Carrier 58CTW 100 Series Instruction Manual

Browse online or download Instruction Manual for Cookers Carrier 58CTW 100 Series. Carrier 58CTW 100 Series Instruction manual User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 56
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
1
58CTW/CTY
V a r i a b l e --- S p e e d , E C M
I n d u c e d --- C o m b u s t i o n 2 --- S t a g e D e l u x e
4---Way Multipoise Gas Furnace
Series 100
Installation, Start---up, Operating and
Se rvice and Maint enance Ins t r uct io ns
SAFETY CONSIDERATIONS 2........................
INTRODUCTION 4..................................
CODES AND STANDARDS 4..........................
Safety 4...........................................
General Installation 4................................
Combustion and Ventilation Air 4......................
Duct Systems 4.....................................
Acoustical Lining and Fibrous Glass Duct 4...............
Gas Piping and Gas Pipe Pressure Testing 4...............
Electrical Connections 4..............................
Venting 4.........................................
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE 4.....................................
LOCATION 5.......................................
AIR FOR COMBUSTION AND VENTILATION 8.........
Outdoor Combustion Air Method 9....................
The Standard Method: 9............................
Combination of Indoor and Outdoor Air 10.............
INSTALLATION 10..................................
Bottom Return Air Inlet 10..........................
Side Return Air Inlet 10.............................
Leveling Legs (If Desired) 11........................
Bottom Return Air Inlet 11..........................
Suspended Furnace Support 11.......................
Platform Furnace Support 11.........................
Roll--Out Protection 12.............................
Bottom Return Air Inlet 12..........................
Side Return Air Inlet 12.............................
Filter Arrangement 13..............................
AIR DUCTS 13......................................
General Requirements 13............................
Ductwork Acoustical Treatment 13....................
Supply Air Connections 14..........................
Upflow and Horizontal Furnaces 14...................
Downflow Furnaces 14.............................
Return Air Connections 20..........................
Downflow Furnaces 20.............................
Upflow and Horizontal Furnaces 20...................
GAS PIPING 20.....................................
ELECTRICAL CONNECTION 21.......................
ACCESSORIES 23...................................
VENTING 23.......................................
START--UP, ADJUSTMENT, AND SAFETY CHECK 35.....
General 35........................................
Start--Up Procedures 36..............................
Adjustments 38.....................................
Check Safety Controls 45.............................
Checklist 45.......................................
SERVICE AND MAINTENANCE PROCEDURES 45.......
General 45........................................
Care and Maintenance 47.............................
Sequence of Operation 50.............................
Wiring Diagram 53..................................
Troubleshooting 54..................................
PARTS REPLACEMENT INFORMATION GUIDE 57.......
Always Ask For
Use of the AHRI Certified
TM
Mark indicates a
manufacturer’s participation in the program. For
verification of certification for individual products,
go to www.ahridirectory.org.
NOTE: Read the entire instruction manual before starting the
installation.
Portions of the text and tables are reprinted from NFPA 54/ANSI
Z223.1--2012E, with permission of National Fire Protection
Association, Quincy, MA 02269 and American Gas Association,
Washington DC 20001. This reprinted material is not the
complete and official position of the NFPA or ANSI on the
referenced subject, which is represented only by the standard in
its entirety.
Page view 0
1 2 ... 56

Summary of Contents

Page 1 - Series 100

158CTW/CTYV a r i a b l e --- S p e e d , E C MI n d u c e d --- C o m b u s t i o n 2 --- S t a g e D e l u x e4---Way Multipoise Gas FurnaceSeries 1

Page 2 - SAFETY CONSIDERATIONS

10Infiltration rates greater than 0.60 ACH shall not be used. Theminimum required volume of the space varies with the number ofACH and shall be determ

Page 3

111 3 / 4 1 3 / 4 1 3/ 4 1 3/ 4 5/ 16 5 / 16 5/ 16 5/ 16 (44mm) (8mm) (44mm) (8mm) (8mm) (8mm) (44mm) (44mm) A89014Fig. 10 --

