Carrier 48TJD User Manual

Browse online or download User Manual for Conditioners Carrier 48TJD. Carrier 48TJD User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 52
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 534-774 Printed in U.S.A. Form 48TJ-18SI Pg 1 10-00 Replaces: 48TJ-16SI
Book 1 4
Ta b 1 a 6 a
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS
. . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-36
Step 1 — Provide Unit Support
. . . . . . . . . . . . . . . . . . . 1
•ROOF CURB
SLAB MOUNT
Step 2 — Field Fabricate Ductwork
. . . . . . . . . . . . . . . 2
Step 3 — Install External Trap for
Condensate Drain
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 4 — Rig and Place Unit
. . . . . . . . . . . . . . . . . . . . . 2
POSITIONING
Step 5 — Install Flue Hood
. . . . . . . . . . . . . . . . . . . . . . . 4
Step 6 — Install Gas Piping
. . . . . . . . . . . . . . . . . . . . . . 4
Step 7 — Make Electrical Connections
. . . . . . . . . . . 5
DISCONNECT BOX LOCATION
FIELD POWER SUPPLY
FIELD CONTROL WIRING
HEAT ANTICIPATOR SETTINGS
Step 8 — Make Outdoor-Air Adjustment and
Install Outdoor-Air Hood
. . . . . . . . . . . . . . . . . . . . . . 12
MANUAL OUTDOOR-AIR DAMPER
OPTIONAL DURABLADE ECONOMIZER
OPTIONAL ECONOMI$ER
Step 9 — Adjust Evaporator-Fan Speed
. . . . . . . . . 20
DIRECT-DRIVE MOTORS
BELT-DRIVE MOTORS
START-UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37-39
SERVICE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40-44
TROUBLESHOOTING
. . . . . . . . . . . . . . . . . . . . . . . . . 45-50
START-UP CHECKLIST
. . . . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
INSTALLATION
Unit is shipped in the vertical discharge configuration. To
convert to horizontal configuration, remove screws from side
duct opening covers and remove covers. Using the same
screws, install covers on vertical duct openings with the insula-
tion side down. Seals around duct openings must be tight. See
Fig. 1.
Step 1 — Provide Unit Support
ROOF CURB Assemble and install accessory roof curb in
accordance with instructions shipped with curb. See Fig. 2. In-
stall insulation, cant strips, roofing felt, and counter flashing as
shown.
Ductwork must be attached to curb, not to the unit. The
accessory thru-the-bottom power and gas connection package
must be installed before the unit is set on the roof curb.
If field-
installed (thru-the-roof curb) gas connections are desired, use
factory-supplied
3
/
4
in. pipe coupling and gas plate assembly to
mount the thru-the-roof curb connection to the roof curb. Gas
connections and power connections to the unit must be field in-
stalled after the unit is installed on the roof curb.
If electric and control wiring is to be routed through the
basepan, attach the accessory thru-the-bottom service connec-
tions to the basepan in accordance with the accessory installa-
tion instructions.
Ensure voltage listed on unit data plate agrees with electri-
cal supply provided for the unit.
Disconnect gas piping from unit when leak
testing at pressure greater than
1
/
2
psig. Pres-
sures greater than
1
/
2
psig will cause gas valve
damage resulting in hazardous condition. If
gas valve is subjected to pressure greater than
1
/
2
psig, it
must
be replaced before use. When
pressure testing field-supplied gas piping at
pressures of
1
/
2
psig or less, a unit connected to
such piping must be isolated by manually clos-
ing the gas valve.
Before performing service or maintenance operations on
unit, turn off main power switch to unit and install lockout
tag. Electrical shock could cause personal injury.
IMPORTANT: The gasketing of the unit to the roof curb
is critical for a watertight seal. Install gasket supplied
with the roof curb as shown in Fig. 2. Improperly
applied gasket can also result in air or water leaks and
poor unit performance.
48TJE,TJF004
48TJD,TJE,TJF005-007
Single-Package Rooftop Heating/Cooling Units
Page view 0
1 2 3 4 5 6 ... 51 52

Summary of Contents

Page 1 - Service Instructions

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 1

Page 2 - Drain —

10LEGENDFig. 11 — Power Wiring ConnectionsC—ContactorCOMP —CompressorNEC —National Electrical CodeTB —Terminal BlockFig. 12 — Low-Voltage Connections

Page 3 - Fig. 2 — Roof Curb Dimensions

11Table 2 — Electrical Data LEGEND*Used to determine minimum disconnect per NEC.†Fuse or HACR circuit breaker.NOTES:1. In

Page 4 - Step 5 — Install Flue Hood —

12Step 8 — Make Outdoor-Air Adjustments andInstall Outdoor-Air HoodMANUAL OUTDOOR-AIR DAMPER — The outdoor-airhood and screen are attached to the bas

