Rev. (0) - 201303502823 INSTALLATION MANUALCarrier is committed to continuously improving its products according to national and international standar
8 9. SELECTING INSTALLATION LOCATION OF OUTOOR UNIT 9.1 INSTALLATION LOCATIONS The outdoor unit can be installed in any outside location, on a wal
9 SELECTING INSTALLATION LOCATION OF OUTOOR UNIT (Cont.) CONSIDERATIONS FOR SELECTING INSTALLATION LOCATION (Cont.) Select the installation locati
10 SELECTING INSTALLATION LOCATION OF OUTOOR UNIT (Cont.) 9.3 MINIMUM CLEARANCES WHEN SELECTING INSTALLATION LOCATION FOR SINGLE OU
11 SELECTING INSTALLATION LOCATION OF OUTOOR UNIT (Cont.) 9.4 MINIMUM CLEARANCES WHEN SELECTING INSTALLATION LOCATION FOR SERIAL I
12 10. INSTALLATION LOCATION CHECK LIST (A) INDOOR UNIT - The installation location is close to the outdoor unit - The wall hole (required to
13 11. INSTALLATION ACCESSORIES 11.1 STANDARD INSTALLATION ACCESSORIES SUPPLIED FROM THE FACTORY DESCREPTION SHAPE QTY USE Battery 1.5 volt si
14 INSTALLATION ACCESSORIES (Cont.) 11.4 OTHER INSTALLATION ACCESSORIES Not supplied from the factory but must be used in the installation field
15 12. INSTALLATION CHART 1) Installing outdoor unit 5) Connecting refrigerant piping lines 9) Air purging with a vacuum pump 2) Drilling hole thru
16 13. INDOOR UNIT INSTALLATION 13-1 PREPARATION STEPS BEFORE INSTALLATION STEP (1) :Selecting Wall Hole Location Back right or Back left pipi
17 INDOOR UNIT INSTALLATION (Cont.) 13-2 INSTALLATION STEPS OF INDOOR UNIT Step (1) : Installing wall hang bracket • Allow the clearance space
TABLE OF CONTENTS PAGE NO. 1. GENERAL NOTES TO INSTALLER 1 2. PRECAUTIO
18 INSTALLATION OF INDOOR UNIT (Cont.) INSTALLATION STEPS OF INDOOR UNIT (Cont.) Step (4): Install indoor unit on the wall hang bracket 1. P
19 14. REMOTE CONTROL INSTALLATION 14-1 HOW TO INSERT BATTERIES: (a) Remove the cover of battery compartment at the back of the remote control
20 REMOTE CONTROL INSTALLATION (Cont.) 14-2 INSTRUCTIONS OF USING WIRELESS REMOTE CONTROL 1- The remote control must be directed toward the recei
212 4 1 3 4 Final Assembly of wall support 2 4 1 3 4 A 15. OUTDOOR UNIT INSTALLATION 15.1 PREPARATION STEPS BEFORE INSTALLATION a. Put packe
22 16. CONNECTING REFRIGERANT PIPING LINES 16-1 REFRIGERANT CONNECTIONS CHART (1) Pipes Flaring (2) Pipes Connections (3) Air Purging (4) Lea
23 CONNECTING REFRIGERANT PIPING LINES (Cont.) 16-2 POSSIBLE OUTLET LOCATIONS OF REFRIGERANT PIPING LINES FROM INDOOR UNIT The refrigerant piping l
24 CONNECTING REFRIGERANT PIPING LINES (Cont.) 16-3 INSTRUCTIONS OF CONNECTIING REFRIGERANT PIPING LINES Avoid excessive height difference b
25L CONNECTING REFRIGERANT PIPING LINES (Cont.) 16-4 USE OF REFRIGERANT PIPING LINES The following data refers to the use of refrigerant piping
26 CONNECTING REFRIGERANT PIPING LINES (Cont.) 16-5 DIAMETERS OF REFRIGERANT PIPING LINES UP TO 25 METER LENGTH System Model Gas line diameter L
27 CONNECTING REFRIGERANT PIPING (Cont.) 16-7 DESCRIPTION OF REFRIGERANT CONNECTIONS OF OUTDOOR UNIT Refrigerant Connections Details
1 1. GENERAL NOTES TO INSTALLER Split room air conditioner has been carefully designed and manufactured under strict Quality Control conditions. T
28Corrugated Cutting Wrap Cutting CONNECTING REFRIGERANT PIPING LINES (Cont.) 16-11 STEPS OF PREPARING REFRIGERANT PIPING LINES BEFORE CONNECTION
29 CONNECTING REFRIGERANT PIPING LINES (Cont.) STEPS OF PREPARING REFRIGERANT PIPING LINES BEFORE CONNECTIONS (Cont.) STEP (4): Removing protecti
30 CONNECTING REFRIGERANT PIPING (Cont.) 16-12 STEPS OF CONNECTING REFRIGERANT PIPING LINES TO INDOOR UNIT Connecting gas and liquid piping lin
31 CONNECTING REFRIGERANT PIPING LINES (Cont.) 16-14 AIR PURGING OF INDOOR UNIT AND REFRIGERANT PIPING LINES 16-14-1 INTRODUCTION • In some count