Page 4 - PRECAUTIONS PROCEDURE

12PLENUMOPENINGCABDFLOOROPENINGA96283Fig. 11 -- Floor and Plenum Opening DimensionsRoll--Out ProtectionProvide a minimum 17--3/4--in. X 22--in. (451 X

Page 5 - LOCATION

13Table 3 – Opening Dimensions -- In. (mm)FURNACECASINGWIDTHIN. (mm)APPLICATIONPLENUM OPENING FLOOR OPENINGA B C D14–3/16(360)Upflow Applications on C

Page 6

14shall be accessible when the furnace is installed and shall be ofsuch a size that the heat exchanger can be viewed for possibleopenings using light

Page 7 - MINIMUM TO BURNERS

151 / 4 " (6mm) THREADED ROD4 REQ.SECURE ANGLEIRON TO BOTTOMOF FURNACE WITH3 #8 x 3/4" (19mm) SCREWSTYPICAL FOR 2 SUPPORTS1” (25mm) SQUARE,

Page 8 - VENTILATION

1630-IN . (762mm) MIN WORK AREA6 ″ M IN * TYPE-B VENT 17 3 / 4 ″22 ″SHEET MET AL SEDIMENT TRAP EQUIPMENT MANU AL SHUT -OFF GAS VA LV E LINE CONT A

Page 9 - A&BC&DD&EF&G

17DOWNFLOW RETURN AIR CONFIGURATIONS AND RESTRICTIONSA02163Fig. 19 -- Downflow Return Air Configurations and RestrictionsA02162Fig. 20 -- Horizontal R

Page 10 - INSTALLATION

18Table 4 – Air Delivery -- CFM (With Filter)*COOLING4AND HEATING AIR DELIVERY - CFM (Bottom Return5With Filter)(SW1-5 and SW2-2 set to OFF, except as

Page 11 - S Coil Box Part No. KCAKC

19Table 4 -- Air Delivery -- CFM (With Filter)* (CONTINUED)Unit SizeCooling Switch Settings External Static Pressure (ESP)SW2-8 SW2-7 SW2-6 0.1 0.2 0.

Page 12

2SAFETY CONSIDERATIONSFIRE, EXPLOSION, ELECTRICAL SHOCK, ANDCARBON MONOXIDE POISONING HAZARDFailure to follow this warning could result in dangerousop

Page 13

20Return AirConnectionsFIRE HAZARDA failure to follow this warning could cause personal injury,death and/or property damage.Never connect return--air

Page 14 - UPFLOW DOWNFLOW HORIZONTAL

21joint union between furnace gas control valve and exteriormanual equipment gas shutoff valve.A 1/8--in. (3 mm) NPT plugged tapping, accessible for t

Page 15 - " (6mm) THREADED ROD

22Table 6 – Electrical DataFURNACE SIZEVOLTS -HERTZ -PHASEOPERATING VOLTAGERANGE *MAX. UNITAMPSUNITAMPACITYMAX WIRELENGTH FT(M)‡MAX . FUSEOR CKT. BKRA

Page 16 - (559mm)

238. Remove cover from furnace J--Box.9. Route field ground wire through holes in electrical boxand casing, and into furnace J--Box.10. Reattach furna

Page 17

24115-VOLT FIELD-SUPPLIEDFUSEDDISCONNECT JUNCTIONBOX CONTROLBOX24-VOLTTERMINALBLOCK THREE-WIREHEATING-ONLY FIVEWIRE NOTE 2NOTE 11-STAGETHERMO

Page 18

25VENTINGThe furnace shall be connected to a listed factory built chimneyor vent, or a clay--tile lined masonry or concrete chimney. Ventinginto an un

Page 19

26A00275Fig. 27 -- Two--Stage Furnace with Single--SpeedAir ConditionerSee notes 2, 5, 8, 10, 11 and 12on the page following these figuresA03179Fig. 2

