Installation Instructions
50HCQ
Single Package Rooftop
Heat Pump
with Puronr (R---410A) Refrigerant
S i z e s 0 7 --- 0 9
NOTE: Read the entire instruction manual before starting
the installation
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 2....................
INSTALLATION 6...............................
Jobsite Survey 6................................
Step 1 -- Plan for Unit Location 6..................
Roof Mount 7...............................
Step 2 -- Plan for Sequence of Unit Installation 7......
Curb--Mount Installation 7.....................
Pad--Mount Installation 7......................
Frame--Mount Installation 7....................
Step 3 -- Inspect Unit 7...........................
Step 4 -- Provide Unit Support 7...................
Roof Curb Mount 7..........................
Slab Mount (Horizontal Units Only) 7...........
Alternate Unit Support 7......................
Step 5 -- Field Fabricate Ductwork 9................
For Units with Accessory Electric Heaters 9......
Step 6 -- Rig and Place Unit 9.....................
Positioning on Curb 10.......................
Step 7 -- Convert to Horizontal & Connect Ductwork 10.
Step 8 -- Install Outside Air Hood 11...............
Economizer Hood Removal and Setup 11........
Two Position Damper Hood Removal and Setup 11..
Economizer Hood and Two--Position Hood 12.....
Step 9 -- Install External Condensate Trap and Line 12...
Step 10 -- Make Electrical Connections 13...........
Field Power Supply 13........................
Units without Factory--Installed Disconnect 13....
Units with Factory--Installed Disconnect 14.......
Convenience Outlets 14.......................
Factory--Option Thru--Base Connections 15.......
Units without Thru--Base Connections 16.........
Field Control Wiring 16.......................
Thermostat 16...............................
Unit without Thru--Base Connection Kit 16.......
Heat Anticipator Settings 16...................
Electric Heaters 17..............................
Single Point Boxes and Supplementary Fuses 18.....
PremierLinkt (Factory Option) 19.................
Supply Air Temperature (SAT) Sensor 19.........
Outdoor Air Temperature (OAT) Sensor 21.......
EconoMi$ert221...........................
Field Connections 21..........................
Space Temperature (SPT) Sensors 21............
Connect Thermostat 21.......................
Configure the Unit for Thermostat Mode 24......
Economizer Controls 24........................
Outdoor Air Enthalpy Control 24...............
Differential Enthalpy Control 24................
Return Air Enthalpy Sensor 24
.................
Indoor Air Quality (CO
2
sensor) 24.............
Outdoor Air Quality Sensor 25.................
Smoke Detector/Fire Shutdown (FSD) 25.........
Filter Status Switch 26........................
Supply Fan Status Switch 26...................
Remote Occupied Switch 26...................
Space Relative Humidity Sensor 26.............
Power Exhaust (output) 26.....................
CCN Communication Bus 26..................
RTU--MP Control System 28......................
Supply Air Temperature (SAT) Sensor 30.........
Outdoor Air Temperature (OAT) Sensor 30.......
EconoMi$ert230...........................
Field Connections 31..........................
Space Sensors 31............................
Economizer Controls 31........................
Outdoor Air Enthalpy Control 31...............
Page view 0
1 2 ... 48

Summary of Contents

Page 1 - Installation Instructions

1Installation Instructions50HCQSingle Package RooftopHeat Pumpwith Puronr (R---410A) RefrigerantS i z e s 0 7 --- 0 9NOTE: Read the entire instruction

Page 2 - SAFETY CONSIDERATIONS

10DETAIL “A”PLACE ALL SEAL STRIP IN PLACEBEFORE PLACING UNIT ON ROOF CURB. DUCT ENDSEE DETAIL “A”“C”“B”“A”914-1371(36"-54")SPREADERBARSREQUI

Page 3

11Step 8 — Install Outside Air HoodEconomizer Hood Removal and Setup --Factory Option —1. The hood is shipped in knock--down form and locatedin the re

Page 4

12Economizer Hood and Two--Position Hood —NOTE: If the power exhaust accessory is to be installedon the unit, the hood shipped with the unit will not

Page 5

13NOTE: Trap should be deep enough to offset maximum unit staticdifference. A 4” (102) trap is recommended.MINIMUM PITCH1” (25mm) PER10’ (3m) OF LIN

