Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata
10a30-5376Fig. 7A — Typical Wiring Schematic, 30RAP010,015 Units — Power Wiring
100APPENDIX B — CCN TABLES (cont)CCN MAINTENANCE TABLES — STRTHOURCCN MAINTENANCE TABLES — CURRMODSDESCRIPTION VALUE UNITS POINT NAMEMachine Operating
101APPENDIX B — CCN TABLES (cont)CCN MAINTENANCE TABLES — ALARMSCCN MAINTENANCE TABLES — VERSIONSCCN MAINTENANCE TABLES — LOADFACTDESCRIPTION VALUE PO
102APPENDIX B — CCN TABLES (cont)CCN MAINTENANCE TABLES — PM-PUMPCCN MAINTENANCE TABLES — PM-STRNCCN MAINTENANCE TABLES — PM-COILDESCRIPTION VALUE UNI
103APPENDIX B — CCN TABLES (cont)CCN MAINTENANCE TABLES — TESTMODECCN MAINTENANCE TABLES — RUNTESTDESCRIPTION VALUE UNITS POINT NAMEService Test Mode
104APPENDIX B — CCN TABLES (cont)CCN MAINTENANCE TABLES — RUNTEST (cont)DESCRIPTION VALUE UNITS POINT NAMEMinimum Load Valve Relay On/Off MLV_RLYCompr
105APPENDIX B — CCN TABLES (cont)CCN MAINTENANCE TABLES — DUALCHILDESCRIPTION VALUE UNITS POINT NAMEDual Chiller Link Good? Yes/No DC_LINKMaster Chill
106APPENDIX C — FACTORY SETTINGS FOR PUMP AND MANUAL STARTERS*Identtified by 12th digit in unit model number.30RAP UNIT SIZE PUMP SIZE PUMP OPTION* UN
107APPENDIX D — BACNET COMMUNICATION OPTIONThe following section is used to configure the UPC Open con-troller which is used when the BACnet* communic
108APPENDIX D — BACNET COMMUNICATION OPTION (cont)CONFIGURING THE BAS PORT FOR BACNET MS/TP — Use the same baud rate and communication settings forall
109APPENDIX D — BACNET COMMUNICATION OPTION (cont)To install a BT485 terminator, push the BT485 terminatoron to the BT485 connector located near the B
11Fig. 7B — Typical Wiring Schematic, 30RAP010,015 Units — Control Wiring a30-5377
110APPENDIX D — BACNET COMMUNICATION OPTION (cont)Table D — Open System Wiring Specifications and Recommended Vendors LEGE
111APPENDIX D — BACNET COMMUNICATION OPTION (cont)If the UPC Open is used with the chiller application ofLead/Lag/Standby, all chillers and UPC Open&a
112APPENDIX D — BACNET COMMUNICATION OPTION (cont)Table G — Network Points List LEGENDPOINT DESCRIPTIONCCN POINT NAMEREAD/WRITEUNITSDEFAULTVALUERAN
113APPENDIX D — BACNET COMMUNICATION OPTION (cont) Table G — Network Points List (cont) LEGENDPOINT DESCRIPTIONCCN POINT NAMEREAD/W
114APPENDIX D — BACNET COMMUNICATION OPTION (cont)Table G — Network Points List (cont) LEGENDPOINT DESCRIPTION POINT NAMEREAD/WRITEUNITSDEFAULTVAL
115APPENDIX D — BACNET COMMUNICATION OPTION (cont)Table G — Network Points List (cont) LEGENDPOINT DESCRIPTION POINT NAMEREAD/WRITEUNITSDEFAULTVAL
116APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS30RAP Weekly Maintenance LogPlant ___________________________Machine Model No. ________________NOT
117APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont)30RAP Monthly Maintenance LogNOTE: Equipment failures caused by lack of adherence to the Main
118APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont)30RAP Seasonal Shutdown LogNOTE: Equipment failures caused by lack of adherence to the Mainte
119INDEXActual start-up 43Alarms and alerts 67 Compressor failure alerts 74 Compessor stuck on failure alarms 74AUX board (A
12COMP A2TRAN1H2H3H4SECONDARY 24VREDFC2FU3SW2C1A1B1H1X1CONNECT FORAPPROPRIATEPRIMARY VOLTAGESEE TABLE 1123CB1A111213TO FUSED DISCONNECTPER NECOPTIONAL
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata
CL-2- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
CL-310. VERIFY COOLER FLOW RATE. YES NOPRESSURE ENTERING COOLER ________ psig (kPa)PRESSURE LEAVING COOLER ________ psig (kPa)COOLER PRESSURE DROP
CL-4- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
CL-5III. Unit Start-Up (cont)RECORD CONFIGURATION SETTINGSUNIT (Configuration Settings)PRESS ESCAPE KEY TO DISPLAY ‘UNIT’. PRESS DOWN ARROW KEY TO DIS
CL-6- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
CL-7III. Unit Start-Up (cont)PRESS ESCAPE KEY TO DISPLAY ‘HP.B’. PRESS DOWN ARROW KEY TO DISPLAY ‘EXV.A’.PRESS ENTER KEY.RECORD CONFIGURATION INFORMAT
CL-8- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
CL-9III. Unit Start-Up (cont)PRESS ESCAPE KEY TO DISPLAY ‘RSET’. PRESS DOWN ARROW KEY TO DISPLAY ‘SLCT’.PRESS ENTER KEY.RECORD CONFIGURATION INFORMATI
13LEGENDTERMINAL BLOCKXTERMINAL (UNMARKED)TERMINAL (MARKED)SPLICEFACTORY WIRINGFIELD WIRINGACCESSORY OR OPTION WIRINGTO INDICATE COMMON POTENTIALONLY,
CL-10- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
CL-11Service Test Mode and Sub-Mode Directory (cont)NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display.SUB-MOD
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata
14COMP A2GRN/YELTRAN1H2H3H4SECONDARY 24VREDFC2BLK-1BLK-2BLK-3FU3SW2C1A1B1123H1X1CONNECT FORAPPROPRIATEPRIMARY VOLTAGESEE TABLE 1123CB1A111213TO FUSED
15LEGENDTERMINAL BLOCKXTERMINAL (UNMARKED)TERMINAL (MARKED)SPLICEFACTORY WIRINGFIELD WIRINGACCESSORY OR OPTION WIRINGTO INDICATE COMMON POTENTIALONLY,
16a30-5454Fig. 10A — Typical Wiring Schematic, 30RAP070-090 Units — Power Wiring
17LEGENDTERMINAL BLOCKXTERMINAL (UNMARKED)TERMINAL (MARKED)SPLICEFACTORY WIRINGFIELD WIRINGACCESSORY OR OPTION WIRINGTO INDICATE COMMON POTENTIALONLY,
18EQUIP GNDGRN/YELOFM5TRAN1H2H3H4SECONDARY 24VREDFC1BLK-1BLK-2BLK-3332211J2BRNVIO221J1133FU3SW2C1A1B1123H1X1CONNECT FORAPPROPRIATEPRIMARY VOLTAGESEE T
19LEGENDTERMINAL BLOCKXTERMINAL (UNMARKED)TERMINAL (MARKED)SPLICEFACTORY WIRINGFIELD WIRINGACCESSORY OR OPTION WIRINGTO INDICATE COMMON POTENTIALONLY,
2CONTENTS (cont)Page•EPM CHIP• LOSS OF CCN COMMUNICATIONS• REPLACING DEFECTIVE MODULESHydronic Package. . . . . . . . . . . . . . . . . . . . . . . .
