Product Data
38MG / 40MA / 40MB
Multi- Zone Ductless Split Syst em
Size 18k, 27k, 36k and 48k
INDUSTRY LEADING
FEATURES / BENEFITS
AN INEXPENSIVE AND CREATIVE
SOLUTION TO DESIGN PROBLEMS.
The 38MG / 40MA / 40MB ductless inverter driven multi- zone
system provides individual comfort control for up to 5 separate
zones. Two, three, four or five space- saving cassette, floor console,
high wall, or ducted fan coils can be matched with one outdoor
heat pump. The indoor fan coils are connected to the outdoor unit
by refrigerant tubing and wires.
The different styles of indoor units can be mounted in several
locations to accommodate the application. This selection of fan
coils permits inexpensive and creative solutions to design problems
such as:
S When adding air conditioning to spaces that are heated
by hydronic or electric heat and have no ductwork.
S Historical renovations or any application where
preserving the look of the original structure is essential.
S Commercial add- on jobs where the existing air
conditioning system cannot be stretched.
These compact indoor fan coil units take up very little space in the
room and do not obstruct windows. The fan coils are attractively
styled to blend with most room decors.
Advanced system components incorporate innovative technology
to provide reliable cooling and heating performance at low sound
levels.
Page view 0
1 2 3 4 5 6 ... 35 36

Summary of Contents

Page 1 - Product Data

Product Data38MG / 40MA / 40MBMulti- Zone Ductless Split Syst emSize 18k, 27k, 36k and 48kINDUSTRY LEADINGFEATURES / BENEFITSAN INEXPENSIVE AND CREATI

Page 2

10DIMENSIONS - OUTDOOR (CONTINUED)Fig. 7 – Outdoor Dimensions Size 27

Page 3 - MODEL NUMBER NOMENCLATURE

11DIMENSIONS - OUTDOOR (CONTINUED)Fig. 8 – Outdoor Dimensions Size 36

Page 4 - OUTDOOR UNITS

12DIMENSIONS - OUTDOOR (CONTINUED)Fig. 9 – Outdoor Dimensions Size 48

Page 5 - COMBINATION TABLE

13CLEARANCES - INDOOR6" (0.15m) min.5"(0.13m)min.6'5"(0.13m)min.(1.8m)CEILINGFLOORFig. 10 – High Wall clearanceFig. 11 – Cassette

Page 6 - DIMENSIONS - INDOOR

14CLEARANCES - INDOOR (CONTINUED)Fig. 12 – Ducted clearanceFig. 13 – Floor Console clearances

Page 7 - Fig. 4 – Ducted Dimensions

15CLEARANCES - OUTDOORADBAir-outletAir-inletCEFig. 14 – Clearances OutdoorUNITMinimum Valuein. (mm)A 24 (609)B 24 (609)C 24 (609)D 4 (101)E 4 (101)

Page 8 - Unit size 9 12

16PHYSICAL DATA - OUTDOORSystemSize 18 27 36 48Outdoor Model 38MGQC18---3 38MGQD27---3 38MGQF36---3 38MGQF48---3Max Number of Zones 2 3 4 5Energy Star

Page 9 - DIMENSIONS - OUTDOOR

17PHYSICAL DATA - INDOORHigh WallIndoor UnitSize 9 12 18 24Model 40MAQB09B--3 40MAQB12B--3 40MAQB18B--3 40MAQB24B--3Unit Width In. 32.9 32.9 39 46.7Un

Page 10

18COOLING PERFORMANCEModelCooling Outdoor conditions (DB)Indoor Conditions DB75F(24C) 85F(29.5C) 95F(35C) 105F(40.5C)DB WB1869.8F(21C) 59F(15C)TC 18.0

Page 11

19PIPING REQUIREMENTSSystem size 18K 27K 36K 48KPipingMin. Piping Length ft (m) 10 (3) 10 (3) 10 (3) 10 (3)Standard Piping Length ft (m) 25 (7.5) 25 (

Page 12

2INVERTER TECHNOLOGYThe inverter driven compressor is designed to run at various inputpower frequencies (Hz) which controls the motor speed of thecomp

Page 13 - CLEARANCES - INDOOR

20APPLICATION DATAOutdoor Unit Model Cooling Capacity (Btu/h) Heating Capacity (Btu/h)38MGQC18---3 Type Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 1 Zone

Page 14 - Fig. 12 – Ducted clearance

21UNIT MOUNTING (INDOOR)Mounting Bracket – The fan coil units are furnished withmounting brackets or dedicated mounting holes to hang the unit.Support

Page 15 - CLEARANCES - OUTDOOR

22WIRELESS REMOTE CONTROL1. A wireless remote control is supplied for system operation.2. Each battery- operated wireless remote control may be usedto

Page 16 - PHYSICAL DATA - OUTDOOR

23AIR FLOW DATAHigh WallSystem size 9 12 18 24Indoor (CFM)Turbo 380 380 680 870High 360 360 650 780Medium 290 300 450 620Low 210 210 310 520CassetteSy

Page 17 - PHYSICAL DATA - INDOOR

24ELECTRICAL DATAHigh WallUNIT SIZESystem Voltage OPERATING VOLTAGE INDOOR FANVOLT / PHASE / HZ MAX / MIN V-PH-HZ FLA HP W9208-230/1/60 253 / 187 208-

