Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS .................1
GENERAL ..................................1
INSTALLATION ............................1-12
Step 1 − Complete Pre-Installation Checks ..1
Step 2 − Rig and Place Unit ................7
RIGGING
PLACING THE UNIT
VIBRATION ISOLATION
POSITIONING THE 09BY UNIT
VERTICAL DISCHARGE
Step 3 − Install Accessory Low-Ambient Kit or
Inlet Filter Kit (If Required) ................8
Step 4 − Install Rain Drain .................8
Step 5 − Complete Refrigerant Piping .......8
GENERAL
REFRIGERANT LINE SIZING
PRESSURE RELIEF
REFRIGERANT RECEIVER
LIQUID LIFT
SWEAT CONNECTIONS
FIELD PIPING
MANIFOLDING CIRCUITS
CHECK VALVE
SERVICE VALVES
Step 6 − Ductwork ........................10
CONDENSER AIR DUCT INSULATION
Step 7 − Insulate the Unit .................11
Step 8 − Complete Electrical Connections ..11
GENERAL
MAIN POWER WIRING
CONTROL CIRCUIT POWER WIRING
GENERAL WIRING NOTES
START-UP .................................13
System Evacuation and Dehydration ........13
Charging Procedure .......................13
Check Operation of Condenser Fan Motor
Controls and Rotation of Fans ...........13
Adjust Fan Speed .........................13
SERVICE .................................13-15
Cleaning Condenser Coils .................13
Lubrication ................................13
Condenser Fan Adjustment ................13
TO CHANGE FAN SPEED
PULLEY ALIGNMENT
BELT TENSION ADJUSTMENT
TO CHANGE FAN WHEEL
TO REPLACE FAN BEARING
MAINTENANCE ............................15
Cleaning ..................................15
Inspection .................................15
Air Filters .................................15
Condensate Drain .........................15
TROUBLESHOOTING ......................16
START-UP CHECKLIST ................CL-1,CL-2
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip-
ment can be hazardous due to system pressures, electrical
components, and equipment location.
Only trained, qualified installers and service mechanics
should install, start-up, and service this 09BY equipment
(Fig. 1).
When working on the equipment, observe precautions in
the literature and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes. Wear safety glasses and work gloves.
Keep quenching cloth and fire extinguisher nearby when braz-
ing. Use care in handling, rigging, and setting bulky
equipment.
ELECTRIC SHOCK HAZARD
Separate power sources (main and control
power circuits) are used for these units. Be
sure both main and control power circuits are
disconnected before servicing.
GENERAL
The 09BY air-cooled condenser is a remote air-cooled con-
denser designed to be used with the 50BZ vertical packaged
units. See Table 1. Airflow is horizontal, both into and out
from the same face of the unit. The unit is designed to be
mounted indoors in a window, through the wall in high-rise
buildings, or on the wall on the building exterior. See Fig. 2
for typical applications. Ductwork is not needed, but may be
added easily if required by the application. Airflow is pro-
vided by centrifugal fans with an adjustable belt drive to meet
varying static requirements. Units may also be matched with
other compressor and evaporator combinations. Contact your
local representative for more details.
Check space requirements, service clearances, floor strength,
location of piping, size of power supply, and location of duct-
work (if used) before installing. See Fig. 3 for unit dimen-
sions and Table 2 for unit operating weights.
INSTALLATION
Step 1 Complete Pre-Installation Checks
Examine unit for damage incurred during shipment. File claim
immediately with transit company if damage is found. Check
the shipment for completeness. Verify that the nameplate elec-
trical requirements match the available power supply.
09BY006-024
Air-Cooled Condenser Units
5to20Tons
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 4
Tab 4a 4a
PC 111 Catalog No. 530-969 Printed in U.S.A. Form 09BY-2SI Pg 1 9-96 Replaces: 09BY-1SI
Page view 0
1 2 3 4 5 6 ... 19 20

