Carrier 16JT080-150 Specifications

Browse online or download Specifications for Power generators Carrier 16JT080-150. Carrier 16JT080-150 Specifications User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 128
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 211 Catalog No. 531-610 Printed in U.S.A. Form 16JT-3SS Pg 1 901 2-97 Replaces: New
Book 2
Ta b 5 b
Start-Up, Operation, and
Maintenance Instructions
SAFETY CONSIDERATIONS
Absorption liquid chillers provide safe and reliable service when
operated within design specifications. When operating this equip-
ment, use good judgment and safety precautions to avoid damage
to equipment and property or injury to personnel.
Be sure you understand and follow the procedures and safety pre-
cautions contained in the chiller instructions as well as those listed
in this guide.
DO NOT USE OXYGEN or air to purge lines, leak test, or pressurize
a chiller. Use dry nitrogen.
NEVER EXCEED specified test pressures. For the 16JT chiller, the
maximum pressure is 12 psig (83 kPa).
WEAR goggles and suitable protective clothing when handling lith-
ium bromide, octyl alcohol, inhibitor, lithium hydroxide, and hydro-
bromic acid. IMMEDIATELY wash any spills from the skin with
soap and water. IMMEDIATELY FLUSH EYES with water and con-
sult a physician.
DO NOT USE eyebolts or eyebolt holes to rig chiller sections or the
entire assembly.
DO NOT work on high-voltage equipment unless you are a qualified
electrician.
DO NOT WORK ON electrical components, including control pan-
els or switches, until you are sure ALL POWER IS OFF and no resid-
ual voltage can leak from capacitors or solid-state components.
LOCK OPEN AND TAG electrical circuits during servicing. IF
WORK IS INTERRUPTED, confirm that all circuits are deenergized
before resuming work.
NEVER DISCONNECT safety devices or bypass electric interlocks
and operate the chiller. Also, never operate the chiller when any safety
devices are not adjusted and functioning normally.
DO NOT syphon lithium bromide or any other chemical by mouth.
BE SURE all hydrogen has been exhausted before cutting into purge
chambers. Hydrogen mixed with air can explode when ignited.
WHEN FLAMECUTTING OR WELDING on an absorption chiller,
some noxious fumes may be produced. Ventilate the area thoroughly
to avoid breathing concentrated fumes.
DO NOT perform any welding or flamecutting to a chiller while it is
under a vacuum or pressurized condition.
NEVER APPLY an open flame or live steam to a refrigerant cyl-
inder. Dangerous overpressure can result. When necessary to heat a
cylinder, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to
refill them. It is DANGEROUS AND ILLEGAL. When cylinder is
emptied, evacuate remaining gas pressure, loosen the collar and
unscrew and discard the valve stem. DO NOT INCINERATE.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while
chiller is under pressure, vacuum or while chiller is running.
CONNECT THE ABSORPTION CHILLER to an emergency power
source to ensure that a constant power supply is maintained to the unit
in the event that the main electrical power source is interrupted or
temporarily lost. Failure to provide an emergency power source to the
chiller could result in crystallization of the lithium bromide solution
inside the machine, rendering it temporarily inoperative. A potentially
lengthy decrystallization process might be required to return the
chiller to normal operation depending on the severity of the crystalli-
zation and/or the length of time the machine was without power.
PROVIDE AN EMERGENCY POWER SOURCE to the chilled
water and condenser water pumps to prevent the possibility of an
evaporator freeze-up. Failure to provide emergency power to these
pumps could result in machine operation with no flow of water
through the tubeside of the evaporator, absorber and condenser sec-
tions thereby allowing the water inside the evaporator tubes to freeze.
Further, a frozen evaporator tube can burst causing contamination of
the lithium bromide solution and the inside of the chiller. A freeze-up
in the evaporator will also result in a long period of chiller down time
due to the extensive repairs required to bring the chiller and the lith-
ium bromide solution back to its original condition.
DO NOT climb over a chiller. Use platform, catwalk or staging. Fol-
low safe practices when using ladders.
DO NOT STEP ON chiller piping. It might break or bend and cause
personal injury.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or
move inspection covers or other heavy components. Even if com-
ponents are light, use such equipment when there is a risk of slipping
or losing your balance.
VALVE OFF AND TAG steam, water or brine lines before opening
them.
DO NOT LOOSEN waterbox cover bolts until the waterbox has been
completely drained.
DO NOT VENT OR DRAIN waterboxes containing industrial brines,
liquid, gases, or semisolids without permission of your process con-
trol group.
BE AWARE that certain automatic start arrangements can engage
starters. Open the disconnects ahead of the starters in addition to shut-
ting off the chiller or pump.
USE only repaired or replacement parts that meet the code require-
ments of the original equipment.
DO NOT ALLOW UNAUTHORIZED PERSONS to tamper with
chiller safeties or to make major repairs.
PERIODICALLY INSPECT all valves, fittings, piping, and relief
devices for corrosion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pressure
relief device to prevent a build-up of condensate or rain water.
IMMEDIATELY wipe or flush the floor if lithium bromide or octyl
alcohol is spilled on it.
16JT
Double-Effect Hermetic Absorption
Liquid Chillers With PIC Controls
Units 810-880, 080-150, 080L-150
L
Page view 0
1 2 3 4 5 6 ... 127 128