Page 6 - INSTALLATION

14Units with Factory--Installed Disconnect —The factory--installed option disconnect switch is locatedin a weatherproof enclosure located under the ma

Page 7 - Step 4 — Provide Unit Support

15Mount the weatherproof cover to the backing plate asshown in Fig. 19. Remove two slot fillers in the bottom ofthe cover to permit service tool cords

Page 8 - UNIT SIZE

16LOW VOLTAGECONDUITCONNECTORHIGH VOLTAGECONDUITCONNECTORC08637Fig. 21 -- Thru--Base Connection FittingsField--supplied and field--installed liquid--t

Page 9 - DIFFERENCE IN. (MM)

17RACEWAYHOLE IN END PANEL (HIDDEN)C08027Fig. 23 -- Field Control Wiring RacewayElectric Heaters50HCQ units may be equipped with field--installedacces

Page 10 - Ductwork (when required)

18TRACKFLANGEC08135Fig. 26 -- Typical Module InstallationSingle Point Boxes and Supplementary FusesWhen the unit MOCP device value exceeds 60--A,unit-

Page 11 - Screws for Metal Tray

19PremierLinkt (Factory--Option)C08199Fig. 29 -- PremierLink ControllerThe PremierLink controller (see Fig. 29) is compatiblewith Carrier Comfort Netw

Page 12

2Differential Enthalpy Control 31...Return Air Enthalpy Sensor 31...Indoor Air Quality (CO2sensor) 32...Outdoor A

Page 13 - FIRE HAZARD

20C10469Fig. 31 -- Typical PremierLink Wiring Schematic50HCQ

Page 14 - Units With Disconnect Option

21Outdoor Air Temperature (OAT) Sensor —The OAT is factory--mounted in the EconoMi$er2 (FIOPor accessory). It is a nominal 10k ohm thermistor attached

Page 15

22GJ4-12J4-10J4-8Y1Y22RR46J4-6J4-4W2C810C SPACETHERMOSTATPL CTBTHERMOSTATW1TB1 CTBTHERMOSTATC08119Fig. 36 -- Space Thermostat Conne

Page 16 - Field Wiring

23Table 4 – Space Sensor ModeTB1 TERMINAL FIELD CONNECTION INPUT SIGNAL1 T 5 5 --- S E N / T 5 6 --- S E N Analog (10k thermistor)2 RMTOCC Discrete, 2

Page 17 - Electric Heaters

24If the 50HCQ unit has an economizer system andfree--cooling operation is required, a sensor representingReturn Air Temperature must also be connecte

Page 18

258765432121HG24 VACOR24 VDCNCALARMRELAYCONTACTSCOMNO}0-10VDCSIG COM4-20mA++-+-J3 J4C08635Fig. 39 -- Indoor/Outdoor Air Quality (CO2)Sensor(33ZCSENCO2

Page 19

26On 50HCQ units equipped with factory--installed SmokeDetector(s), the smoke detector controller implements theunit shutdown through its NC contact s

Page 20

27signal pins must be wired to the signal ground pins.Wiring connections for CCN must be made at the 3--pinplug.At any baud (9600, 19200, 38400 baud),

Page 21 - Field Connections

28RTU--MP Control SystemThe RTU--MP controller, see Fig. 48, provides expandedstand--alone operation of the HVAC system plusconnection and control thr

Page 22

29C10470Fig. 50 -- Typical RTU--MP System Control Wiring Diagram50HCQ

Page 23 - Table 5 – Thermostat Mode

3Horizontal Connections / EconomizerVertical Connections / EconomizerC10464Fig. 1 -- Unit Dimensional Drawing: 07 — 08 Size Units50HCQ

Page 24 - Economizer Controls

30Table 8 – RTU--MP Controller Inputs and OutputsPOINT NAMEBACnet OBJECTNAMETYPE OF I/OCONNECTION PINNUMBERSINPUTSSpace Temperature Sensor sptsens AI

Page 25 - COVER REMOVED SIDE VIEW

31Field ConnectionsField connections for accessory sensors and input devicesare made the RTU--MP, at plugs J1, J2, J4, J5, J11 and J20.All field contr

Page 26

32To wire the return air enthalpy sensor, perform thefollowing:1. Use a 2--conductor, 18 or 20 AWG, twisted pair cableto connect the return air enthal

