Carrier 23XL User Manual

Browse online or download User Manual for Unknown Carrier 23XL. Carrier 23XL Product data

  • Download
  • Add to my manuals
  • Print
  • Page
    / 48
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
The 23XL screw chiller provides the
performance and reliability of a
centrifugal class machine by using
advanced engineering technology.
Optimized for low life cycle costs, the
23XL offers superior value in a
compact design.
Features/Benefits
Exceptional full and part load
efficiencies, coupled with a design
that is easy to install and main-
tain, provide low overall cost of
ownership.
The rugged, reliable, and fully
field serviceable compressor is de-
signed for a lifetime of trouble-
free operation.
A low leak, ASME certified, positive
pressure design uses environmen-
tally acceptable HCFC-22 or
HFC-134a refrigerant.
Innovative direct digital controls
combine an easy to use Local Inter-
face Device (LID) with sophisti-
cated capabilities.
Carrier’s factory testing program
ensures quality while providing
peace of mind and protecting your
chiller investment.
Low operating costs
Advanced internally and exter-
nally enhanced heat transfer sur-
faces provide exceptional thermal
performance.
Precise compressor tolerances in
a design optimized for air-conditioning
duty provide superior compression
efficiency.
Integral FLASC (FLAsh SubCooler)
increases the refrigeration effect and
reduces compressor power
consumption.
Product
Data
23XL
Hermetic Screw Liquid Chiller
50/60 Hz
60 Hz 150 to 360 Nominal Tons (530 to 1,270 kW)
50 Hz 130 to 300 Nominal Tons (460 to 1,060 kW)
Copyright 1996 Carrier Corporation Form 23XL-3PD
Page view 0
1 2 3 4 5 6 ... 47 48

Summary of Contents

Page 1 - Features/Benefits

The 23XL screw chiller provides theperformance and reliability of acentrifugal class machine by usingadvanced engineering technology.Optimized for low

Page 2 - Table of contents

Options and accessoriesITEM OPTION* ACCESSORY†Shipped Factory Charged with Refrigerant XShipped Factory Charged with Nitrogen XOne, 2, or 3 Pass Coole

Page 3 - Features/Benefits (cont)

Machine componentsFRONT VIEW1—Power Panel2—Local Interface Display (LID) Control Center3—ASME (American Society of MechanicalEngineers) Nameplate, Coo

Page 4 - Model number nomenclature

Machine components (cont)FRONT VIEW1—Compressor Nameplate2—Power Panel3—Local Interface Display (LID) Control Center4—ASME (American Society of Mechan

Page 5

Physical dataNOMINALCAPACITYTONS (kW)COOLER CONDENSERECONOMIZERCOMPRESSORUNITMOUNTEDSTARTERTOTALDRY WEIGHTREFRIGERANTWEIGHT*TOTALOPERATINGWEIGHT60 Hz

Page 6 - Feature/Benefits (cont)

Physical data (cont)COMPRESSOR WEIGHTS23XLUNITCOMPRESSOR SIZEASSEMBLYlb kgFrame 1C2 2270 1029C4 2300 1043Frame 2 C6 2400 1088Frame 4D4 3300 1497D6 340

Page 7 - 23XL Refrigeration Cycle

WATERBOX COVER WEIGHTS (FRAME 1 AND 2 CHILLERS)*HEAT EXCHANGERWATERBOXDESCRIPTIONPSI(kPa)FRAME 1 FRAME 2lbs kg lbs kgCooler orCondenserNIH, 1 Pass150(

Page 8

Dimensions23XL FRAME 1 AND 2 CHILLERSNOTES:1. Service access should be provided per ANSI/ASHRAE 15 (American National Standards Institute/American Soc

Page 9 - FOR EASY REALIGNMENT

23XL FRAME 4 CHILLERSNOTES:1. For flanged waterbox nozzles, refer to the certified drawings for length addition measurements.2. Service access should be