20STANDARDTERMINALBLOCKPER NECTO FUSED DISCONNECT212223TB1AEQUIP GNDCOMP A1COMP A2GRN/YELOFM5TRAN1H2H3H4SECONDARY 24VREDFC1BLK-1BLK-2BLK-3332211J2BRNV
21LEGENDTERMINAL BLOCKXTERMINAL (UNMARKED)TERMINAL (MARKED)SPLICEFACTORY WIRINGFIELD WIRINGACCESSORY OR OPTION WIRINGTO INDICATE COMMON POTENTIALONLY,
22LEGEND FOR FIG. 3-12BMain Base Board (MBB) — See Fig. 13. The MBB isthe heart of the ComfortLink control system. It contains themajor portion of ope
23Energy Management Module (EMM) — The EMMmodule is available as a factory-installed option or as a field-installed accessory. The EMM module receives
24which should be blinking whenever power is on. Check LENconnections for potential communication errors at the board J3and/or J4 connectors. Communic
25Table 7 — CCN Communication Bus WiringSensors — The electronic control uses 4 to 7 thermistors tosense temperatures for controlling chiller operatio
26Energy Management Module (Fig. 18) — Thisfactory-installed option (FIOP) or field-installed accessory isused for the following types of temperatur
27The standard control has an automatic lead-lag feature builtin which determines the wear factor (combination of starts andrun hours) for each compre
28Table 8 — Part Load Data Percent Displacement, Standard Units with Minimum Load Valve*Minimum Load Valve energized.NOTE: These capacity steps may va
29Minimum Load Control — If equipped, the minimum loadcontrol valve is energized only when one compressor is run-ning on Circuit A and capcity is decr
3 GENERALThis publication contains Controls, Start-Up, Operation,Service, and Troubleshooting information for the AquaSnap®30RAP air-cooled chillers
30MOTORMASTER® V OPTION — Motormaster V is stan-dard on 30RAP010 and 015 size units. For all other units thatneed low-ambient operation, the lead f
31Table 9 — Fan Stages30RAP UNIT SIZEFAN STAGESFan Stage Contactor Energized Fans Operating010,015 Stage 1 FC1 OFM1018-030Stage 1Stage 2FC1FC1,2OFM1OF
32Cooling Set Point SelectSINGLE — Unit operation is based on Cooling Set Point 1(Set PointsCOOLCSP.1).DUAL SWITCH — Unit operation is based on Cool
33The pump(s) in the hydronic package come factorypre-wired into the main unit power supply/starter. In order tocheck proper pump rotation, use the Se
34factory-installed package, an auxiliary set of contacts is wiredto the MBB to serve as Chilled Water Pump Interlock. Whenthe mechanical cooling is c
35limit Pump Changeover Hours (ConfigurationOPT1PM.DT) is reached, the lead pump will be turned OFF. Ap-proximately one (1) second later, the lag pu
36Table 11 — Dual Chiller Configuration (Master Chiller Example)SUB-MODE ITEM KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENTSDISPUNITOPT1OPT2CTRL CONTROL
37Table 11 — Dual Chiller Configuration (Master Chiller Example) (cont)NOTES:1. Master Control Method (CTRL) can be configured as 0-Switch, 2-Occupanc
38Table 12 — Dual Chiller Configuration (Slave Chiller Example)NOTES:1. Slave Control Method (CTRL) must be configured for 0.2. Slave CCN Address (CCN
39Table 13 — 4 to 20 mA ResetNOTE: The example above shows how to configure the chiller for 4 to 20 mA reset. No reset willoccur at 4.0 mA input, and
4When a specific item is located, the item name alternateswith the value. Press the key at a changeable itemand the value will be displayed. Press
