NOTE: Read the entire instruction manual before starting the installation. These instructions must be affixed on or adjacent to the boiler.
This symbol indicates a change since the last issue.
Index Page
SAFETY CONSIDERATIONS.....................................................................................................................................................................................3
INTRODUCTION..........................................................................................................................................................................................................3
BOILER RATINGS AND CAPACITIES ....................................................................................................................................................................4
ama
ASME
®
A95139
Continuous Pilot
MODEL BS1
A90003
Electronic Intermittent Ignition
MODEL BS2
Installation, Start-Up, and Operating Instructions
BS1 and BS2
Series B
Gas-Fired
Natural Draft Steam Boilers
Sizes 70,000 through 299,000
Form: IM-BS1A-05 Cancels: IM-BS1A-04 Printed in U.S.A. 8-03 Catalog No. 63BS-1A3
Page view 0
1 2 3 4 5 6 ... 31 32

Summary of Contents

Page 1 - Sizes 70,000 through 299,000

NOTE: Read the entire instruction manual before starting the installation. These instructions must be affixed on or adjacent to the boiler.This symbol

Page 2

IMPORTANT: The damper blade on factory-supplied vent damper has a 1/2-sq in. hole (approximately 3/4-in. diameter). On boilers equippedwith standing p

Page 3

At the time of removal of an existing boiler, the following items shall be followed with each appliance remaining connected to the common ventingsyste

Page 4

VENT DAMPER OPERATIONPROCEDURE 1—AUTOMATIC OPERATION OF VENT DAMPERFor safe, efficient operation, vent damper and all flue product carrying areas of a

Page 5

The boiler and its individual shutoff valve must be disconnected from gas supply piping system during any pressure testing of gas supply pipingsystem

Page 6

→ Fig. 12—Wiring Diagram for Intermittent Ignition Boilers with PS-802 Probe-Type Low Water Cut-OffNOTE: If any of the original wire as supplied with

Page 7

→ Fig. 13—Wiring Diagram for Standing Pilot Boilers with PS-802 Probe-Type Low Water Cut-OffNOTE: If any of the original wire as supplied with this ap

Page 8

Fig. 14—Wiring Diagrams for Intermittent Ignition Boilers with Float-Type Low Water Cut-OffNOTE: If any of the original wire as supplied with this app

Page 9 - TO SHOW COMMON MISTAKES

Fig. 15—Wiring Diagrams for Standing Pilot Boilers with Float-Type Low Water Cut-OffNOTE: If any of the original wire as supplied with this appliance

Page 10

The boiler, when installed, must be electrically grounded in accordance with requirements of the authority having jurisdiction, or in the absenceof su

Page 11

CONTROLS AND ACCESSORIESPROCEDURE 1—RELIEF VALVEThe relief valve should open automatically if boiler steam pressure exceeds pressure rating of valve (

Page 12

LOCATING THE BOILER...

Page 13 - * Outside diameter

B. BEFORE OPERATING, smell all around appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air andwill settle o

Page 14 - MOLEX PLUG

4. Remove lower front panel.5. Turn gas control knob clockwise to OFF position. (See Fig. 19.)6. Wait 5 minutes to clear out any gas. Then smell for g

Page 15

4. Allow boiler to fill until water runs out gauge drain valve, then close gauge drain valve.5. Continue to fill boiler until water reaches indicated

Page 16

The above is an example of a typical 1-pipe system. For larger systems or other types of systems such as 2-pipe systems or systems with convectorsor f

Page 17 - THERMOSTAT

If cleaning is necessary, repeat skimming and blowdown procedures above. Usually a long skim is sufficient to clean boiler.In more troublesome cases,

Page 18 - ELECTRONIC

3. Remove 2 screws attaching intermediate front panel to left and right side jacket panels.4. Remove draft diverter and intermediate front panel as 1

Page 19

SERVICE HINTSYou may avoid inconvenience and service calls by checking these points before you call for service.FOR YOUR SAFETYWHAT TO DO IF YOU SMELL

Page 20

REPAIR PARTSJacket—Section and Base PartsThis is a Repair Parts List—Not a Packing ListKEYNO.DESCRIPTIONPART NO.3 Section 4 Section 5 Section 6 Sectio

Page 21 - MATCH HOLDER

REPAIR PARTSGas Burners and Manifold PartsThis is a Repair Parts List—Not a Packing ListKEYNO.DESCRIPTIONPART NO.3 Section 4 Section 5 Section 6 Secti

Page 22 - SHARP INNER CONES

REPAIR PARTSKEY NO. DESCRIPTION PART NO.1 3/4-in. Relief Valve 157-00-012 3/4-in. Coupling 115-00-013 3/4-in. X 6-1/2-in. Nipple 146-07-0024 Steam Pre

Page 23

SAFETY CONSIDERATIONSInstalling and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified pers

Page 24

—30—

Page 25

A94328SERVICE TRAININGPackaged Service Training programs are an excellent way to increase yourknowledge of the equipment discussed in this manual, inc

Page 26 - FOR YOUR SAFETY

© 2003 CAC/BDP 7310 W. Morris St., Indianapolis, IN 46231 imbs1a05—32—Catalog No. 63BS-1A3

Page 27 - REPAIR PARTS

BOILER RATINGS AND CAPACITIESThe ratings marked "Net I=B=R Rating" indicate the amount of equivalent direct cast iron radiation each boiler

Page 28

FRESH AIR FOR COMBUSTIONProvision for combustion and ventilation air must be in accordance with Section 5.3 of NFGC, Air for Combustion and Ventilatio

Page 29

PROCEDURE 2—BOILER LOCATED IN CONFINED SPACEEXAMPLE 2A: ALL AIR FROM INSIDE THE BUILDINGThe confined space shall be provided with two permanent openin

Page 30

3. This boiler is equipped with two 2-1/2-in. supply connections and two 2-1/2-in. return connections, 1 each on both the left and right sidesof boile

Page 31 - SERVICE TRAINING

14. For pumped return systems, follow condensate pump or boiler feed pump manufacturer’s instructions for proper installation and hookup.15. In connec

Page 32 - Catalog No. 63BS-1A3

WRONG WAYMISSING TEE FOR SKIMMINGWRONG WAYTAKE OFFS MUST BE BETWEEN RISER & EQUALIZERWRONG WAYSWING JOINTS ARE MISSINGWRONG WAYDO NOT BULLHEAD,USE