Page 20

27See notes 1, 2, 4, 11, 14, 15, and 16on the page following these figuresA03181Fig. 31 -- Dual--Fuel Thermostat with Two--Stage Furnaceand Single--S

Page 21 - Street Elbow

28NOTES FOR FIGURES 27 -- 341. Heat pump MUST have a high pressure switch for dual fuel applications.2. Refer to outdoor equipment Installation Instru

Page 22

29CHIMNEY INSPECTION CHARTFor additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211Chimneys, Fireplaces, V

Page 23

3A10269Fig. 1 -- Clearances to Combustibles

Page 24

30Masonry Chimney RequirementNOTE: These furnaces are CSA design--certified for use inexterior tile--lined masonry chimneys with a factory accessoryCh

Page 25

31Table 8 – Minimum Allowable Input Rating ofSpace--Heating Appliance in Thousands of Btuh per HourVENT HEIGHTFT. (M)INTERNAL AREA OF CHIMNEYSQ. IN. (

Page 26

32SEE NOTES: 1,2,4,7,8,9on the page followingthese figuresA03208Fig. 36 -- Upflow Application -- Vent Elbow UpSEE NOTES: 1,2,3,4,7,8,9on the pages fol

Page 27 - See notes 1 and 2 on the page

33SEE NOTES: 1,2,4,5,6,7,8,9,10on the page following these figuresA03207Fig. 40 -- Downflow Application -- Vent Elbow Left then UpSEE NOTES:1,2,3,4,5,

Page 28 - NOTES FOR FIGURES 27 -- 34

34SEE NOTES: 1,2,4,5,7,8,9 on the pagefollowing these figuresA03215Fig. 45 -- Horizontal Left Application -- Vent Elbow UpSEE NOTES: 1,2,4,5,7,8,9 on

Page 29 - CHIMNEY INSPECTION CHART

35Caution!! For the following applications, use the minimum vertical heights as specified below.For all other applications, follow exclusively the Nat

Page 30

36BURNER ORIFICEA93059Fig. 50 -- Orifice HoleR Y W G10 TURNSTHERMOSTAT SUBBASETERMINALS WITHTHERMOSTAT REMOVED(ANITICIPATOR, CLOCK, ETC.,MUST BE OUT O

Page 31

37SETUP SWITCHSWITCH NAMENORMAL POSITIONDESCRIPTION OF USESW1-1 Status Code Recovery OFFTurn ON to retrieve up to 7 stored status codes for troublesho

Page 32 - SEE NOTES:1,2,3,4,5,7,8,9

38A14310Fig. 54 -- Service LabelAdjustmentsFIRE HAZARDFailure to follow this warning could result in personalinjury, death and/or property damage.DO N

Page 33

39EXAMPLE 1: 0–2000 ft. (0--610 M) altitudeFor 22,000 Btuh per burner application use Table 12.Heating value = 1000 Btuh/cu ft.Specific gravity = 0.62

Page 34 - SEE NOTES: 1,2,4,5,7,8,9

4INTRODUCTIONThe Series 100 4--way multipoise Category I fan--assisted furnaceis CSA (formerly A.G.A. and C.G.A.) design--certified. ACategory I fan--

Page 35 - REGULATOR COVER SCREW

40the range specified on furnace rating plate. If temperat-ure rise is outside this range, proceed as follows:(1.) Check gas input for low-- and high-

Page 36

41A14327Fig. 55 -- Wiring Diagram

Page 37

42Table 11 – Gas Rate (CU ft./hr)SECONDS GFOR 1 REVOLUTIONSIZE OF TEST DIALSECONDSFOR 1 REVOLUTIONSIZE OF TEST DIAL1CuFt. 2CuFt. 5CuFt. 1CuFt. 2CuFt.