40Table 15 — Configuring Outdoor Air and Space Temperature Reset*One item skipped in this example.Table 16 — Configuring Return Temperature Reset*4 it
41Under normal operation, the chiller will maintain a constantleaving fluid temperature approximately equal to the chilledfluid set point. As the cool
42DEMAND LIMIT (CCN Loadshed Controlled) — To con-figure Demand Limit for CCN Loadshed control set the De-mand Limit Select (ConfigurationRSETDMDC)
43Digital Scroll Option — The 30RAP010-090 unitshave a factory-installed option for a digital scroll compressorwhich provides additional stages of unl
44CSP.1) or (Set PointsCOOLCSP.2), or if reset isused, with the control point (Run StatusVIEWCTPT).6. Check the cooler leaving chilled water temp
45Table 20 — Minimum Fluid Volume in CirculationLEGENDHigh Cooler Leaving Chilled Water (Fluid) Temperatures(LCWT) — During start-up with cooler LCWT
46For all units, if temperature reset is being used, the unit con-trols to a higher leaving-fluid temperature as the building loadreduces. If demand l
47During the next several seconds, carefully connect the nega-tive test lead to pins 1,2,4 and 5 in succession (plug J6 for Cir-cuit A, plug J7 for Ci
48VALVE MOTOR REPLACEMENTSizes 025, 030, and 050-060 Perform the following procedure to replace the EXVmotor:1. Be sure the refrigerant has been reco
49SPORLANMOTOR AND ADAPTERASSEMBLYCABLECABLECABLE RETAINERCABLERETAINERMOTOR ADAPTERASSEMBLYMOTOR ADAPTERASSEMBLYINCLUDED IN CABLE KITGASKETSIGHTGLASS
5Table 3 — Operating ModesMODE NO. ITEM EXPANSION DESCRIPTION01 CSM CONTROLLING CHILLER Chillervisor System Manager (CSM) is controlling the chiller.
50Compressor Replacement (Fig. 34-36) — Allmodels contain scroll compressors and have from one to sixcompressors. The size 010-030 units are a sin
51UNIT SIZES 100-150MANUFACTURER OILICI. . . . . . . . . . . . . . . . . . . . . . . . . . . . Emkarate RL 32HDo not reuse drained oil or any oil tha
52A1A2B1B2OILSIGHT GLASSDISCHARGEACCESSVALVEFLOWSWITCHLWTDTTDISCHARGEACCESSVALVEDPTHPSRGTSPTSUCTIONACCESSVALVERGTSPTDPTHPSEWTLEGENDDPT — Discharge Pre
53MINIMUM LOAD VALVE — On units equipped with thefactory-installed capacity reduction option, a solenoid valveand discharge bypass valve (minimum
54value read by the control in the Temperatures mode using thescrolling marquee display.Pressure Transducers — The suction and dischargetransducers ar
55Table 25 — 5K Thermistor Temperatures (°F) vs. Resistance/Voltage Drop(Voltage Drop for EWT, LWT, RGT, and OAT)TEMP(F)VOLTAG EDROP (V)RESISTANCE(Ohm
56Table 26 — 5K Thermistor Temperatures (°C) vs. Resistance/Voltage Drop(Voltage Drop for EWT, LWT, RGT, and OAT)TEMP(C)VOLTAG EDROP(V)RESISTANCE(Ohms
57Table 27 — 10K Thermistor Temperature (°F) vs. Resistance/Voltage Drop(For SPT)TEMP(F)VOLTAG EDROP(V)RESISTANCE(Ohms)–25 4.758 196,453–24 4.750 189,
58Table 28 — 10K Thermistor Temperature (°C) vs. Resistance/Voltage Drop(For SPT)Table 29 — 86K Thermistor vs Resistance (DTT) TEMP(C)VOLTAG EDROP(V
59The flow sensor cable is provided with (3) LEDs that indi-cate if 24 vac power is present and also status of the switchcontacts. The LEDs are as fol
6ACCESSORY NAVIGATOR™ DISPLAY MODULE —The Navigator module provides a mobile user interface to theComfortLink control system, which is only available
