Installation Instructions
Part No. 50DJ900021
SAFETY CONSIDERATIONS
Before beginning any modification, be certain that the
main line electrical disconnect switch is in the OFF
position. Electric shock could result. Tag disconnect switch
with suitable warning labels.
Installation and servicing of air-conditioning equip-
ment can be hazardous due to system pressure, flammable
gases, and electrical components. Only trained and qualified
personnel should install, repair, or service air-conditioning
equipment.
Untrained personnel can perform the basic maintenance
functions of cleaning coils and replacing filters. All other
operations should be performed by trained service person-
nel. When working on air-conditioning equipment, observe
precautions in literature, tags and labels attached to unit, and
other safety precautions that may apply. Follow all safety
codes.
GENERAL
This accessory space temperature reset package consists
of a thermistor and potentiometer. See Table 1. It is used to
elevate the supply-air temperature in 48DK,FK,JK and
50DK,DY,FK,FY,JK,JY variable air volume units in order
to avoid over-cooling of the space while maintaining occu-
pied space air motion and ventilation.
Table 1 Package Contents
ITEM QUANTITY PART NO.
Thermistor Sensor with
35-ft Leads
1 HH79NZ014
Temperature Reset
Potentiometer
1 32GB500574
INSTALLATION
Thermistor (T10) must be wired in series with poten-
tiometer (P7). The two of them must then be wired to the
appropriate terminal block in the unit control box. All wir-
ing must conform to NEC (National Electrical Code) and
local codes. To install the accessory space temperature reset
package:
1. Turn off all power to unit.
2. Install thermistor T10 in the occupied space to be con-
trolled. Locate the thermistor in the space with the great-
est cooling load, so that the leaving-air temperature is not
reset too much to cool the space with the most demand-
ing cooling load.
3. Mount potentiometer in the unit control box or some other
secure indoor location. Set the potentiometer for the tem-
perature at which reset is to begin. When the occupied
space temperature drops below this setting, reset will
occur.
4. Wire thermistor and potentiometer as shown in Fig. 1.
The thermistor has 35-ft leads, but additional wire may
be spliced in to make the leads longer.
NOTE: When splicing additional wires, solder the wires
at the splices to achieve maximum continuity.
5. Set DIP (dual in-line package) switch no. 2 on the main
VAV (variable air volume) control board to the ON
position to enable the reset function. See Fig. 2.
6. Find potentiometer P3 in the center of the accessory reset
board in the unit control box, and set it for the maximum
reset temperature to be allowed when the unit is in the
Reset mode. See Fig. 3.
7. Multiple T10 space sensors may be used. Multiple (4
or 9) sensors (part no. HH79NZ014) may be wired as
shown in Fig. 4 with total wiring not to exceed 1000 ft.
12
15
1
2
TB3
1
2
TB1
32GB500574
TB2
POTENTIOMETER
P7
THERMISTOR
T10
12
15
1
2
TB4
1
2
TB1
32GB500574
TB2
POTENTIOMETER
P7
THERMISTOR
T10
SIZES 034-048
SIZES 054-074
LEGEND
TB Terminal Block
Fig. 1 Accessory Wiring Detail
48/50DK,FK,JK034-074
50DY,FY,JY034-074
Accessory Space Temperature Reset Package
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 1
Tab 1a 1b
PC 111 Catalog No. 564-976 Printed in U.S.A. Form 48/50D,F,J-3SI Pg 1 9-98 Replaces: 48/50D-4SI
Page view 0
1 2 3 4

Summary of Contents

Page 1

Installation InstructionsPart No. 50DJ900021SAFETY CONSIDERATIONSBefore beginning any modification, be certain that themain line electrical disconnect

Page 2 - VAV — Variable Air Volume

Fig. 2 — Main Variable Air Volume Control BoardLEGENDP—PotentiometerVAV — Variable Air VolumeFig. 3 — Accessory Reset Board2

Page 3 - OPERATION

OPERATIONIf space temperature is equal or less than the reset set point(T10 < P7), the LED (light-emitting diode) 2-digit displayon the unit displa

Page 4 - Tab 1a 1b

Outdoor-Air Temperature Reset — Space tempera-ture is the recommended means of initiating reset because itensures that the space is adequately cooled