Summary of Contents

Page 1 - Service Instructions

Installation, Start-Up andService InstructionsCONTENTSPageSAFETY CONSIDERATIONS ...1GENERAL ...1INSTALLAT

Page 2

CHECK VALVE — When the 09BY condenser is installedwith the condenser located above the compressor evapora-tor, it is recommended that a field-supplied

Page 3 - Refrigerant Connection

3. A high-density fiberglass (2 lb minimum density) or semi-rigid foamed insulation such as Styrofoam™ will be re-quired inside the ducts to prevent ai

Page 4 - 09BY DIMENSIONS (SI)

Determine maximum deviation from average voltage:(AB) 243 – 239=4v(BC) 239 – 236=3v(AC) 239 – 238=1vMaximum deviation is then 4 v. To determine the pe

Page 5

START-UPTo prevent personal injury, be sure wire fan guards aresecured in place over each fan discharge (or that fansare ducted) before starting the u

Page 6 - Table 2 — Physical Data

Table 5 — Condenser Fan PerformanceUNIT09BYAIRFLOW(Cfm)EXTERNAL STATIC PRESSURE (in. wg)0.0 0.2 0.4 0.6 0.8 1.0Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp

Page 7 - Step 2 — Rig and Place Unit

TO CHANGE FAN WHEEL — If a fan wheel should fail,it may be replaced as follows:1. Remove belts from fan pulley.2. Loosen locking collars on the fan be

Page 8

TROUBLESHOOTINGSee Table 6 for problems and possible solutions.Table6—TroubleshootingPROBLEM POTENTIAL CAUSE SOLUTIONUnit is tripping onhigh-pressure

Page 10

Copyright 1996 Carrier CorporationManufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and w

Page 11

START-UP CHECKLISTA. Preliminary InformationCOMPRESSOR BEARING UNIT: MODEL NO. SERIAL NO.09BY UNIT: MODEL NO. SERIAL NO.FIELD-INSTALLED ACCESSORIESB.

Page 12

Fig. 1 — 09BY Unit (008-014 Shown)2

Page 13

CHECK VOLTAGE IMBALANCEIS CONDENSER MOTOR WIRED FOR CORRECT VOLTAGE? (Y/N)LINE-TO-LINE VOLTS: AB VACVBCV(AB + AC + BC)/3 = AVERAGE VOLTAGE =VMAXIMUM D

Page 14

LEGENDRefrigerant ConnectionField-Supplied Refrigerant Piping*Field-Supplied Floor Stand (Height to Match Wall Opening).Fig. 2 — Mounting Applications

Page 15 - Cleaning —

09BY DIMENSIONS (English)DIMENSION006(Ft-in.)008(Ft-in.)012(Ft-in.)014(Ft-in.)016,024(Ft-in.)A 2-111⁄23- 613⁄163- 613⁄163- 613⁄165- 0B 1- 711⁄161-115⁄

Page 16 - TROUBLESHOOTING

NOTES:1. Operational clearances are 0 in. on all sides of the unit.2. Service clearances are 0 in. (minimum) on the top, rear, and frontof the unit. A

Page 17

Table 1 — Condenser Unit ApplicationUNIT50BZ09BY006 008 012 014 016 024006 S008 S012 OS014 OS016 OS024 OSLEGENDS—StandardO—OptionalNOTE: Contact your

Page 18 - Tab 4a 4a

Step 2 — Rig and Place UnitRIGGING — The 09BY units are mounted on skids. Leavethe unit on the skid until it is in the final position. While onthe skid

Page 19 - A. Preliminary Information

Step 3 — Install Accessory Low-Ambient Kit orInlet Filter Kit (If Required) —If the unit will be op-erated with inlet air to the condenser below 50 F,

Page 20 - C. Start-Up

LIQUID LIFT — Amount of liquid lift available before re-frigerant flashing occurs depends on amount of liquid sub-cooling in the system.All 09BY conden