Installation, Start-Up andService InstructionsCONTENTSPageSAFETY CONSIDERATIONS ...1GENERAL ...1-5RECEI
Table 3 — Electrical DataUNIT50ZHNOMINALV-PH-HzIFMTYPEVOLTAGERANGECOMPRESSOROFMFLAIFMFLAHEATERPACKAGE NO.ELECTRICHEATPOWERSUPPLYDISCONNECTSIZEMin Max
PRE-START-UPFailure to observe the following warnings could resultin serious personal injury:1. Follow recognized safety practices and wear protec-tiv
START-UPUse the Start-Up Checklist supplied at the end of this book,and proceed as follows:Check for Refrigerant Leaks — Locate and repairrefrigerant
Fig. 16 — Cooling Charging Chart — 50ZH030Fig. 17 — Cooling Charging Chart — 50ZH036Fig. 15 — Cooling Charging Chart — 50ZH024Fig. 18 — Cooling Chargi
INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTSFor cooling operation, the recommended airflow is350 to 450 cfm per each 12,000 Btuh of rated coolingcapacity.Tab
UNIT CONTROLS — All compressors have the followinginternal-protection controls.High-Pressure Relief Valve — This valve opens when thepressure differen
Inspect air filter(s) at least once each month and replace(throwaway-type) or clean (cleanable-type) at least twice dur-ing each cooling season or when
Refrigerant Circuit — Inspect all refrigerant tubing con-nections and the unit base for oil accumulations annually.Detecting oil generally indicates a
TROUBLESHOOTINGCooling and Heating Troubleshooting ChartSYMPTOM CAUSE REMEDYCompressor and out-door fan will not start.Power failure Call power compan
Cooling and Heating Troubleshooting Chart (cont)SYMPTOM CAUSE REMEDYExcessive headpressure.Dirty air filter Replace filter.Dirty indoor or outdoor coil
UNITELECTRICALCHARACTERISTICSV-Ph-HzUNIT WEIGHT CENTER OF GRAVITY mm (in.)Lb Kg X Y Z50ZH024 208/230-1-60 232 106 356 (14.0) 483 (19.0) 305 (12.0)50ZH
PACKAGED SERVICE TRAININGOur packaged service training programs provide an excellent way to increase your knowledge of theequipment discussed in this
START-UP CHECKLIST(Remove and Store in Job File)I. PRELIMINARY INFORMATIONMODEL NO.:DATE:SERIAL NO.:TECHNICIAN:II. PRE-START-UP (insert checkmark in b
UNITELECTRICALCHARACTERISTICSV-Ph-HzUNIT WEIGHT CENTER OF GRAVITY mm (in.)Lb Kg X Y Z50ZH036 208/230-1-60, 208/230-3-60 277 126 356 (14.0) 483 (19.0)
UNITELECTRICALCHARACTERISTICSV-Ph-HzUNIT WEIGHT CENTER OF GRAVITY mm (in.)Lb Kg X Y Z50ZH060208/230-1-60, 208/230-3-60,460-3-60368 167 356 (14.00) 508
RECEIVING AND INSTALLATIONStep 1 — Check EquipmentIDENTIFY UNIT — The unit model number and serial num-ber are stamped on the unit identification plate
Select and size ductwork, supply-air registers andreturn-air grilles according to ASHRAE (American Societyof Heating, Refrigeration, and Air Condition
CONVERTING HORIZONTAL DISCHARGE UNITS TODOWNFLOW (VERTICAL) DISCHARGEBefore performing service or maintenance operations onthe system, turn off the ma
HIGH-VOLTAGE CONNECTIONS — The unit must havea separate electrical service with a field-supplied, water-proof disconnect switch mounted at, or within s
HIGH-VOLTAGEPOWER WIRINGENTRY HOLELOW-VOLTAGEWIRING ENTRYHOLEFig. 10 — Unit Electrical Connection Entry HolesELECTRICHEATERFUSESCIRCUITBREAKER(24v)IND