Page 10 - Options and accessories

Electrical dataCOMPRESSORMOTORELECTRICALCHARACTERISTICS60 Hz MOTORS 50 Hz MOTORSLow Voltage Low VoltageSize VI TypeMax208 V 230 V 400 V 460 V 575 VMax

Page 11 - Machine components

Performance dataComputerized ratingsBecauseof the large number ofavailableCarrier 23XL ScrewChiller component combinations and the wide variability in

Page 12 - Machine components (cont)

Variable refrigerant meteringeliminates inefficient vapor bypass andprovides superior part-load perfor-mance when compared to fixed orificemetering desig

Page 13 - Physical data

Application data (cont)CHILLER FOOTPRINT (FRAME 1 AND 2 CHILLERS)DIMENSIONHEAT EXCHANGER SIZE10 or 11 20 or 21ft-in. mm ft-in. mmA 4-51⁄41353 4-71⁄414

Page 14 - Physical data (cont)

STANDARD ISOLATIONVIEW B-BNOTES:1. Dimensions in ( ) are in millimeters.2. Isolation package includes 4 shear flex pads.ACCESSORY ISOLATIONHRS — Hot Ro

Page 15

Application data (cont)FRAME 1 AND 2 NOZZLE ARRANGEMENTSCOOLER AND CONDENSER NOZZLE ARRANGEMENTSNOZZLE ARRANGEMENT CODESCooler CondenserPass In Out Co

Page 16 - Dimensions

FRAME 4 NOZZLE ARRANGEMENTSCOOLER AND CONDENSER NOZZLE ARRANGEMENTSNOZZLE ARRANGEMENT CODESCooler CondenserPass In Out Code Pass In Out Code185 A111 2

Page 17 - 23XL FRAME 4 CHILLERS

Application data (cont)Vent and drain connectionsAll vents and drain connections are found in the waterboxcovers. Connection size is3⁄4-in. FPT.Provid

Page 18 - Electrical data

InsulationINSULATION REQUIREMENTSCOMPONENT FRAME FT2M2Cooler1 60 5.572 66 6.134 113 10.49Compressor1, 2 35 3.254 41 3.81Economizer1, 2 17 1.584 28 2.6

Page 19 - Application data

Application data (cont)INSULATION AREA FOR FRAME 1 AND 2 CHILLERSINSULATION AREA FOR FRAME 4 CHILLERS26

Page 20 - Application data (cont)

FLOOR CONTACT SURFACE LOADINGHEAT EXCHANGER FRAME PAD POSITIONMINIMUM MAXIMUMlb kg lb kg1A 2970 1347 3310 1501B 2740 1243 3200 1451C 2270 1029 2630 11

Page 21 - (Isometric View)

ControlsMicroprocessor controlsMicroprocessor controls provide the safety, interlock, ca-pacitycontrol and indications necessaryto operate the chiller

Page 22

MICROPROCESSOR CONTROL CENTERSOFTKEYS29

Page 23 - WATERBOX NOZZLE SIZES

Features/Benefits (cont)Automatic two chiller lead/lagcapability provides integral standbycontrols.A 16 line by 40 character LCDdisplay offers ‘‘all in

Page 24

Controls (cont)CONTROL CENTER (FRONT VIEW), WITH OPTIONSLEGEND1—Local Interface Device (LID)Input/Output Interface Panel Display2—Processor Module (PS

Page 25 - Insulation

TYPICAL LOCAL INTERFACE DEVICE (LID) DISPLAY SCREENS (cont)Schedule Screen — A user established occupancy schedule canbe easily configured for your par

Page 26

Controls (cont)TYPICAL LOCAL INTERFACE DEVICE (LID) DISPLAY SCREENS (cont)The Control Test Screen — This screen allows access to the vari-ous control

Page 27 - FRAME 4 CHILLERS

Control sequenceTo start: Push Start button — Start initiated; all safetiesare checked to see that they are satisfied (if one is not, anindication of t

Page 28 - Controls

Typical piping and wiring23XL CHILLER WITH FREE-STANDING STARTERLEGEND1—Chilled Water Pump Starter2—Condenser Water Pump Starter3—Cooling Tower Fan St

