Project No.
ADDITION TO ZION'S CAUSE BAPTIST CHURCH
11530
DATE
06/20/11
CCOPYRIGHT , 2011 - MARCUM ENGINEERING, LLC
PHONE - 270.444.9274 FAX - 270.443.1904
S
T
A
T
E
O
F
K
E
N
T
U
C
K
Y
HVAC SCHEDULES
H-5
?
DIFFUSER AND GRILLE SCHEDULE
PHYSICAL DATA PERFORMANCE DATA
MARK MFG. MODEL
SIZE
(INCHES)
NECK
SIZE
(INCHES)
CORE
TYPE
NOM.
CFM
TYPE OF
MOUNTING
THROW
PRESS.
DROP
(IN. H2O)
SOUND
RATING
(NC)
VOLUME
DAMPER
FT. AT
50 FPM
DIR.
S-1 PRICE SPD 12 X 12 
PLAQUE
125 LAY-IN 9 4-WAY 0.097 <15 NO
S-2 PRICE SPD 24 X 24 
PLAQUE
200 LAY-IN 7 4-WAY 0.042 <15 NO
S-3 PRICE SPD 24 X 24

PLAQUE
300
LAY-IN
9
4-WAY
0.065 <15
NO
S-4 PRICE SDB100
48
 2-SLOT
185
LAY-IN 21
ADJ. 0.087 19
NO
S-5 PRICE SDB100 48  4-SLOT 310 LAY-IN 27 ADJ. 0.060 20 NO
S-6 PRICE 520 10 X 6 --- LOUVER 200 SURFACE 20 ADJ. 0.058 <15 YES
S-7 PRICE
520 16 X 8
--- LOUVER
250
SURFACE
23 ADJ. 0.017 <15
NO
R-1 PRICE 80 24 X 24 22 X 22 GRID
1,995
LAY-IN --- --- 0.038 <15 NO
R-2 GREENHECK AFS-120 42 X 60 40 X 58 LOUVER
1,700
SURFACE --- --- 0.020 <15 NO
R-3
PRICE
REMARKS AND ACCESSORIES:
1
FURNISH DIFFUSERS WITH SQUARE-TO-ROUND NECK TRANSITIONS AS REQUIRED.
2
FURNISH ALL DIFFUSERS AND GRILLES WITH POWDER-COATED FINISH IN COLOR AS SELECTED BY ARCHITECT FROM ALL AVAILABLE
OPTIONS.
3
GRILLE TAGGED R-2 SHALL BE CONTRUCTED OF ALUMINUM SIGHT-PROOF BLADES FILLED WITH FORMED FIBERGLASS INSULATION FOR
SOUND ABSORPTION.
4
COORDINATE LOCATION OF DIFFUSERS TAGGED S-7 AND GRILLES TAGGED R-2 AND R-3 WITH ARCHITECTURAL DRAWINGS.
5
SEE HVAC DETAILS FOR THROW DIRECTIONS FOR DIFFUSERS TAGGED S-4 AND S-5.
PRICE, METAL-AIRE, TITUS, OR APPROVED EQUAL
AIR COOLED CONDENSING UNIT SCHEDULE
MARK MFG. MODEL SIZE REFRIG.
COOLING CAPACITY
VOLTAGE
/ PHASE
MCA
(AMPS)
MOCP
(AMPS)
REMARKS AND
ACCESSORIES
TOTAL
(MBH)
SENSIBLE
(MBH)
SEER
CU-1 CARRIER 24APA7 48 R-410A 51.0 36.4 13.6  27.8 40 SEE BELOW
CU-2 CARRIER
24APA7 24
R-410A 25.6 18.7 16.5  13.6 20 SEE BELOW
CU-3 CARRIER 24APA7
36 R-410A 37.1 26.9 16.5
 22.1
35
SEE BELOW
CU-4 CARRIER 24APA7 48 R-410A 51.0 36.4 13.6  27.8 40 SEE BELOW
CU-5 CARRIER 24APA7 24 R-410A 25.6 18.7 16.5  13.6 20 SEE BELOW
CU-6 CARRIER
24APA7
36 R-410A 37.1 26.9 16.5 
22.1
35 SEE BELOW
REMARKS AND ACCESSORIES:
1
COMPRESSOR(S) SHALL HAVE AT MINIMUM FOUR (4) YEAR EXTENDED WARRANTY.
2
PROVIDE UNIT WITH FACTORY INSTALLED LOW PRESSURE SWITCH, HIGH PRESSURE SWITCH, CRANKCASE
HEATER, AND FILTER DRIER.
3 CONDENSING UNIT AND MATCHING INDOOR DX COIL SHALL BE FURNISHED BY FURNACE MANUFACTURER.
4

