INSTALLATION MANUAL
Carrier is committed to continuously improving its products according to national and international standards
to ensure the highest quality and reliability standards, and to meet market regulations and requirements.
All specications subject to change without prior notice according to Carrier policy of continuous development.
Hi Wall Split Air Conditioners
53KHET 30-36 Cool Only
53QHET 30-36 & 53QHE36
Heat Pump
220-240V ~ 50Hz 1Ph
R
2
2
Quality
Management System
ISO 9001 : 2008
Certicate No.: QS-5519HH
Enviromental
Management System
ISO 14001 : 2004
Certicate No : 12 104 30334 TMS
Safety
Management System
BS OHSAS 18001 : 2007
Certicate No : 12 116 30334 TMS
Page view 0
1 2 3 4 5 6 ... 53 54

Summary of Contents

Page 1 - Heat Pump

Rev. (0) - 201303502823 INSTALLATION MANUALCarrier is committed to continuously improving its products according to national and international standar

Page 2 - TABLE OF CONTENTS

8 9. SELECTING INSTALLATION LOCATION OF OUTOOR UNIT 9.1 INSTALLATION LOCATIONS The outdoor unit can be installed in any outside location, on a wal

Page 3

9 SELECTING INSTALLATION LOCATION OF OUTOOR UNIT (Cont.) CONSIDERATIONS FOR SELECTING INSTALLATION LOCATION (Cont.) Select the installation locati

Page 4

10 SELECTING INSTALLATION LOCATION OF OUTOOR UNIT (Cont.) 9.3 MINIMUM CLEARANCES WHEN SELECTING INSTALLATION LOCATION FOR SINGLE OU

Page 5 - Air outlet

11 SELECTING INSTALLATION LOCATION OF OUTOOR UNIT (Cont.) 9.4 MINIMUM CLEARANCES WHEN SELECTING INSTALLATION LOCATION FOR SERIAL I

Page 6

12 10. INSTALLATION LOCATION CHECK LIST (A) INDOOR UNIT - The installation location is close to the outdoor unit - The wall hole (required to

Page 7

13 11. INSTALLATION ACCESSORIES 11.1 STANDARD INSTALLATION ACCESSORIES SUPPLIED FROM THE FACTORY DESCREPTION SHAPE QTY USE Battery 1.5 volt si

Page 8

14 INSTALLATION ACCESSORIES (Cont.) 11.4 OTHER INSTALLATION ACCESSORIES Not supplied from the factory but must be used in the installation field

Page 9 - 1900 mm

15 12. INSTALLATION CHART 1) Installing outdoor unit 5) Connecting refrigerant piping lines 9) Air purging with a vacuum pump 2) Drilling hole thru

Page 10 - 9.1 INSTALLATION LOCATIONS

16 13. INDOOR UNIT INSTALLATION 13-1 PREPARATION STEPS BEFORE INSTALLATION STEP (1) :Selecting Wall Hole Location Back right or Back left pipi

Page 11

17 INDOOR UNIT INSTALLATION (Cont.) 13-2 INSTALLATION STEPS OF INDOOR UNIT Step (1) : Installing wall hang bracket • Allow the clearance space

Page 12

TABLE OF CONTENTS PAGE NO. 1. GENERAL NOTES TO INSTALLER 1 2. PRECAUTIO

Page 13

18 INSTALLATION OF INDOOR UNIT (Cont.) INSTALLATION STEPS OF INDOOR UNIT (Cont.) Step (4): Install indoor unit on the wall hang bracket 1. P

Page 14

19 14. REMOTE CONTROL INSTALLATION 14-1 HOW TO INSERT BATTERIES: (a) Remove the cover of battery compartment at the back of the remote control

Page 15 - DESCREPTION SHAPE QTY USE

20 REMOTE CONTROL INSTALLATION (Cont.) 14-2 INSTRUCTIONS OF USING WIRELESS REMOTE CONTROL 1- The remote control must be directed toward the recei

Page 16

212 4 1 3 4 Final Assembly of wall support 2 4 1 3 4 A 15. OUTDOOR UNIT INSTALLATION 15.1 PREPARATION STEPS BEFORE INSTALLATION a. Put packe