60configurations, the MMV follows a 4 to 20 mA speed refer-ence signal present on terminals 25 (+) and 2 (-). One addition-al jumper is required to co
61 Fig. 41 — Typical Motormaster WiringCONFIGURATION TABLE*208-v can run in mode 5 or 6.MODE NOMINAL VOLTAGE HzCONTROL INPUT(PINS 25, 2)START JUMPER5
62Table 30 — Fault Codes LEGENDFAULT CODE DESCRIPTION SOLUTIONAF High Temperature Fault: Ambient temperature is too high; Cooling f
63Table 31 — Motormaster® V Program Parameters for Operating Modes LEGENDPARAMETERS DESCRIPTION MODE 5 MODE 6 MODE 7 MODE 8P01
64 1. Check that all power to unit is off. Carefully disconnectall wires from the defective module by unplugging itsconnectors. 2. Remove the defectiv
65MAINTENANCERecommended Maintenance Schedule — The fol-lowing are only recommended guidelines. Jobsite conditionsmay dictate that maintenance schedul
66If there is a command for a compressor to run and there isno current, then one of the following safeties or conditionshave turned the compressor off
67NOTE: Turning off power to the module will reset it immedi-ately.For this reason, module power must never be switched withthe control circuit voltag
68 and until the sub-menu item RCRN “RESETALL CURRENT ALARMS” is displayed. Press .The control will prompt the user for a password, by displayingPA
69Table 34 — Alarm and Alert CodesSee Legend on page 73.ALARM/ALERTCODEALARMORALERTDESCRIPTIONWHY WAS THISALARMGENERATED?ACTION TAKENBY CONTROLRESETME
7CONTROL BOXFAN1A1COMPRESSORLOCATED OVER EMM AND EXVEMMEXVLONAUXUPCTB1TB4CSB-A1MBBCHCCCBFB-1TRANDISCONNECTOPTION/TBC-A1MMMS-CWP1CWP1MS-CWP2CWP2EMMEXVC
70Table 34 — Alarm and Alert Codes (cont)ALARM/ALERTCODEALARMORALERTDESCRIPTIONWHY WAS THISALARMGENERATED?ACTION TAKENBY CONTROLRESETMETHODPROBABLECAU
71Table 34 — Alarm and Alert Codes (cont)See Legend on page 73.ALARM/ALERTCODEALARMORALERTDESCRIPTIONWHY WAS THISALARMGENERATED?ACTION TAKENBY CONTROL
72Table 34 — Alarm and Alert Codes (cont)ALARM/ALERTCODEALARMORALERTDESCRIPTIONWHY WAS THISALARMGENERATED?ACTION TAKENBY CONTROLRESETMETHODPROBABLECAU
73Table 34 — Alarm and Alert Codes (cont) LEGENDALARM/ALERTCODEALARMORALERTDESCRIPTIONWHY WAS THISALARMGENERATED?ACTION TAKENBY
74COMPRESSOR FAILURE ALERTST051, T052, T053 (Circuit A Compressor Failures)T055, T056, T057 (Circuit B Compressor Failures) — Alertcodes T051-T053 are
75the alert is usually a faulty transducer, faulty 5-v power supply,or a loose connection.T092 (Circuit A Suction Pressure Transducer Failure)T093 (Ci
76T170 (Loss of Communication with the Compressor Expan-sion Module) —This alert indicates that there are communica-tions problems with the compressor
77APPENDIX A — DISPLAY TABLESRun Status Mode and Sub-Mode DirectoryNOTE: If the unit has a single circuit, the Circuit B items will not appear in the
78APPENDIX A — DISPLAY TABLES (cont)Run Status Mode and Sub-Mode Directory (cont)SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENTPMPREVENTIVE MAINTENANC
79APPENDIX A — DISPLAY TABLES (cont)Service Test Mode and Sub-Mode DirectoryTemperature Mode and Sub-Mode Directory*Refer to Fig. 21 on page 30 for co
8LOCATED OVER EMM AND EXVCONTROL BOX ENDA1A2B1B2COMPRESSORSFAN3FAN1FAN2FAN4055,060 UNIT ONLYTRAN-1CB-1CB-2FCB-1/2/3TRAN-2CSB-A1CSB-A2C-A1FR-1FR-2C-A2F