Page 18 - HEATI NG PERFORMANCE

25FAN PERFORMANCES (DUCTED UNITS)Static pressure curve (static pressure deducted)Code 0 1 2 3 4 Max Static PressureSizes9&12 0.00 0.04 0.08 0.12 0

Page 19 - PIPING REQUIREMENTS

26Fig. 18 – 18KFig. 19 – 24K

Page 20

27WIRING DIAGRAMSFig. 20 – Wiring Diagrams 18kOUTDOOR UNIT CONTROL BOARD SIZE 18CODE PART NAMECN18/CN19/CN22 Output:Pin5&6(12V) Pin1-Pin4:Pulse wa

Page 21 - Long Line Applications:

28Fig. 21 – Wiring Diagrams 27kOUTDOOR UNIT CONTROL BOARD SIZE 27CODE PART NAMECN18/CN19/CN22 Output:Pin5&6(12V) Pin1-Pin4:Pulse waveform,(0-12V)C

Page 22 - SEQUENCE OF OPERATION

29Fig. 22 – Wiring Diagram 36kOUTDOOR UNIT CONTROL BOARD SIZE 36CODE PART NAMECN17/CN18/CN19/CN20/CN21 Output:Pin5&6(12V) Pin1-Pin4:Pulse waveform

Page 23 - SOUND PRESSURE

3MODEL NUMBER NOMENCLATUREBQDB=ALLSYSTEM TYPEQ =HEATPUMPNOT USEDINDOOR UNIT40 MB 30940 = FAN COIL UNITMA =HIGHWALLMB = CASSETTE, DUCTED, FLOOR CONSOLE

Page 24 - MAX STATIC PRESSURE - DUCTED

30Fig. 23 – Wiring Diagrams 48KOUTDOOR UNIT CONTROL BOARD SIZE 48CODE PART NAMECN1,CN3、P-1 Power input: 230V ACCN2,CN4 Output: Power output for DRIVER

Page 25 - Fig. 17 – 9K and 12K

31GUIDE SPECIFICATIONSHORIZONTAL DISCHARGE OUTDOOR UNITSSize Range:1 1/2, 2 1/4, 3 and 4 Ton Nominal Cooling and Heating CapacityCarrier Model Number:

Page 26 - Fig. 19 – 24K

32GUIDE SPECIFICATIONSINDOOR WALL- MOUNTED DUCTLESS UNITSSize Range: 3/4 to 2 Ton Nominal Cooling and Heating CapacityCarrier Model Number: 40MAQPART1

Page 27 - WIRING DIAGRAMS

33GUIDE SPECIFICATIONSINDOOR CASSETTE DUCTLESS UNITSSize Range: 3/4 to 1 1/2 Ton Nominal Cooling and Heating CapacityCarrier Model Number: 40MB*CPART

Page 28 - Fig. 21 – Wiring Diagrams 27k

34GUIDE SPECIFICATIONSINDOOR DUCTED UNITSSize Range: 3/4 to 2 Ton Nominal Cooling and Heating CapacityCarrier Model Number: 40MB*DPART 1 - GENERAL1.01

Page 29 - Fig. 22 – Wiring Diagram 36k

35GUIDE SPECIFICATIONSINDOOR FLOOR CONSOLE DUCTLESS UNITSSize Range: 3/4 to 1 Ton Nominal Cooling and Heating CapacityCarrier Model Number: 40MB*FPART

Page 30 - Fig. 23 – Wiring Diagrams 48K

36Copyright 2015 Carrier Co rp. S 7310 W. Morris St. S Indianapolis, IN 46231Manufacturer reserves the right to change, at any time, specifications an

Page 31 - PART 2 – PRODUCTS

4STANDARD FEATURES AND ACCESSORIESEase of InstallationMounting Bracket SLow Voltage Controls SComfort FeaturesMicroprocessor Control SWired Remote Con

Page 32

5COMBINATION TABLEIndoor Unit Nominal Unit Btuh Indoor Model Number Outdoor Model NumberHigh Wall9,000 40MAQB09B--338MGQC18---312,000 40MAQB12B--3Cass

Page 33

6DIMENSIONS - INDOORFig. 2 – High Wall DimensionsUnit Size W In. (mm) D In. (mm) H In. (mm)Operating WeightLbs. (kg)9K/12K 32.9(835) 7.8(198) 11.0(280

Page 34 - PART 2 - PRODUCTS

7DIMENSIONS - INDOOR (CONTINUED)Fig. 4 – Ducted DimensionsOutline dimensions in(mm) Air outlet opening size in(mm)Air return opening sizein(mm)HangerB

Page 35

8DIMENSIONS - INDOOR (CONTINUED)Fig. 5 – Floor Console DimensionsUnit size 9 12Height in (mm) 8.27 (210) 8.27 (210)Width in (mm) 27.56 (700) 27.56 (70

Page 36 - Catalog No. 38MG- 02PD

9DIMENSIONS - OUTDOORUnit Size 18 27 36 48Height in (mm) 27.56(700) 31.89(810) 31.89(810) 36.93(1369)Width in (mm) 33.27(845) 37.20(945) 37.20(945) 53