Page 17 - 12. INSTALLATION CHART

22 16. CONNECTING REFRIGERANT PIPING LINES 16-1 REFRIGERANT CONNECTIONS CHART (1) Pipes Flaring (2) Pipes Connections (3) Air Purging (4) Lea

Page 18

23 CONNECTING REFRIGERANT PIPING LINES (Cont.) 16-2 POSSIBLE OUTLET LOCATIONS OF REFRIGERANT PIPING LINES FROM INDOOR UNIT The refrigerant piping l

Page 19

24 CONNECTING REFRIGERANT PIPING LINES (Cont.) 16-3 INSTRUCTIONS OF CONNECTIING REFRIGERANT PIPING LINES  Avoid excessive height difference b

Page 20

25L CONNECTING REFRIGERANT PIPING LINES (Cont.) 16-4 USE OF REFRIGERANT PIPING LINES The following data refers to the use of refrigerant piping

Page 21

26 CONNECTING REFRIGERANT PIPING LINES (Cont.) 16-5 DIAMETERS OF REFRIGERANT PIPING LINES UP TO 25 METER LENGTH System Model Gas line diameter L

Page 22

27 CONNECTING REFRIGERANT PIPING (Cont.) 16-7 DESCRIPTION OF REFRIGERANT CONNECTIONS OF OUTDOOR UNIT Refrigerant Connections Details

Page 23

1 1. GENERAL NOTES TO INSTALLER Split room air conditioner has been carefully designed and manufactured under strict Quality Control conditions. T

Page 24

28Corrugated Cutting Wrap Cutting CONNECTING REFRIGERANT PIPING LINES (Cont.) 16-11 STEPS OF PREPARING REFRIGERANT PIPING LINES BEFORE CONNECTION

Page 25

29 CONNECTING REFRIGERANT PIPING LINES (Cont.) STEPS OF PREPARING REFRIGERANT PIPING LINES BEFORE CONNECTIONS (Cont.) STEP (4): Removing protecti

Page 26 - Recommended

30 CONNECTING REFRIGERANT PIPING (Cont.) 16-12 STEPS OF CONNECTING REFRIGERANT PIPING LINES TO INDOOR UNIT Connecting gas and liquid piping lin

Page 27

31 CONNECTING REFRIGERANT PIPING LINES (Cont.) 16-14 AIR PURGING OF INDOOR UNIT AND REFRIGERANT PIPING LINES 16-14-1 INTRODUCTION • In some count

Page 28

32 CONNECTING REFRIGERANT PIPING LINES (Cont.) AIR PURGING OF INDOOR UNIT AND REFRIGERANT PIPING LINES USING REFRIGERANT CONTAINED IN OUTDOOR UNI

Page 29

33 CONNECTING REFRIGERANT PIPING LINES (Cont.) AIR PURGING OF INDOOR UNIT AND REFRIGERANT PIPING LINES (Cont.) 16-14-3 AIR PURGING OF INDOOR UNI

Page 30

34 CONNECTING REFRIGERANT PIPING LINES (Cont.) 16-15 PUMPING DOWN (RE-INSTALLATION) • INTRODUCTION Pump down means collecting all the refriger

Page 31

35 CONNECTING REFRIGERANT PIPING LINES (Cont.) 16-16 REFRIGERANT LEAK CHECK After connecting the refrigerant piping lines with both outdoor and

Page 32

36 17. CONNECTING CONDENSATE DRAIN LINE 17-1 SIZE OF CONDENSATE DRAIN LINE The condensate drain line (not supplied) for indoor unit must be made

Page 33

37 CONNECTING CONDENSATE DRAIN LINE (Cont.) 17-3 INSTRUCTIONS OF CONNECTING CONDENSATE DRAIN LINE (1) The drain hose must be gradually inclined

Page 34

2 2. PRECAUTIONS BEFORE INSTALLATION SAFETY PRECAUTIONS • Installation and maintenance of air conditioning equipment can be hazardous due to sys