Page 5

13OPTIONAL DURABLADE ECONOMIZER — The option-al economizer hood assembly is packaged and shipped in the fil-ter section. Damper blades and control boa

Page 6 - Table 1 — Physical Data

14ECONOMIZERCONTROLBOARDECONOMIZERPLUGECONOMIZERMOTORTOPSCREWBAROMETRICRELIEF DAMPERWIRINGHARNESSPOSITION SETTINGBRACKETU-SHAPEDHOLE(NOTSHOWN)SHIPPING

Page 7

15OPTIONAL ECONOMI$ER — See Fig. 26 for EconoMi$ercomponent locations.1. To remove the existing unit filter access panel, raise thepanel and swing the

Page 8 - Fig. 6 — Base Unit Dimensions

165. Slide the outdoor-air inlet screens into the screen track onthe hood side panels. While holding the screens in place,fasten the screen retainer t

Page 9 - SPACING OF SUPPORTS

17OUTDOORAIRSENSORTEMPTEMPCOMOUTPWRBROWNVIOLETWHITEREDBROWNTEMPTEMPCOMOUTPWRRETURNAIRSENSORVIOLETWHITEREDOATCOMOAH-15 VRATCOMRAH+15 VECONOMI$ERCONTROL

Page 10

184-PINCONNECTORPLUGL1L2GREEN11223344GND230 VAC1 PHASEGREEN/YELLOW3215869BA74LT. BLUEBLACKBROWNC1BLUEGREEN/YELLOW3215869BA74LT. BLUEBLACKBROWNC1BLUEFA

Page 11 - Table 2 — Electrical Data

19CO2 Control Set Up — If a CO2 sensor is not being used,proceed to the next section. If a CO2 sensor is being used, per-form the following:1. Determi

Page 12 - Install Outdoor-Air Hood

2Curb should be level. Unit leveling tolerances are shown inFig. 3. This is necessary for unit drain to function properly. Re-fer to Accessory Roof Cu

Page 13

20Step 9 — Adjust Evaporator-Fan Speed — Ad-just evaporator-fan rpm to meet jobsite conditions. Table 5shows fan rpm at motor pulley settings. Table 6

Page 14 - Determine — Setting = 5 in

21Table 5 — Fan Rpm at Motor Pulley Settings**Approximate fan rpm shown.†Indicates alternate motor and drive package.**Indicates high-static motor and

Page 15 - Outdoor-Air Thermostat

22Table 8 — Fan Performance 48TJ004 — Vertical Discharge Units, Standard Motor LEGENDNOTES:1. Values include losses for filte

Page 16

23Table 10 — Fan Performance 48TJ004 — Vertical Discharge Units, High-Static Motor LEGEND*Motor drive range is 1075 to 1455

Page 17 - Fig. 33 — EconoMi$er Wiring

24Table 12 — Fan Performance 48TJ005 — Vertical Discharge Units, Alternate Motor LEGEND*Motor drive range is 835 to 118

Page 18 - DISCONNECT

25Table 14 — Fan Performance 48TJ006 — Vertical Discharge Units, Standard Motor LEGENDNOTES:1. Values include losses for filt

Page 19

26Table 16 — Fan Performance 48TJ006 — Vertical Discharge Units, High-Static Motor LEGEND*Motor drive range is 1300 to 1685 rpm

Page 20 - DIMPLED HEAT EXCHANGER

27Table 17 — Fan Performance 48TJ007 — Vertical Discharge Units, Standard Motor LEGEND*Motor drive range is 1070 to 1460 rpm. A

Page 21 - Table 6 — Motor Data

28Table 18 — Fan Performance 48TJ007 — Vertical Discharge Units, High-Static Motor LEGEND*Motor drive range is 1300 to 1685 r

Page 22

29Table 19 — Fan Performance 48TJ004 — Horizontal Discharge Units, Standard Motor LEGENDNOTES:1. Values include losses for filt

Page 23

3TO ENSURE AIRTIGHT CONNECTIONPLACE UNIT AS CLOSE TOEND AS POSSIBLE.TO ENSURE AIRTIGHT CONNECTIONPLACE UNIT AS CLOSE TOEND AS POSSIBLE.Fig. 2 — Roof C

Page 24

30Table 21 — Fan Performance 48TJ004 — Horizontal Discharge Units, High-Static Motor LEGEND*Motor drive range is 1075 to 1455 rpm.

Page 25

31Table 22 — Fan Performance 48TJ005 — Horizontal Discharge Units, Standard Motor LEGENDNOTES:1. Values include losses for filt

Page 26

32Table 24 — Fan Performance 48TJ005 — Horizontal Discharge Units, High-Static Motor LEGEND*Motor drive range is 1075 to 1455 rpm.