32 CONNECTING REFRIGERANT PIPING LINES (Cont.) AIR PURGING OF INDOOR UNIT AND REFRIGERANT PIPING LINES USING REFRIGERANT CONTAINED IN OUTDOOR UNI
33 CONNECTING REFRIGERANT PIPING LINES (Cont.) AIR PURGING OF INDOOR UNIT AND REFRIGERANT PIPING LINES (Cont.) 16-14-3 AIR PURGING OF INDOOR UNI
34 CONNECTING REFRIGERANT PIPING LINES (Cont.) 16-15 PUMPING DOWN (RE-INSTALLATION) • INTRODUCTION Pump down means collecting all the refriger
35 CONNECTING REFRIGERANT PIPING LINES (Cont.) 16-16 REFRIGERANT LEAK CHECK After connecting the refrigerant piping lines with both outdoor and
36 17. CONNECTING CONDENSATE DRAIN LINE 17-1 SIZE OF CONDENSATE DRAIN LINE The condensate drain line (not supplied) for indoor unit must be made
37 CONNECTING CONDENSATE DRAIN LINE (Cont.) 17-3 INSTRUCTIONS OF CONNECTING CONDENSATE DRAIN LINE (1) The drain hose must be gradually inclined
2 2. PRECAUTIONS BEFORE INSTALLATION SAFETY PRECAUTIONS • Installation and maintenance of air conditioning equipment can be hazardous due to sys
38 18. CONNECTING ELECTRICAL WIRING 18-1 ELECTRICAL WIRING BETWEEN ELECTRICAL POWER SUPPLY AND CIRCUIT BREAKER OF AIR CONDITIONER All electrical
39 CONNECTING ELECTRICAL WIRING (Cont.) 18-2 ELECTRICAL WIRING BETWEEN INDOOR UNIT, OUTDOOR UNIT AND CIRCUIT BREAKER OF AIR CONDITIONER All elect
40 CONNECTING ELECTRICAL WIRING (Cont.) 18-3 ELECTRICAL DATA Split System Model Starting Current (Note 1) Nominal System Power Supply Electrical Co
41 CONNECTING ELECTRICAL WIRING (Cont.) 18-4 CONNECTING ELECTRICAL WIRING TO OUTDOOR UNIT connect electrical cables to the terminal block of outd
42 CONNECTING ELECTRICAL WIRING (Cont.) 18-6 FIELD CONNECTIONS ELECTRICAL WIRING OF COOL ONLY AND HEAT PUMP SYSTEMS LEGEND Eart
43Piping Decorative TapeSaddles 19. FINISHING INSTALLATION FINISHING STEPS FOR INSTALLATION a. Tie together refrigerant piping, drain h
44 20. TEST RUNNING 20.1 PRECAUTIONS BEFORE TEST RUNNING - Operate test running after checking that the air filters and front panel are properly m
45 TEST RUNNING (Cont.) 20.3 STEPS FOR COOLING TEST RUNNING a. Move circuit breaker to ON position. b. Operate the system for cooling operatio
46 21. AIR CIRCULATION FOR INDOOR UNIT 21-1 AIR FLOW DIRECTION CONTROL Air is supplied into the room through the supply air louvers located o
47 AIR CIRCULATION FOR INDOOR UNIT (Cont.) 21-3 For model 36K ↕ SWING Function To automatically ↕ swing the horizontal louvers for the verti
3 3. SPLIT SYSTEM DESCRIPTION 1: Remote control signal receiver. 2: LCD Display panel 3: Panel frame 4: Chassis 5: Front panel 6: Horizontal su
48 AIR CIRCULATION FOR INDOOR UNIT (Cont.) 21-4 For model 30K To set the horizontal supply air direction (left - right) for Size 30K • Adjust
49 22. AFTER INSTALLATION CHECK LIST 22.1 INDOOR UNIT a. The installation location is adequate. b. The unit is solidly mounted and leveled. c.
50 AFTER INSTALLATION CHECK LIST (Cont.) 22.6 FINISHING INSTALLATION a. The refrigerant piping lines, electrical cables and drain hose are lumped
51 23. SELF DIAGNOSTIC FUNCTION FOR MALFUNCTIONS DETECTION EXPLAINATION OF SELF-DIAGNOSTIC FUNCTION - Self-diagnostic function is the key for succ
www.miraco.com.eg
4 4. MODELS HEAT PUMP Cool only System Model Indoor Unit Model Outdoor Unit Model System Model Indoor Unit Model Ou
5 6. DIMENSIONS AND WEIGHT OF INDOOR UNIT DIMENSIONS (mm) Indoor Unit Model Type Dimensions (mm) Weight Kg W H D 42KHET
6 8. SELECTING INSTALLATION LOCATION OF INDOOR UNIT 8.1 CONSIDERATIONS OF SELECTING INSTALLATION LOCATION Select installation location which a
7 SELECTING INSTALLATION LOCATION OF INDOOR UNIT (Cont.) CONSIDERATIONS OF SELECTING INSTALLATION LOCATION (Cont.) Select installation location wh