5

6
MAINTAIN MINIMUM MANUFACTURERS RECOMMENDED CLEARANCES.
7
PROVIDE UNIT WITH LOUVERED COIL/HAIL GUARD.
8
PROVIDE UNIT WITH THERMAL OVERLOAD PROTECTION.
9
PROVIDE UNIT WITH TWO (2) STAGE SCROLL COMPRESSOR FOR TWO (2) STAGE COOLING.
10
PROVIDE UNIT WITH SOUND BLANKET AND MOTOR/BLOWER VIBRATION ISOLATION TO MINIMIZE UNIT NOISE.
CARRIER, TRANE, YORK, OR APPROVED EQUAL
FURNACE SCHEDULE
MARK MFG.
MODEL
TYPE
CONFIGURATION SIZE CFM
EXT.
S.P.
DRIVE
MOTOR
H.P.
RPM
NATURAL GAS FIRED FURNACE DATA
COND.
UNIT
ELECTRICAL DATA
REMARKS AND
ACCESSORIES
INPUT
(MBH)
OUTPUT
(MBH)
EFF.
FLUE
SIZE
FLUE TYPE
MCA
(AMPS)
MOCP
(AMPS)
VOLTAGE/
PHASE
F-1 CARRIER 58MEC UPFLOW
100-20
1,600
0.5
DIRECT
1.0
1,050
100.0 93.0 93% 3"
CONCENTRIC CU-1
15.9 20
 SEE BELOW
F-2 CARRIER 58MEC HORIZONTAL 060-12 800 0.5 DIRECT 1/2
1,050
60.0 56.0 93% 2" CONCENTRIC CU-2 11.0 15  SEE BELOW
F-3 CARRIER 58MEC HORIZONTAL 080-12
1,200
0.5 DIRECT 1/2
1,050
80.0 75.0 94% 2" CONCENTRIC CU-3 11.0 15  SEE BELOW
F-4 CARRIER 58MEC UPFLOW
100-20
1,600
1.0
DIRECT
1.0
1,050
100.0 93.0 93% 3"
CONCENTRIC CU-4
15.9 20 
SEE BELOW
F-5
CARRIER 58MEC HORIZONTAL
060-12 800 0.5
DIRECT 1/2
1,050
60.0 56.0 93%
2" CONCENTRIC CU-5
11.0 15
 SEE BELOW
F-6 CARRIER 58MEC HORIZONTAL 080-12
1,200
0.5 DIRECT 1/2
1,050
80.0 75.0 94% 2" CONCENTRIC CU-6 11.0 15  SEE BELOW
REMARKS AND ACCESSORIES
1
FURNISH UNIT WITH A TWENTY (20) YEAR LIMITED HEAT EXCHANGER WARRANTY AND ONE (1) YEAR PARTS AND LABOR WARRANTY.
2
PROVIDE WITH MATCHING CASED DX COOLING COIL BY FURNACE MANUFACTURER. UNIT SHALL BE SUITABLE FOR TWO (2) STAGE COOLING.
3
PROVIDE UNIT WITH 1" THICK FIBERGLASS FILTERS.
4
MAINTAIN MANUFACTURER'S MINIMUM CLEARANCES.
5
PROVIDE UNIT WITH AT MINIMUM FIVE (5) SPEED ECM MOTOR.
6
PROVIDE UNIT WITH AT MINIMUM TWO (2) STAGE NATURAL GAS HEAT.
7
PROVIDE UNIT WITH MANUFACTURER'S CONENTRIC VENT.
8
PROVIDE UNIT WITH 7-DAY PROGRAMMABLE THERMOSTAT CAPABLE OF CONTROLLING ALL UNIT FUNCTIONS.