Summary of Contents

Page 1 - Maintenance Instructions

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 2

Page 2 - CONTENTS

0 5 10 15 20 25 30 35 40 455055 60 65 70% LITHIUM BROMIDE BY WEIGHT IN SOLUTIONVAPOR PRESSURE IN INCHES (mm) OF MERCURY ABSOLUTESOLUTION TEMPERATURE F

Page 3 - CONTENTS (cont)

Table 12 — Additional Problems/Symptoms and Their Probable Causes and Remedies (cont)PROBLEM/SYMPTOM PROBABLE CAUSE REMEDYLeaving Chilled Water Temper

Page 4

VOLTAGE DROP —Using a digital voltmeter, the voltagedrop across any energized sensor can be measured while thecontrol is energized. Tables 13A-14B lis

Page 5

Table 13A — 5K Ohm Thermistor Temperature (F) vs Resistance/Voltage DropTEMPERATURE VOLTAGE RESISTANCE(F) DROP (V) (OHMS)−25.0 4.821 98010−24.0 4.818

Page 6 - RIGHT END VIEW REAR VIEW

Table 13B — 5K Ohm Thermistor Temperature (C) vs Resistance/Voltage DropTEMPERATURE VOLTAGE RESISTANCE(C) DROP (V) (Ohms)−40 4.896 168 230−39 4.889 15

Page 7

Table 14A — 100K Ohm Thermistor Temperature (F) vs Resistance/Voltage DropTEMPERATURE VOLTAGE RESISTANCE(F) DROP(V) (OHMS)442 0.300 395441 0.303 39944

Page 8

Table 14A — 100K Ohm Thermistor Temperature (F) vs Resistance/Voltage Drop (cont)TEMPERATURE VOLTAGE RESISTANCE(F) DROP (V) (OHMS)146 3.906 22,106145

Page 9

GREEN LEDS — There are one or 2 green LEDs on eachtype of module. These LEDs indicate the communication sta-tus between different parts of the control

Page 10 - 110 (43.3)

Terminal block connections are provided on the 8-inputmodules. Any spare sensor inputs are field wired and in-stalled. For installation, refer to the u

Page 11

If a CCN Building Supervisor or Service Tool is present,the module configuration should have already been up-loaded into memory; then, when the new mod

Page 12

Table 15 — 16JT Heat Exchanger Weights16JTUNITSIZEENGLISH SIAbsorber/EvaporatorGenerator/CondenserLiBrRefrigerant(Water)OperatingWeight(lb)Absorber/Ev

Page 13 - Definitions

The slightly sloped vertical lines extending from the bot-tom of the diagram are solution specific gravity lines. Theconcentration of a lithium bromide

Page 14

Table 17 — 16JT Waterbox Cover Weights for Unit Sizes 080 to 150, 080L to 150L(lb)16JTUNITSIZESCONDENSER COVER ABSORBER COVER EVAPORATOR COVER EVAPORA

Page 15 - LID Operation and Menus

INDEXAbbreviations and Explanations, 4Abnormal Shutdown, Actions After, 77Absorber Loss Determination, 80Absorber/Condenser (Inspect the Heat Exchange