Page 27

33Input 8 or 9 is recommended for easy of installation. Referto Fig. 48 and Fig. 50 for wire terminations at J5.Remote Occupancy: The remote occupancy

Page 28 - RTU--MP Control System

34Local Access —BACview6Handheld: The BACview6is a keypad/displayinterface used to connect to the RTU--MP to access thecontrol information, read senso

Page 29

35Table 9 – LEDsThe LEDs on the RTU--MP show the status of certain functionsIf this LED is on... Status is...Power The RTU MP has powerRx The RTU MP i

Page 30

36Duct smoke sensorcontrollerFastener(2X)Controller coverConduit nuts(supplied by installer)Conduit support plateCover gasket(ordering option)Conduit

Page 31

37location and the tubing to the sampling tube be connected.See “Completing Installation of Return Air SmokeSensor:” for details.)Return Air Detector

Page 32

38Table 10 – Unit Wire/Fuse or HACR Breaker Sizing DataUNITNO M . V --- P h --- H ZIFM TYPEELEC. HTR P. E . NO C.O. or UNPWR C.O.CRHEATER***Nom(kW)FLA

Page 33 - Baud Rate Selections

39Table 10 — Unit Wire/Fuse or HACR Breaker Sizing Data (cont)UNITNO M . V --- P h --- H ZIFM TYPEELEC. HTR P. E . w/ PWRD C.O.CRHEATER***Nom(kW)FLA F

Page 34

4C10465Fig. 1 -- Unit Dimensional Drawing: 07 — 08 Size Unit (cont.)50HCQ

Page 35 - Smoke Detectors

40Table 10 — Unit Wire/Fuse or HACR Breaker Sizing Data (cont)UNITNO M . V --- P h --- H ZIFM TYPEELEC. HTR P. E . NO C.O. or UNPWR C.O.CRHEATER***Nom

Page 36 - Smoke Detector Locations

41Table 10 — Unit Wire/Fuse or HACR Breaker Sizing Data (cont)UNITNO M . V --- P h --- H ZIFM TYPEELEC. HTR P. E . w/ PWRD C.O.CRHEATER***Nom(kW)FLA F

Page 37 - Exhaust Tube

42Table 10 — Unit Wire/Fuse or HACR Breaker Sizing Data (cont)UNITNO M . V --- P h --- H ZIFM TYPEELEC. HTR P. E . NO C.O. or UNPWR C.O.CRHEATER***Nom

Page 38

43Table 10 — Unit Wire/Fuse or HACR Breaker Sizing Data (cont)UNITNO M . V --- P h --- H ZIFM TYPEELEC. HTR P. E . w/ PWRD C.O.CRHEATER***Nom(kW)FLAFL

Page 39

44Legend and Notes for Table 10LEGEND:BRKR --- Circuit breakerCO --- Convenient outletDD --- Direct driveindoor fan motorDISC --- DisconnectFLA --- Fu

Page 40

45Step 12 — Install AccessoriesAvailable accessories include:Roof CurbThru--base connection kit (must be installed before unitis set on curb)Manual ou

Page 41

4650HCQ

Page 42

4750HCQ

Page 43

48Copyright 2010 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 04/ 10Manufacturer reserves the right to

Page 44 - Legend and Notes for Table 10

5Horizontal Connections / EconomizerVertical Connections / EconomizerC10460Fig. 2 -- Unit Dimensional Drawing: 09 Size Units50HCQ

Page 45 - Pre--Start and Start--Up

6C10461Fig. 2 -- Unit Dimensional Drawing: 09 Size Unit (cont.)INSTALLATIONJobsite SurveyComplete the following checks before installation.1. Consult

Page 46

7Roof Mount —Check building codes for weight distributionrequirements. Unit operating weight is shown in Table 1.Step 2 — Plan for Sequence of Unit In

Page 47

8UNIT SIZE50HCQ*07-09C10462Fig. 4 -- Roof Curb Details: Size 07 — 09 Units50HCQ

Page 48 - Catalog No: 50HCQ---02SI

9A-B0.5” (13)B-C1.0” (25)A-C1.0” (25)MAXIMUM ALLOWABLEDIFFERENCE IN. (MM)C06110Fig. 5 -- Unit Leveling TolerancesStep 5 — Field Fabricate DuctworkCabi