CARRIER, TRANE, YORK, OR APPROVED EQUAL
ELECTRIC UNIT HEATER SCHEDULE
MARK MFG. SERVICE MODEL SIZE CFM
MOUNTING
HEIGHT
KW
VOLTAGE/
PHASE
MCA
(AMPS)
MOCP
(AMPS)
REMARKS AND
ACCESSORIES
UH-1
QMARK
STORAGE &
EQUIPMENT 108
MUH 05-81 350 7' - 6" 5.0  30.0 35 SEE BELOW
UH-2
QMARK
MECH. ROOM 134 MUH 03-21 350 7' - 6" 2.2  13.8 20 SEE BELOW
REMARKS AND ACCESSORIES:
1
MOUNTING HEIGHT IS FROM FINISHED FLOOR TO BOTTOM OF UNIT.
2
PROVIDE UNIT WITH THERMAL OVERLOAD PROTECTION.
3
PROVIDE WITH NON-FUSED ELECTRICAL DISCONNECT SWITCH WITH SINGLE POINT ELECTRICAL CONNECTION.
4
PROVIDE UNIT WITH AUTOMATIC RESET CONTROL.
5
PROVIDE UNIT WITH ADJUSTABLE DISCHARGE LOUVERS.
6
MAINTAIN MANUFACTURER'S MINIMUM RECOMMENDED CLEARANCES.
7
PROVIDE WITH UNIT MOUNTED THERMOSTAT.
MARKEL, QMARK, REZNOR, OR APPROVED EQUAL
LOUVER SCHEDULE
MARK MFG. DESCRIPTION MODEL/TYPE
SIZE
(INCHES)
CFM
FREE AREA
(SQ. FT.)
FACE VELOCITY
(FPM)
PRESSURE
DROP
(IN. H2O)
TYPE OF
FRAME AND
MOUNTING
MOUNTING
HEIGHT
SERVICE
REMARKS AND
ACCESSORIES
L-1
GREENHECK
COMBINATION
LOUVER/DAMPER
EAC-601 32 X 16 X 6 155 0.75 207 0.01 CHANNEL 16' - 4" VENT. AIR INTAKE SEE BELOW
L-2 GREENHECK
COMBINATION
LOUVER/DAMPER
EAC-601 32 X 16 X 6 460 0.75 614 0.05 CHANNEL 16' - 4" VENT. AIR INTAKE SEE BELOW
L-3 GREENHECK
COMBINATION
LOUVER/DAMPER
EAC-601 16 X 16 X 6 230 0.34 678 0.06 CHANNEL 8' - 0" VENT. AIR INTAKE SEE BELOW
REMARKS AND ACCESSORIES:
1 MOUNTING HEIGHT MEASURED FROM BOTTOM OF LOUVER TO TOP OF FINISHED FLOOR. REFER TO ARCHITECTURAL PLANS FOR FINISHED MOUNTING HEIGHT AND LOCATION.
2
SIZES ARE SPECIFIED AS: FIRST FIGURE-WIDTH, SECOND FIGURE-HEIGHT, AND THIRD FIGURE- DEPTH.
3 PROVIDE UNIT WITH EXTENDED SILL.
4 PROVIDE UNIT IN ALUMINUM CONSTRUCTION.
5 PROVIDE UNIT WITH ALUMINUM BIRD SCREEN.
6 PROVIDE UNIT WITH 70% KYNAR FINISH. COLOR TO BE SELECTED BY ARCHITECT.
7 INSTALL UNIT IN 18 GAUGE SHEETMETAL WALL SLEEVE.
8