Page 16

INDEX (cont)Field Wiring, Inspect, 55Final Adjustment of Capacity Controls, 61First 8-Input Module Inputs Test, 33First 8-Input Module, 15First Stage

Page 17

INDEX (cont)Operator Duties, 76Operator, Instruct the, 68Ordering Replacement Chiller Parts, 92Outputs Test,PC6400, 32Slave PSIO, 32Override Operation

Page 18

INDEX (cont)Solution Analysis, 82Solution and Refrigerant, Charge Chiller With, 58Solution Concentration Control, 34Solution Concentration Control,Fir

Page 19 - LID — Local Interface Device

INITIAL START-UP CHECKLIST FOR16JT DOUBLE-EFFECT HERMETIC ABSORPTION LIQUID CHILLER(Remove and use for job file.)MACHINE INFORMATION:NAME JOB NO.ADDRES

Page 20

INSPECT WIRING AND RECORD ELECTRICAL DATA:RATINGS:Line Voltages: ControlsCONTROLS: SAFETY, OPERATING, ETC.Perform Control Test (Yes/No)PIC CAUTIONPUMP

Page 21 - TIME PERIOD SELECT

16JT DOUBLE-EFFECT ABSORPTION LIQUID CHILLERCONFIGURATION SETTINGS LOG(Remove and use for job file.)16JT SET POINT TABLE CONFIGURATION SHEETDESCRIPTION

Page 22 - PIC System Functions

LOCAL 16JT PIC TIME SCHEDULE CONFIGURATION SHEET OCCPC01SDay Flag Occupied UnoccupiedMTWTF S SH Time TimePeriod 1:Period 2:Period 3:Period 4:Period 5:

Page 23 - SCREEN (STATUS TABLE)

16JT PIC CONFIG TABLE CONFIGURATION SHEETDESCRIPTION RANGE UNITS DEFAULT VALUERESET TYPE 1Degrees Reset at 20 mA−15 to 15(−8.3 to 8.3)DEG F(DEG C)10(5

Page 24

Point 10 represents the strong solution leaving the low-stagegenerator and entering the low-temperature heat exchanger.It is at a weaker concentration

Page 25

16JT PIC SERVICE1 TABLE CONFIGURATION SHEETDESCRIPTION RANGE UNITS DEFAULT VALUERefrigerant Trip Point37 to 42(2.8 to 55)DEG F(DEG C)38(3.3)Refrigeran

Page 26

16JT PIC SERVICE2 TABLE CONFIGURATION SHEETDESCRIPTION RANGE UNITS DEFAULT VALUECHWS Temp Enable0to2(0 = DSABLE1 = LOW2 = HIGH)0CHWS Temp Alert−40 to

Page 27 - (EQUIPMENT SERVICE TABLE)

16JT PIC SERVICE3 TABLE CONFIGURATION SHEETDESCRIPTION RANGE UNITS DEFAULT VALUEControl Point Deadband0.5 to 2.0(0.3 to 1.1)DEG F(DEG C)1.0(0.56)Propo

Page 28

HOLIDAY CONFIGURATION SHEET (HOLDY S)DESCRIPTION RANGE UNITS VALUEStart Month 1to12Start Day 1to31Duration 0to99 DAYSHOLIDAY CONFIGURATION SHEET (HOLD

Page 29

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 2

Page 33

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 2

Page 34

CONTROLSDefinitionsANALOG SIGNAL — An analog signal varies in propor-tion to the monitored source. It quantifies values betweenoperating limits. For exa

Page 35

The control center is divided into two areas. The controlvoltages contained in each area of the control center are:• upper right side: all extra-low v

Page 36 - M — Motor Starter

MASTER COMFORT CONTROLLER (PC6400) MOD-ULE — The PC6400 module contains all the operating soft-ware needed to control the chiller. To sense pressures

Page 37

• CCN (Carrier Comfort Network) Operation — The PICcan be placed in CCN Operating mode by pressing theCCNsoftkey. The control will then accept modifica

Page 38

CCNLOCAL RESETMENUDEFAULT SCREENStart Chiller In CCN ControlStart Chiller In Local ControlClear AlarmsSTATUSSCHEDULE SETPOINTSERVICE(SOFTKEYS)Access M