Page 38

43Table 12 – Orifice Size and Manifold Pressure (In. W.C.) for Gas Input Rate(Tabulated Data Based on 22,000 Btuh High--Heat/14,500 Btuh for Low--Heat

Page 39

44Table 12 -- Orifice Size and Manifold Pressure (In. W.C.) for Gas Input Rate (Con’t.)(Tabulated Data Based on 22,000 Btuh High--Heat/14,500 Btuh for

Page 40

45Check Safety ControlsThe flame sensor, gas valve, and pressure switch were all checkedin the Start--up procedure section as part of normal operation

Page 41 - Fig. 55 -- Wiring Diagram

46GeneralThese instructions are written as if the furnace is installed in anupflow application. An upflow furnace application is where theblower is lo

Page 42

47CARE ANDMAINTENANCEFIRE OR EXPLOSION HAZARDFailure to follow this warning could result in personalinjury, death and/or property damage.Never store a

Page 43 - (305 M) Above Sea Level)

48Table 13 – Filter Size Information -- In. (mm)FURNACE CASING WIDTHFILTER SIZEFIL TER TYPESIDERETURNBOTTOMRETURN14---1/2 (368)16 X 25 X 3/4(406 X 635

Page 44 - Above Sea Level)

49A05025Fig. 56 -- Igniter Position -- Side View1-7/8(47.6 mm)A05026Fig. 57 -- Igniter Position -- Top ViewIf it becomes necessary to clean the heat e

Page 45 - PROCEDURES

5AAB[736.9][736.9]2929Ø7/8Ø7/8[22.2][22.2]ACCESSORYACCESSORY5 15/165 15/16[150.7][150.7]28.3928.39[721.2][721.2]Ø7/8Ø7/8[22.2][22.2]ACCESSORYACCESSORY

Page 46

5013. Reconnect wires to the following components (Use con-nection diagram on wiring label, if wires were not markedfor reconnection locations.):a. Dr

Page 47

51repeat the ignition sequence for up to three more Tri-als--For--Ignition before going to Ignition--Lockout.Lockout will be reset automatically after

Page 48

52which is the true on--board CF selection as shown in Fig. 53.If the furnace control CPU switches from low--cooling tohigh--cooling, the furnace cont

Page 49 - (47.6 mm)

536. Heat pumpSee Fig. 29 -- 32 for thermostat connections.When installed with a heat pump, the furnace control auto-matically changes the timing sequ

Page 50

54Is AMBER LED status light on? Is there 24V at SEC-1 and SEC-2? Is there 115V at L1 and L2? Replace furnace control. Is door switch closed? Repl

Page 51

55 25 INVALID MODEL SELECTION OR SETUP ERROR – If status code 25 only flashes 4 times on power-up the control is missing its model plug PL4 and is de

Page 52

56PARTS REPLACEMENT INFORMATION GUIDECASING GROUPOuter doorBlower doorTop filler plateBottom filler plateBottom enclosureELECTRICALGROUPControl bracke

Page 53

6THE BLOWER IS LOCATEDTO THE RIGHT OF THEBURNER SECTION, ANDAIR CONDITIONED AIR ISDISCHARGED TO THE LEFT.THE BLOWER ISLOCATED BELOW THEBURNER SECTION,

Page 54 - Guide – Variable Speed

7 18-IN. (457.2 mm) MINIMUM TO BURNERSA93044Fig. 5 -- Installation in a GarageFIRE HAZARDFailure to follow this warning could result in personalinjur

Page 55

8Table 1 – Minimum Free Area Required for Each Combustion Air opening of Duct to OutdoorsFURNACEINPUT(BTUH)TWO HORIZONTAL DUCTS SINGLE DUC T OR OPENIN

Page 56 - Catalog No: 58CTW---03SI

91 SQ IN . PER 4000 BTUH* DUCTS TO O UTDOORS 1 SQ IN. PER 4000 BTUH* C IRCULA TING AIR DUCTS VENT THR OUGH R OOF D B A C E 1 SQ IN. PER 4000 BTUH* DUC

Comments to this Manuals

No comments