GREENHECK, NCA, RUSKIN, OR APPROVED EQUAL
VENTILATING FAN SCHEDULE
PHYSICAL DATA PERFORMANCE DATA UNIT OPERATION CONTROL ELECTRICAL DATA
REMARKS AND
ACCESSORIES
MARK MFG. AREA SERVED
MODEL/
TYPE
SIZE
APPROX.
UNIT
WEIGHT
(LBS.)
MOUNTING
RATED
CFM
ESP
(IN. H2O)
DRIVE FRPM
MOTOR
TYPE
MOTOR
RPM
dBA SWITCH OCC. T-STAT WATTS HP
ELECT.
CHAR.
EF-1 GREENHECK MENS TOILET 133 SP A410 50 CEILING 300 0.15 DIRECT 826 ODP
1,000
36 X 121 ---  1-6
EF-2
GREENHECK JANITOR 131 SP A70 20 CEILING 40 0.15 DIRECT 697 ODP 850 29 X 20 ---  1-6
EF-3
GREENHECK WOMENS TOILET 113 SP
A410 50
CEILING
300 0.15
DIRECT
826
ODP
1,000
36
X 121 --- 
1-6
EF-4 GREENHECK TOILET 117 SP A90 20 CEILING 50 0.15 DIRECT 709 ODP 900 27 X 29 ---  1-6
EF-5 GREENHECK TOILET 124 SP A90 20 CEILING 50 0.15 DIRECT 709 ODP 900 27 X 29 ---  1-6
EF-6 GREENHECK TOILET 127 SP A90 20 CEILING 50 0.15 DIRECT 709 ODP 900 27 X 29 ---  1-6
EF-7 GREENHECK
STORAGE & EQUIPMENT 108
AP
A200 35
CEILING
200 0.15
DIRECT
850
ODP
900 39
X
48
--- 
1-6
EF-8
GREENHECK TOILET 208 SP
A90 20
CEILING
50 0.15
DIRECT
709
ODP
900
27 X
29
--- 
1-6
EF-9 GREENHECK ALTERNATE TOILET SP A110 25 CEILING 75 0.15 DIRECT 834 ODP 950 30 X 49 ---  1-7
EF-10 GREENHECK ALTERNATE TOILET SP A110 25 CEILING 75 0.15 DIRECT 834 ODP 950 30 X 49 ---  1-7
REMARKS AND ACCESSORIES:
1
PROVIDE UNIT WITH ALUMINUM INTAKE GRILLE WITH WHITE ENAMEL FINISH.
2
PROVIDE UNIT WITH ROUND DUCT CONNECTOR.
3
PROVIDE UNIT WITH CAST ALUMINUM BRICK VENT TERMINATION WITH 70% MINIMUM KYNAR FINISH AND INTEGRAL BACKDRAFT DAMPER (GREENHECK MODEL BVC OR EQUAL). COLOR TO BE SELECTED BY ARCHITECT.
4 PROVIDE UNIT WITH SOLID-STATE FAN SPEED CONTROL.
5 PROVIDE UNIT WITH VIBRATION ISOLATION KIT.
6 PROVIDE UNIT WITH THERMAL OVERLOAD PROTECTION.
7 THIS UNIT SHALL BE FURNISHED AS AN ALTERNATE. REFERENCE ARCHITECTURAL DRAWINGS FOR APPROPRIATE ALTERNATE NUMBER.
UNIT OPERATION CONTROL:
SWITCH - UNIT SHALL BE CONTROLLED BY INDEPENDENT PILOT LIT SWITCH.
OCC. - UNIT SHALL BE ELECTRICALLY INTERLOCKED WITH AND CONTROLLED BY ZONE LIGHT CONTROL.
T-STAT - NOT USED.
COOK, GREENHECK, PENNBARRY, OR APPROVED EQUAL
PACKAGED AIR CONDITIONING UNIT WITH NATURAL GAS HEAT SCHEDULE
UNIT PHYSICAL DATA COOLING PERFORMANCE NATURAL GAS HEAT PERFORMANCE ELECTRICAL DATA
REMARKS AND
ACCESSORIES
MARK MFG. MODEL SIZE CONFIG. REFRIG.
APPROX.
UNIT
WEIGHT
(LBS.)
OUTSIDE
AIR
(CFM)
SUPPLY FAN DATA COOLING CAP.
(S)EER @
AHRI COND.
INPUT
(MBH)
OUTPUT
(MBH)
AFUE
EFFICIENCY
(%)
TEMP.
RISE

