Installation, Start-Up andService InstructionsCONTENTSPageSAFETY CONSIDERATIONS ...1INSTALLATION ...1-8Step
High-Pressure Switch (HPS) — When the refriger-ant high-side pressure reaches 426 psig (2937 kPa), the HPSopens 24-v power to the compressor contactor
SERVICEWhen servicing unit, shut off all electrical power to theunit to avoid shock hazard or injury from rotating parts.Cleaning — Inspect unit inter
4. Adjust fan height as shown in Fig. 13.5. Tighten setscrews.6. Replace condenser-fan assembly.Capacity Control — Unit 38AKS012 Only — Asuction press
TROUBLESHOOTING GUIDESYMPTOM CAUSE REMEDYCompressor does not run —Contactor openPower off. Restore power.Fuses blown. Replace with correct fuses after
LEGEND AND NOTES FOR FIG. 15 AND 16C—Contactor, CompressorCAP — CapacitorCB — Circuit BreakerCH — Crankcase HeaterCLO — Compressor LockoutCOMP — Compr
START-UP CHECKLISTA. Preliminary InformationOUTDOOR: MODEL NO. SERIAL NO.INDOOR: AIR HANDLER MANUFACTURERMODEL NO. SERIAL NO.ADDITIONAL ACCESSORIESB.
CHECK VOLTAGE IMBALANCELINE-TO-LINE VOLTS: ABVAC VBC V(AB + AC + BC)/3 = AVERAGE VOLTAGE =VMAXIMUM DEVIATION FROM AVERAGE VOLTAGE =VVOLTAGE IMBALANCE
Table 1A — Physical Data — 50/60 Hz (English)UNIT 38 AK007 AK008 AK012 AKS008 AKS009 AKS012OPERATING WEIGHT (lb)Aluminum Coils (Standard) 340 370 395
Table 1B — Physical Data — 50/60 Hz (SI)UNIT 38 AK007 AK008 AK012 AKS008 AKS009 AKS012OPERATING WEIGHT (kg)Aluminum Coils (Standard) 154 168 179 231 2
CONSIDER SYSTEM REQUIREMENTS• Consult local building codes and NEC for special instal-lation requirements.• Allow sufficient space for airflow clearanc
UNIT 38 DIM. A DIM. B DIM. C DIM. D DIM. E DIM. FAK00718-61⁄29 18-23⁄49 —18-21⁄49 18-45⁄169 28-95⁄169[470.0] [375.0] — [362] [415] [846.5]AK00818-89 1
FILTER DRIER AND MOISTURE INDICATOR — The fil-ter drier is factory installed. Moisture indicator is field-supplied and should be installed just after li
Table 5 — Electrical DataUNIT38NOMINAL VOLTAGE(V-Ph-Hz)VOLTAGE RANGE COMPRESSOR OFM POWER SUPPLYMIN MAX RLA LRA FLA MCA MOCPAK007208/230-3-60 187 254
FIELD CONTROL WIRING — Install a Carrier-approvedaccessory thermostat assembly according to installationinstructions included with the accessory. Loca
START-UPPreliminary Checks1. Field electrical power source must agree with unit name-plate rating.2. Check that all internal wiring connections are ti