Page 35

38 18. CONNECTING ELECTRICAL WIRING 18-1 ELECTRICAL WIRING BETWEEN ELECTRICAL POWER SUPPLY AND CIRCUIT BREAKER OF AIR CONDITIONER All electrical

Page 36

39 CONNECTING ELECTRICAL WIRING (Cont.) 18-2 ELECTRICAL WIRING BETWEEN INDOOR UNIT, OUTDOOR UNIT AND CIRCUIT BREAKER OF AIR CONDITIONER All elect

Page 37

40 CONNECTING ELECTRICAL WIRING (Cont.) 18-3 ELECTRICAL DATA Split System Model Starting Current (Note 1) Nominal System Power Supply Electrical Co

Page 38

41 CONNECTING ELECTRICAL WIRING (Cont.) 18-4 CONNECTING ELECTRICAL WIRING TO OUTDOOR UNIT connect electrical cables to the terminal block of outd

Page 39 - Avoid any rise in drain line

42 CONNECTING ELECTRICAL WIRING (Cont.) 18-6 FIELD CONNECTIONS ELECTRICAL WIRING OF COOL ONLY AND HEAT PUMP SYSTEMS LEGEND Eart

Page 40

43Piping Decorative TapeSaddles 19. FINISHING INSTALLATION FINISHING STEPS FOR INSTALLATION a. Tie together refrigerant piping, drain h

Page 41

44 20. TEST RUNNING 20.1 PRECAUTIONS BEFORE TEST RUNNING - Operate test running after checking that the air filters and front panel are properly m

Page 42 - (Note 1)

45 TEST RUNNING (Cont.) 20.3 STEPS FOR COOLING TEST RUNNING a. Move circuit breaker to ON position. b. Operate the system for cooling operatio

Page 43

46 21. AIR CIRCULATION FOR INDOOR UNIT 21-1 AIR FLOW DIRECTION CONTROL  Air is supplied into the room through the supply air louvers located o

Page 44 - 220-240V ~ 50Hz 1Ph

47 AIR CIRCULATION FOR INDOOR UNIT (Cont.) 21-3 For model 36K ↕ SWING Function To automatically ↕ swing the horizontal louvers for the verti

Page 45 - 19. FINISHING INSTALLATION

3 3. SPLIT SYSTEM DESCRIPTION 1: Remote control signal receiver. 2: LCD Display panel 3: Panel frame 4: Chassis 5: Front panel 6: Horizontal su

Page 46 - 20. TEST RUNNING

48 AIR CIRCULATION FOR INDOOR UNIT (Cont.) 21-4 For model 30K To set the horizontal supply air direction (left - right) for Size 30K • Adjust

Page 47 - TEST RUNNING (Cont.)

49 22. AFTER INSTALLATION CHECK LIST 22.1 INDOOR UNIT a. The installation location is adequate. b. The unit is solidly mounted and leveled. c.

Page 48 - SWING Function

50 AFTER INSTALLATION CHECK LIST (Cont.) 22.6 FINISHING INSTALLATION a. The refrigerant piping lines, electrical cables and drain hose are lumped

Page 49 - ↔ SWING Function

51 23. SELF DIAGNOSTIC FUNCTION FOR MALFUNCTIONS DETECTION EXPLAINATION OF SELF-DIAGNOSTIC FUNCTION - Self-diagnostic function is the key for succ

Page 50 - (three places)

www.miraco.com.eg

Page 51

4 4. MODELS HEAT PUMP Cool only System Model Indoor Unit Model Outdoor Unit Model System Model Indoor Unit Model Ou

Page 52

5 6. DIMENSIONS AND WEIGHT OF INDOOR UNIT DIMENSIONS (mm) Indoor Unit Model Type Dimensions (mm) Weight Kg W H D 42KHET

Page 53

6 8. SELECTING INSTALLATION LOCATION OF INDOOR UNIT 8.1 CONSIDERATIONS OF SELECTING INSTALLATION LOCATION Select installation location which a

Page 54 - www.miraco.com.eg

7 SELECTING INSTALLATION LOCATION OF INDOOR UNIT (Cont.) CONSIDERATIONS OF SELECTING INSTALLATION LOCATION (Cont.) Select installation location wh

Comments to this Manuals

No comments