
Complete Pre-Installation Checks
IDENTIFY UNIT Identify the assembly number (Table 1)
printed on the pumpout unit and storage tank nameplates.
Check this information against the job requirements. Fig. 1
shows the PPS system and its major components. Refer to
Tables 2 and 3 for physical data.
INSPECT SHIPMENT Inspect unit for damage before
removing unit from shipping conveyance. If unit appears dam-
aged, it should be inspected by a shipping inspector before
removal. File a claim with the shipping company if shipment is
damaged or incomplete. The manufacturer is not responsible
for damage incurred during transit.
Check all components. Notify the supplier immediately if
any item is missing. To prevent loss or damage, leave all parts
in their original package until they are needed.
Mount the Pumpout Unit — The pumpout unit, if
purchased separately, may be mounted directly on the chiller or
it may be floor mounted.
MOUNTING ON THE CHILLER — See instructions pro-
vided with the chiller for mounting the pumpout unit. A typical
chiller mount is shown in Fig. 2.
FLOOR MOUNTING — Select a ventilated and accessible
area, free of traffic or other hazards. Remove and discard the
4 angle supports at the base of the pumpout unit and bolt the
unit to the floor through the holes at the base of the pumpout
unit. Special isolation is unnecessary. Contact surface and
dimensions for the pumpout unit are given in Fig. 3.
Table 1 — Positive Pressure System Assembly Numbers (R-134a)
LEGEND
NOTES:
1. All storage vessels are 185 psig (1276 kPa) designs per the ASME (Ameri-
can Society of Mechanical Engineers) Boiler Pressure Vessel Code, Sec-
tion VIII Division 1.
2. All units above are shipped with a 15 psig (103 kPa) nitrogen charge.
3. Nominal horsepower for all pumpout units is 3.0.
PUMPOUT
SYSTEM
ARRANGEMENT
NUMBER
PUMPOUT UNIT
ASSEMBLY NUMBER
COMPRESSOR MOTOR
(V-Ph-Hz)
MAXIMUM
RLA
LRA STORAGE TANK
19XR04027401 19XR04026501 208/230-3-50/60 15.8 105.0 28 cu ft (0.8 cu m)
19XR04027402 19XR04026502 460-3-60 7.8 52.0 28 cu ft (0.8 cu m)
19XR04027403 19XR04026503 400-3-50 7.8 52.0 28 cu ft (0.8 cu m)
19XR04027501 19XR04026501 208/230-3-50/60 15.8 105.0 52 cu ft (1.5 cu m)
19XR04027502 19XR04026502 460-3-60 7.8 52.0 52 cu ft (1.5 cu m)
19XR04027503 19XR04026503 400-3-50 7.8 52.0 52 cu ft (1.5 cu m)
19XR04026801 19XR04026501 208/230-3-50/60 15.8 105.0 Free-standing
19XR04026802 19XR04026502 460-3-60 7.8 52.0 Free-standing
19XR04026803 19XR04026503 400-3-50 7.8 52.0 Free-standing
19XR14017801 19XR04026501 208/230-3-50/60 15.8 105.0 Unit-mounted, frame 1
19XR14017802 19XR04026502 460-3-60 7.8 52.0 Unit-mounted, frame 1
19XR14017803 19XR04026503 400-3-50 7.8 52.0 Unit-mounted, frame 1
19XR34017801 19XR04026501 208/230-3-50/60 15.8 105.0 Unit-mounted, frame 2 or 3
19XR34017802 19XR04026502 460-3-60 7.8 52.0 Unit-mounted, frame 2 or 3
19XR34017803 19XR04026503 400-3-50 7.8 52.0 Unit-mounted, frame 2 or 3
19XR44017801 19XR04026501 208/230-3-50/60 15.8 105.0 Unit-mounted, frame 4
19XR44017802 19XR04026502 460-3-60 7.8 52.0 Unit-mounted, frame 4
19XR44017803 19XR04026503 400-3-50 7.8 52.0 Unit-mounted, frame 4
19XR54017801 19XR04026501 208/230-3-50/60 15.8 105.0 Unit-mounted, frame 5
19XR54017802 19XR04026502 460-3-60 7.8 52.0 Unit-mounted, frame 5
19XR54017803 19XR04026503 400-3-50 7.8 52.0 Unit-mounted, frame 5
19XR64017801 19XR04026501 208/230-3-50/60 15.8 105.0 Unit-mounted, frame 6
19XR64017802 19XR04026502 460-3-60 7.8 52.0 Unit-mounted, frame 6
19XR64017803 19XR04026503 400-3-50 7.8 52.0 Unit-mounted, frame 6
19XR74017801 19XR04026501 208/230-3-50/60 15.8 105.0 Unit-mounted, frame 7
19XR74017802 19XR04026502 460-3-60 7.8 52.0 Unit-mounted, frame 7
19XR74017803 19XR04026503 400-3-50 7.8 52.0 Unit-mounted, frame 7
19XR84017801 19XR04026501 208/230-3-50/60 15.8 105.0 Unit-mounted, frame 8
19XR84017802 19XR04026502 460-3-60 7.8 52.0 Unit-mounted, frame 8
19XR84017803 19XR04026503 400-3-50 7.8 52.0 Unit-mounted, frame 8
LRA Locked Rotor Amps
RLA Rated Load Amps