Page 27

33Table 26 — Fan Performance 48TJ006 — Horizontal Discharge Units, Alternate Motor LEGEND*Motor drive range is 900 to 1300 rpm. Al

Page 28

34Table 27 — Fan Performance 48TJ006 — Horizontal Discharge Units, High-Static Motor LEGEND*Motor drive range is 1300 to 1685 rpm.

Page 29

35Table 28 — Fan Performance 48TJ007 — Horizontal Discharge Units, Standard Motor LEGEND*Motor drive range is 1070 to 1460 rpm. Al

Page 30

36Table 29 — Fan Performance 48TJ007 — Horizontal Discharge Units, High-Static Motor LEGEND*Motor drive range is 1300 to 1685 rpm.

Page 31

37START-UPUnit Preparation — Make sure that unit has been in-stalled in accordance with these installation instructions andapplicable codes.Return-Air

Page 32

38Heating1. Purge gas supply line of air by opening union ahead ofgas valve. If gas odor is detected, tighten union and wait5 minutes before proceedin

Page 33

39Safety Relief — A soft solder joint at the suction serviceSchrader port provides pressure relief under abnormal tempera-ture and pressure conditions

Page 34

4POSITIONING — Maintain clearance around and above unitto provide minimum distance from combustible materials,proper airflow, and service access. See

Page 35

40SERVICECleaning — Inspect unit interior at the beginning of heat-ing and cooling season and as operating conditions require.EVAPORATOR COIL1. Turn u

Page 36

41LubricationCOMPRESSORS — Each compressor is charged with thecorrect amount of oil at the factory.FAN-MOTOR BEARINGS — Fan-motor bearings are ofth

Page 37

42Fig. 49 — Cooling Charging Chart, 48TJ004Fig. 50 — Cooling Charging Chart, 48TJ005Fig. 51 — Cooling Charging Chart, 48TJ006Fig. 52 — Cooling Chargin

Page 38

43Combustion-Air Blower — Clean periodically to as-sure proper airflow and heating efficiency. Inspect blowerwheel every fall and periodically during

Page 39 - Operating Sequence

44Fig. 54 — Burner Tray DetailsFig. 55 — Spark AdjustmentLOW HEAT48TJE004, 48TJD005-007 — 74,000 BTUH INPUTMEDIUM ANDHIGH HEAT48TJE005-007, 48TJF004 —

Page 40 - Cleaning —

45TROUBLESHOOTINGTable 32 — LED Error Code Service Analysis LEGENDTable 33 — Heating Service AnalysisSYMPTOM CAUSE REMEDYHardwar

Page 41

46Table 34 — Cooling Service AnalysisPROBLEM CAUSE REMEDYCompressor and condenser fanwill not start.Power failure. Call power company.Fuse blown or ci

Page 42

47Table 35 — Durablade Economizer Troubleshooting PROBLEM CAUSE REMEDYDamper does notopen.Indoor (evaporator) fan is off. 1. Check to ensure that

Page 43 - Replacement Parts —

48Table 36 — EconoMi$er TroubleshootingLEGENDPL — PlugPROBLEM POTENTIAL CAUSE REMEDYDamper Does NotOpenIndoor (Evaporator) Fan is Off Check to ensure

Page 44 - Fig. 55 — Spark Adjustment

49Fig. 56 — Typical Wiring Diagram and Component Arrangement

Page 45 - TROUBLESHOOTING

5Step 7 — Make Electrical ConnectionsDISCONNECT BOX LOCATION — The field-supplied dis-connect box may be mounted on the unit’s end panel or on thecorn

Page 46

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 1

Page 48

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 1

Page 49

6Table 1 — Physical Data LEGEND*Evaporator coil fin material/condenser coil fin material. Contact your localrepresentative for details abo

Page 50 - Ta b 1 a 6 a

7Table 1 — Physical data (cont) LEGEND*Evaporator coil fin material/condenser coil fin material. Contact your localrepresentative for det

Page 51

8UNIT48TJSTANDARDUNITWEIGHTDURABLADEECONOMIZERWEIGHTECONOMI$ERWEIGHTCORNERWEIGHT(A)CORNERWEIGHT(B)CORNERWEIGHT(C)CORNERWEIGHT(D)Lb Kg Lb Kg Lb Kg Lb K

Page 52 - III. START-UP:

9Voltage to compressor terminals during operation must bewithin voltage range indicated on unit nameplate (see Table 2).On 3-phase units, voltages bet

Related models: 48TJE | TJE | TJF005-007 |

Comments to this Manuals

No comments