Page 39

NEXTPREVIOUSSELECTEXITSERVICE TABLEDisplay Alarm History(The table holds up to 25 alarmsand alerts with the last alarm atthe top of the screen.)• Auto

Page 40

NEXTPREVIOUSSELECTEXITSERVICE MENU CONTINUEDFROM PREVIOUS PAGEEQUIPMENT SERVICE (See Table 3, Examples 9, 10, and 11)Service Tables:• SERVICE 1• SERVI

Page 41

CONTENTSPageSAFETY CONSIDERATIONS ...1INTRODUCTION ...4ABBREVIATIONS AND EXPLANATIONS ...4CHILLER DESCR

Page 42

BASIC LID OPERATIONS (Using the Softkeys) — To per-form any of the operations described below, the PIC must bepowered up and have successfully complet

Page 43

2. Press SELECT to select the highlighted point.For Discrete Points — Press START or STOP to se-lect the desired state.For Analog Points — Press INCRE

Page 44

8. Press EXIT to leave the period or override.9. Either return to Step 4 to select another period or over-ride or press EXITagain to leave the current

Page 45

Table 3 — 16JT LID Display DataIMPORTANT: The following notes apply to all Table 3examples.1. Only 12 lines of information appear on the LID screen at

Page 46

Table 3 — 16JT LID Display Data (cont)EXAMPLE 2 — PUMPSTAT SCREEN (STATUS TABLE)DESCRIPTION RANGE/STATUS UNITS REFERENCE POINT NAMEDesolidification Mod

Page 47

Table 3 — 16JT LID Display Data (cont)EXAMPLE 4 — ABSSTAT SCREEN (STATUS TABLE)To access this display from the LID default screen:1. Press MENU.2. Pre

Page 48

Table 3 — 16JT LID Display Data (cont)EXAMPLE 7 — SETPOINT DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2. Press SET

Page 49

Table 3 — 16JT LID Display Data (cont)EXAMPLE 10 — SERVICE2 DISPLAY SCREEN(EQUIPMENT SERVICE TABLE)To access this display from the LID default screen:

Page 50

Table 3 — 16JT LID Display Data (cont)EXAMPLE 12 — COOLING SCREEN (CONTROL ALGORITHM STATUS TABLE)The data displayed on this screen is read-only data;

Page 51

Table 3 — 16JT LID Display Data (cont)EXAMPLE 14 — OVERRIDE SCREEN (CONTROL ALGORITHM STATUS TABLE)The data displayed on this screen is read-only data

Page 52 - EXTERIOR INTERIOR

CONTENTS (cont)PageInstruct the Operator ...68• PURGE OPERATION• CONTROL SYSTEM• AUXILIARY EQUIPMENT• CHILLER CYCLES• MAINTENANCE

Page 53

Table 3 — 16JT LID Display Data (cont)EXAMPLE 15 − CONCENTR SCREEN (CONTROL ALGORITHM STATUS TABLE)The data displayed on this screen is read-only data

Page 54

Proportional Band — There are two response modes: onefor the temperature response above the control point; the otherfor response below the control poi

Page 55 - Job Data and Tools Required

Each input is followed by an appropriate value. For ex-ample, Weak LiBr Lvg LCD Box is followed by a tempera-ture. Any reading out of the valid range

Page 56

Manual Mode — During the Slave PSIO outputs test, the LIDdisplays the following messages:ABS16JT — CONTROL TESTPSIO OUTPUTS TEST IN PROGRESSCycle Guar

Page 57

Ramp loading is based on chilled water temperature.During the ramp loading mode, the LEAVING CHILLED WA-TER or ENTERING CHILLED WATER temperature chan

Page 58 - Refrigerant

2. Second stage — occurs if the G2 CONDENSATE OVER-RIDE is exceeded by 1° F (0.56 C). The capacity valveis closed.This capacity override ends when the

Page 59 - ADJUSTMENT

LEGEND AND NOTES FOR FIG. 21-34LEGEND51RP — Refrigerant Pump Overload51SP1 — Solution Pump No. 1 Overload51SP2 — Solution Pump No. 2 Overload51SSP — S