Page 29 - MICROPROCESSOR CONTROL CENTER

23XL CHILLER WITH OPTIONAL UNIT-MOUNTED STARTERLEGEND1—Chilled Water Pump Starter2—Condenser Water Pump Starter3—Cooling Tower Fan Starter4—Chilled Wa

Page 30 - Controls (cont)

Typical field wiring23XL TYPICAL FIELD WIRING WITH FREE-STANDING STARTER (FRAME 1 AND 2 CHILLERS)IMPORTANT: Wiring shown is typical and not intended to

Page 31

23XL TYPICAL FIELD WIRING WITH FREE-STANDING STARTER (FRAME 1 AND 2 CHILLERS) (cont)LEGENDLL — Compressor Motor Starter TerminalsMCM — Thousand Circul

Page 32

Typical field wiring (cont)23XL TYPICAL FIELD WIRING WITH OPTIONAL UNIT-MOUNTED STARTER (FRAME 1 AND 2 CHILLERS)IMPORTANT: Wiring shown is typical and

Page 33 - Control sequence

23XL TYPICAL FIELD WIRING WITH OPTIONAL UNIT-MOUNTED STARTER (FRAME 1 AND 2 CHILLERS) (cont)LEGENDMCM — Thousand Circular MilsNEMA — National Electric

Page 34 - Typical piping and wiring

Model number nomenclatureLEGENDVI — Volumetric IndexUnderwriters’LaboratoryCanadaASME‘U‘ StampUnderwriters’LaboratoriesARI (Air Conditioningand Refrig

Page 35

Guide specificationsPackaged Hermetic Screw Liquid ChillerSizeRange:150to360Tons(530to1270kW)—60Hz130to300Tons(460to1060kW)—50HzCarrier Model Number: 2

Page 36 - Typical field wiring

7. Compressor safeties shall include high compres-sor discharge temperature, high motor windingtemperature, low oil pressure, reverse rotation,and hig

Page 37

Guide specifications (cont)2. Tubing shall be copper, high-efficiency type, withintegralinternal andexternal enhancement. Tubesshall be nominal3⁄4-in. O

Page 38 - Typical field wiring (cont)

d. Uponrequestto startthe compressor,thecon-trol system shall start the chilled water pump,condenser water pumps, and tower fans, ifappropriate, and v

Page 39

Guide specifications (cont)one year in advance (month, day, and dura-tionofdays).Display of the occupancy sched-ules shall be viewable on the LCD scree

Page 40 - Guide specifications

c. A slide valve test shall energize the increaseand decrease slide valve solenoids to checkfor proper operation. The controls shall re-questmanualope

Page 41

Guide specifications (cont)J. Insulation:1. Chilled water piping and cooler waterboxes shallbe insulated by the mechanical contractor.2. Factory instal

Page 43

Carrier Corporation • Syracuse, New York 13221 11-96Manufacturer reserves the right to discontinue, or change at any time, specifications or designs wi

Page 44

Features/Benefits (cont)23XL HERMETIC SCREW LIQUID CHILLER (FRAME 1 AND 2 CHILLERS)Technologically advanced chillers designed to answertoday’s environm

Page 45

Feature/Benefits (cont)23XL HERMETIC SCREW LIQUID CHILLER (FRAME 4 CHILLERS)Technologically advanced chillers designed to answertoday’s environmental a

Page 46

23XL Refrigeration CycleThe compressor continuously drawsrefrigerant vapor from the cooler at arate determined by the position ofthe capacity control

Page 47

Features/Benefits (cont)TYPICAL 23XL REFRIGERATION CYCLE ECONOMIZED CHILLERSTYPICAL 23XL REFRIGERATION CYCLE NON-ECONOMIZED CHILLERS8

Page 48 - Replaces: 23XL-2PD

SCREW COMPRESSOR COMPONENTS1—Control Oil Lines2—Capacity Control Solenoid Valve3—Discharge Bearing Assemblies4—Male Rotor5—Semi-Hermetic Motor6—Female