80APPENDIX A — DISPLAY TABLES (cont)Pressures Mode and Sub-Mode DirectorySet Points Mode and Sub-Mode DirectoryInputs Mode and Sub-Mode DirectoryNOTE:
81APPENDIX A — DISPLAY TABLES (cont)Outputs Mode and Sub-Mode DirectoryNOTE: If the unit has a single circuit, the Circuit B items will not appear in
82APPENDIX A — DISPLAY TABLES (cont)Configuration Mode and Sub-Mode DirectorySUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENTDISPDISPLAY CONFIGURATIONTE
83APPENDIX A — DISPLAY TABLES (cont)Configuration Mode and Sub-Mode Directory (cont)SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENTOPT2UNIT OPTIONS 2 C
84APPENDIX A — DISPLAY TABLES (cont)Configuration Mode and Sub-Mode Directory (cont)* Sizes 010-020 and 035-045, default is 1596. Sizes 025,030, 050-0
85APPENDIX A — DISPLAY TABLES (cont)Configuration Mode and Sub-Mode Directory (cont)SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENTMMMOTORMASTERMMR.S Y
86APPENDIX A — DISPLAY TABLES (cont)Configuration Mode and Sub-Mode Directory (cont)SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENTSLCTSETPOINT AND RAM
87APPENDIX A — DISPLAY TABLES (cont)Time Clock Mode and Sub-Mode DirectorySUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENTTIMETIME OF DAYHH.MM XX.XX Hou
88APPENDIX A — DISPLAY TABLES (cont)Time Clock Mode and Sub-Mode Directory (cont)SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENTHD.09HOLIDAY SCHEDULE 0
89APPENDIX A — DISPLAY TABLES (cont)Time Clock Mode and Sub-Mode Directory (cont)SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENTHD.20HOLIDAY SCHEDULE 2
9Fig. 6 — Typical Control Box for 30RAP070-150a30-5453
90APPENDIX A — DISPLAY TABLES (cont)Time Clock Mode and Sub-Mode Directory (cont)SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENTSCH.N Schedule Number 0
91APPENDIX A — DISPLAY TABLES (cont)Time Clock Mode and Sub-Mode Directory (cont)SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENTPER.6OCCUPANCY PERIOD 6
92APPENDIX A — DISPLAY TABLES (cont)Operating Mode and Sub-Mode DirectoryAlarms Mode and Sub-Mode DirectorySUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMM
93APPENDIX B — CCN TABLESCCN DISPLAY TABLES — A_UNIT (General Unit Parameters)CCN DISPLAY TABLES — CIRCA_AN (Circuit A Analog Parameters)DESCRIPTION V
94APPENDIX B — CCN TABLES (cont)CCN DISPLAY TABLES — CIRCADIO (Circuit A Discrete Inputs/Outputs)CCN DISPLAY TABLES — CIRCB_AN (Circuit B Analog Param
95APPENDIX B — CCN TABLES (cont)CCN DISPLAY TABLES — OPTIONS (Unit Parameters)CCN CONFIGURATION TABLES — UNIT (Unit Configuration)DESCRIPTION VALUE UN
96APPENDIX B — CCN TABLES (cont)CCN CONFIGURATION TABLES — OPTIONS1 (Options 1 Configuration)CCN CONFIGURATION TABLES — OPTIONS2 (Options 2 Configurat
97APPENDIX B — CCN TABLES (cont)CCN CONFIGURATION TABLES — RESETCON (Temperature Reset and Demand Limit)CCN CONFIGURATION TABLES — DUALCHIL (Dual Chil
98APPENDIX B — CCN TABLES (cont)CCN CONFIGURATION TABLES — DISPLAY (Marquee Display SETUP)CCN CONFIGURATION TABLES — EXVACONF (EXV Circuit A Configura
99APPENDIX B — CCN TABLES (cont)CCN SERVICE TABLES — SERVICECCN SETPOINT TABLES — SETPOINTCCN MAINTENANCE TABLES — CIRA_EXVCCN MAINTENANCE TABLES — CI
Comments to this Manuals