Page 60

Fig. 21 — 16JT PIC Absorption Chiller Electrical Schematic (High Voltage)37

Page 61 - INITIAL START-UP

Fig. 22 — 16JT PIC Absorption Chiller Electrical Schematic (Low Voltage)38

Page 62

Fig. 23 — 16JT PIC Absorption Chiller Electrical Schematic (Slave PSIO Input)39

Page 63

INTRODUCTIONEveryone involved in the start-up, operation, and main-tenance of the 16JT chiller should be thoroughly familiarwith the following instruc

Page 64

Fig. 24 — 16JT PIC Absorption Chiller Electrical Schematic (Slave PSIO Output)40

Page 65 - CONDENSER APPROACH

Fig. 25 — 16JT PIC Absorption Chiller Electrical Schematic (PC6400 Module)41

Page 66 - 45 (7.2)

Fig. 26 — 16JT PIC Absorption Chiller Electrical Schematic (First 8-Input Module)42

Page 67 - 60 (15.6)

Fig. 27 — 16JT PIC Absorption Chiller Electrical Schematic (Second 8-Input Module)43

Page 68

Fig. 28 — 16JT PIC Absorption Chiller Electrical Schematic (Third 8-Input Module)44

Page 69

Fig. 29 — 16JT PIC Absorption Chiller Electrical Schematic (Six-Pack Relay Board 1)45

Page 70

Fig. 30 — 16JT PIC Absorption Chiller Electrical Schematic (Six-Pack Relay Board 2)46

Page 71

Fig. 31 — 16JT PIC Absorption Chiller Electrical Schematic (Wiring Diagram for 120 V Circuit)47

Page 72

Fig. 32 — 16JT PIC Absorption Chiller Electrical Schematic (Communication Detail)48

Page 73

Fig. 33 — 16JT PIC Absorption Chiller Electrical Schematic (Communication Detail, cont)49

Page 74

The smaller vessel above the evaporator/absorber assem-bly is the high-stage generator. Here, approximately half ofthe diluted solution from the absor

Page 75

Fig. 34 — 16JT PIC Absorption Chiller Electrical Schematic (Terminal board Layout)50

Page 76

Water/Brine Reset — Three chilled water or brine tem-perature reset types are available and can be viewed or modi-fied on CONFIG screen under the EQUIP

Page 77

Table 5 — Safety Contacts and Alert LimitsMONITORED PARAMETER LIMIT APPLICABLE COMMENTSTEMPERATURE SENSORSOUT OF RANGE: 5K OHM−40-245 F ( −40-118.3 C)

Page 78

TO CHANGE THE PASSWORD — The password may bechanged from the LID CONFIG screen.1. Press the MENUand SERVICE softkeys. Enter yourpassword and highlight

Page 79

9. Press SELECT to select the month, day, orduration you wish to modify.10. Press INCREASE or DECREASE to change the se-lected item.11. Press ENTER to

Page 80

To view other devices, access the ATTACH TO NET-WORK DEVICE table. Highlight the desired device num-ber. Press the SELECTsoftkey to change the bus num

Page 81 - Standing Vacuum Test —

3. Verify the correct overload and fuse sizes for all motors.Refer to the 16JT Product Data and Installation Instruc-tions manuals for current draw an

Page 82

Chiller Evacuation — When the chiller’s absolute pres-sure is greater than 1 in. (25 mm) of mercury absolute, thechiller must be evacuated as describe

Page 83

BRODEF — From the BRODEF screen, you can:• Configure the outside air temperature and humidity sen-sors, if installed.• Define the start and end of dayli

Page 84 - REAR VIEW

INITIAL REFRIGERANT CHARGING — The refrigerantcharge must be de-ionized water that meets Carrier Speci-fication No. RW01-19. Do not use tap water. Use

Page 85

LEGEND1—Steam Inlet2—High-Stage Generator (G1)3—Low-Stage Generator (G2)4—Cooling Water Outlet5—Condenser6—Rupture Disc7—Purge Storage Chamber8—Contro

Page 86

Table 7 — 16JT Functions and Devices Tested by the PIC Control TestTEST FUNCTION/DEVICE TESTED1. Automated Control Test Performs tests 2 thru 82. PC64

Page 87

INITIAL START-UPThe following start-up procedures are used for absorptionchillers with PIC control systems. During initial start-up, thereis a period

Page 88 - HP, Frame 8)

Final Refrigerant Charge Adjustment — The ad-justment should be made after:1. Chiller is operating with stable temperatures at 40 to 100%of full load.

