CarrierStart-Up instructions19DAOIL HEATER INDICATOR LIGHTOSso/c/e. ‘»nd oo /or7^er S//ó/^/ z^k^/ {do record r) {dr^'^S fcr /~o ôhiio/ô/e {ak)/o
1 ELECTRONIC CONTROL ON-OFF SWITCH 112 MACHINE START BUTTON 123 CHILLED WATER THERMOSTAT 134 MACHINE STOP BUTTON 145 OIL PUMP AUTO-MANUAL SWI
Calibrating Pneumatic Transducer - Pneumatic control is accomplished by a transformer which converts a 3-15 psi pneumatic signal regul
INSTRUCTING THE CUSTOMER OPERATORUse the following as a guide in giving operating instructions to the customer operator:1. Be sure that the cust
PURGE VALVE OPERATION PLATEPURGE PUMP SWITCHCHILLED WATER LOW TEMP CUTOUTPURGE OPERATING VALVES (6)Fig. 2 - 19DA Rear View1.2.Record and date vacuu
5. Repair any leaks found.6. Reinspect joints and flanges with the leak detector to ensure that all leaks have been found and repair
Check Starter - Before starting the 19DA, check starter as follows:1. Remove the contactor arc chutes. Be sure contactors move freely
.fCheck Operation of Safety Controls - Disconnect main motor leads at starter to prevent compressor motor operation while performing
Table 2 - Setting Safety Controls (Contd)SAFETY OR CONTROL DEVICE RECOMMENDED SETTING2. Refrigerant Low-Temperature Cutout (Fig. 1)1. Install jumper
Table 3 - Motor Overload ModuleCalibrating Electronic Controls - Honeywell (Fig. 4) or Barber-Colman (Fig. 5)SEQUENCEHB-CPROCEDURE1. Check Voltage Sig
Calibrating Electronic Controls - Honeywell Only (Fig. 4)Table 4 - Chilled Water ModuleSEQUENCEPROCEDURE (Compressor Operating)1. Set Differential Adj
1 ELECTRONIC CONTROL ON-OFF SWITCH a MACHINE START BUTTON3 VANE DECREASE BUTTON4 CHILLED WATER THERMOSTAT5 VANE INCREASE BUTTON6 MACHINE STOP BUT