VOLTAGE /
PHASE
MCA
(AMPS)
MOCP
(AMPS)
CFM
ESP
(IN. H20)
MOTOR
POWER
(BHP)
MOTOR
RPM
TOTAL
(MBH)
SENSIBLE
(MBH)
AC-1 CARRIER 48TCE
09
HORIZONTAL
R-410A
1,000
335
3,400
0.8
1.2
750 100.4 72.0 11.0 180.0 147.6 82% 46

40.0 50
1-24
AC-2 CARRIER 48TCE
09
HORIZONTAL
R-410A
1,000
335
3,400
0.8
1.2
750 100.4 72.0 11.0 180.0 147.6 82% 46

40.0 50
1-24
AC-3 CARRIER 48TCE
04
HORIZONTAL
R-410A 500 250
1,200
0.6 0.5 855 35.7 26.3 13.0 115.0 93.0 81%
72 
19.4 25
1-21
AC-4 CARRIER 48TCE
05
HORIZONTAL
R-410A 600 230
1,600
0.8 0.7 973 46.8 32.8 13.0 115.0 93.0 81% 59

23.5 30
1-21
AC-5 CARRIER 48ES
024
HORIZONTAL
R-410A 300 95 800 0.5 0.3
1,050
23.0 17.0 13.2 40.0 32.0 80% 50

19.7 30
1-16, 25
REMARKS AND ACCESSORIES:
1 
TEMPERATURE.
2 PROVIDE UNIT WITH THERMOSTATIC EXPANSION VALVES (TXV) ON ALL DX COILS.
3 PROVIDE UNIT WITH AT MINIMUM TWO (2) STAGE HEATING.
4
PROVIDE UNIT WITH STAINLESS STEEL HEAT EXCHANGER.
5
PROVIDE UNIT WITH HINGED, GASKETED CABINET ACCESS DOORS.
6 PROVIDE UNIT WITH AT MINIMUM 1" THICK, DOUBLE-WALL INSULATED HOUSING.
7
PROVIDE UNIT WITH 2" THICK, 30% EFFICIENT PLEATED FILTERS.
8 PROVIDE UNIT WITH MOTOR/BLOWER VIBRATION ISOLATION.
9 PROVIDE UNIT WITH HAIL-GUARD ON CONDENSING COIL.
10 PROVIDE UNIT WITH UNIT-MOUNTED, NON-FUSED WEATHERPROOF DISCONNECT SWITCH WITH SINGLE-POINT ELECTRICAL CONNECTION.
11
PROVIDE UNIT WITH THERMAL OVERLOAD PROTECTION.
12
PROVIDE UNIT WITH ONE (1) YEAR PARTS AND LABOR WARRANTY, FIVE (5) YEAR COMPRESSOR WARRANTY, AND TEN (10) YEAR HEAT EXCHANGER WARRANTY.
13
THE CONTRACTOR SHALL FURNISH AND INSTALL AN ADDITIONAL SHEAVE, IF NECESSARY, TO BRING AIR SYSTEM TO WITHIN 10% OF DESIGN.
14 MAINTAIN MANUFACTURER'S RECOMMENDED MINIMUM CLEARANCES.
15
PROVIDE UNIT WITH MANUFACTURER'S START-UP AND CERTIFIED REPORT. INSTALLING CONTRACTOR START-UP IS NOT ACCEPTABLE.
16
PROVIDE UNIT WITH 7-DAY PROGRAMMABLE THERMOSTAT CAPABLE OF CONTROLLING ALL UNIT FUNCTIONS.
17
PROVIDE UNIT WITH ELECTRICAL PHASE LOSS PROTECTION.
18 PROVIDE UNIT WITH MODULATING HOT GAS REHEAT FOR HUMIDITY CONTROL.
19
PROVIDE UNIT WITH RETURN AIR HUMIDITY SENSOR FOR CONTROL OF DEHUMIDIFICATION CYCLE.
20
PROVIDE UNIT WITH MODULATING OUTSIDE AIR DAMPER FOR CO2 DEMAND VENTILATION CONTROL.
21
PROVIDE UNIT WITH RETURN AIR MOUNTED CO2 SENSOR FOR DEMAND VENTILATION CONTROL.
22 PROVIDE UNIT WITH SMOKE DETECTOR MOUNTED IN THE RETURN-AIR STREAM TO SHUT DOWN UNIT OPERATION AND INITIATE AN ALARM CONDTION AT THE PRESENCE OF SMOKE.
23
PROVIDE UNIT WITH TWO (2) INDEPENDENT REFRIGERANT CIRCUITS FOR TWO (2) STAGE COOLING.
24
PROVIDE UNIT WITH FULLY-MODULATING ECONOMIZER WITH COMPARATIVE ENTHALPY CONTROL FOR AIRSIDE ECONOMIZER OPERATION.
25
PROVIDE UNIT WITH MANUAL OUTSIDE AIR DAMPER.
CARRIER, TRANE, YORK, OR APPROVED EQUAL