Page 89

JOB NAME: LOCATION:CHILLER MODEL NO: S/N:OPERATION HOURS: TAKEN BY:DATE: JOB NO.:ITEMNO.DATAITEM*RECORD1RECORD2RECORD3RECORD4REOORD5RECORD6RECORD7RECO

Page 90 - HP, Frame P215M)

ITEMNO.DATAITEM*RECORD1RECORD2RECORD3RECORD4REOORD5RECORD6RECORD7RECORD8GENERATOR:24Strong LiBr LeavingG1 Temperature25Strong LiBrLeaving HX126Strong

Page 91

Table 10 — How to Obtain Data for Log (Fig. 38)ITEM NO. HOW OBTAINED UNITS1 Default screen (CHW_IN) or EVAPSTAT screen DEG F (DEG C)2 Default screen (

Page 92

1.351.301.251.201.151.101.05VAPOR PRESSURE IN INCHES (mm) OF MERCURY ABSOLUTE% OF LITHIUM BROMIDE BY WEIGHT IN SOLUTION4035302520151050SATURATION TEMP

Page 93 - CHILLER START/STOP

1.661.641.621.601.581.561.541.521.801.781.761.741.721.701.6865605550% LITHIUM BROMIDE BY WEIGHT IN SOLUTIONSATURATION TEMPERATURE IN DEG F (DEG C)VAPO

Page 94 - WATER FLOW VERIFY TIME

Check Low Refrigerant Level Operation — Af-ter the chiller has completed a normal shutdown:1. From the LID, access the PUMPSTAT display screen bypress

Page 95 - STARTUP PULLDOWN FAIL

Pre-Start — Once these conditions are met, the PIC thenperforms a series of pre-start checks to verify that all pre-start alerts and safeties are with

Page 96 - K. OUT OF RANGE SENSORS

1—Steam Inlet2—High-Stage Generator (G1)3—Low-Stage Generator (G2)4—Condenser5—Cooling Water Condenser Inlet6—Rupture Disc7—Purge Storage Chamber8—Coo

Page 97 - L. PROTECTIVE LIMIT FAULTS

NOPrestart Checks Passed ?YESStart ChilledWater PumpYESNONOYESStart CoolingWater PumpDelay 20 SecondsCooling WaterFLOW = YES?YESNOWATER FLOW VERIFYTim

Page 98 - N. SPARE SENSOR ALERTS

If a function fails, an alarm displays on the LID with amessage specific to the type of failure. To re-start the start-upsequence, find the cause of the

Page 99 - CYCLE GUARD LEVEL AD

set to AUTO. the PIC controls the Cycle-Guard™ valve. TheREFRIGERANT PUMP must be ON in order for the CYCLEGUARD VALVE to be OPEN. To view the status

Page 100 - PROPORATIONAL CHW_IN GAIN

If the STRONG LiBr LVG LOW HX2 temperature is lessthan or equal to 118 F (47.8 C) and the REFRIGERANTLEVEL SENSOR is greater than the CYCLE GUARD LEVE

Page 101 - Control Modules

CONTINUEG1 HIGH LEVELMachine in Warm-upor Run State?NONOYESG1 High Solution Level?YESPersistence Timer Running?NOStart Persistence Timer30 Second Pers

Page 102

SHUTDOWNCLOSE:Capacity ControlValveNOYESYESChilled Water Flow = YES?YESLow Chilled Water Temp = YES?NOSolution Pump Overload?NOYESRefrigerant Pump Ove

Page 103

When the chiller is in RECYCLE mode, the chilled waterpump relay stays energized so that the chilled water tem-perature can be monitored for increasin

Page 104

Start-Up After Extended Shutdown1. Place the Cycle-Guard™ switch on the control panel door(Item 19 in Fig. 10) in the AUTO position.2. Press the LOCAL

Page 105

Actions After Power Interruption — If the controlpower is interrupted during operation, the chiller stops im-mediately without the normal shutdown seq

Page 106 - (Fig. 59) —

Inspect the Heat Exchanger TubesEVAPORATOR — Inspect and clean the evaporator tubes atthe end of the first operating season. The tube condition de-term

Page 107 - PC6400 HARDWARE ADDRESS

LEGENDEA1 — Refrigerant Pump Overload CutoutEA2 — Solution Pump Overload CutoutEA4 — Vacuum Pump Motor OverloadFA1 — Chilled Water Low-Flow CutoutFA2

Page 108

Absorber Loss Determination — Take absorberloss readings when the chiller is operating with a stabletemperature.1. Make sure that the Cycle-Guard™ val

Page 109

7. Release chiller pressure, correct all leaks, and retest toensure a proper repair.8. Perform a chiller evacuation.REFRIGERANT TRACER — Use an enviro

Page 110

Inhibitor — The initial charge of lithium bromide in-cludes a lithium chromate or lithium molybdate inhibitor. Theinhibitor is used in conjunction wit

Page 111

Refrigerant Charge Adjustment — Check the evapo-rator refrigerant (water) charge after every 6 months of op-eration. An increase in the amount of wate

Page 112 - INDEX (cont)

LEGEND1—Vapor Condensate Temperature Thermistor2—Strong LiBr Leaving High-Temperature Heat Exchanger(HX1) Thermistor3—Strong LiBr Leaving Low-Stage Ge

Page 113

LEGEND16 — Condensate Temperature from G2 Thermistor17 — G1 Internal Pressure Transducer18 — G1 High Pressure Switch19 — Refrigerant Temperature Therm

Page 114

25 — Low Chilled Water Temperature Switch26 — Leaving Chilled Water Temperature Thermistor27 — Entering Chilled Water Temperature Thermistor28 — Cooli

Page 115 - INSTRUCTIONS

Hermetic Pump Inspection — The pumps used onCarrier absorption chillers are hermetic and do not requireseals. Pump motors are cooled by the fluids bein

Page 116

LEGEND1—Stator Can2—Rotor Liner3—Rotor Core4—Recirculation Passage5—Cap Screw6—Pump Discharge Pipe7—Pump Casing8—Impeller9—Casing Wearing Ring10 — Imp

Page 117 - CONFIGURATION SETTINGS LOG

LEGEND1—Stator Can2—Rotor Liner3—Rotor Core4—Recirculation Passage5—Cap Screw6—Pump Discharge Pipe7—Pump Casing8—Impeller9—Casing Wearing Ring10 — Imp

Page 118

0 5 10 15 20 25 30 35 40 455055 60 65 70% LITHIUM BROMIDE BY WEIGHT IN SOLUTIONVAPOR PRESSURE IN INCHES OF MERCURY ABSOLUTESOLUTION TEMPERATURE F (C)3

Page 119

LEGEND1—Stator Can2—Rotor Liner3—Rotor Core4—Recirculation Passage5—Cap Screw6—Pump Discharge Pipe7—Pump Casing8—Impeller9—Casing Wearing Ring10 — Imp

Page 120

DECRYSTALLIZATION USING THE PIC CONTROLS —If crystallization occurs, it generally takes place in the shellside of the low-temperature heat exchanger a

Page 121

When desolidification is complete, release manual controlof the target capacity valve by pressing the MENU,STATUS, and MAINSTAT softkeys. Highlight TAR

Page 122

Table 11 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting GuidesA. SHUTDOWN WITH ON/OFF/RESET-OFFPRIMARY MESSA

Page 123

Table 11 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)D. PRESTART FAILURESPRIMARY MESSAGE SEC

Page 124

Table 11 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)G. WARM-UP FAILURESPRIMARY MESSAGE SECO

Page 125

Table 11 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)K. OUT OF RANGE SENSORSPRIMARYMESSAGESE

Page 126

Table 11 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)L. PROTECTIVE LIMIT FAULTSPRIMARYMESSAG

Page 127

Table 11 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)M. MACHINE ALERTSPRIMARY MESSAGE SECOND

Page 128 - Ta b 5 b

Table 12 — Additional Problems/Symptoms and Their Probable Causes and RemediesPROBLEM/SYMPTOM PROBABLE CAUSE REMEDYChiller Will Not Start orShuts Down

Comments to this Manuals

No comments