48PD and 50PD-05, 06
Displacement Ventilation or Single-Zone Variable Airflow Rooftop Units
Single Package, Electric Cooling, Gas or Optional Electric Heating
with PURON® (R-410A) Refrigerant and COMFORTLink™ Controls
Advanced Product Data
This manual provides product information related with the usage and application of the Centurion 48/50PD product series. It is to be used in
conjunction with the Packaged RTU Builder software for performance data and unit selection until replaced by the product data manual.
TABLE OF CONTENTS
FEATURES AND BENEFITS . . . . . . . . . . . . . . . . . . . . . . . . . . 1
UNIT OPERATION SUMMARY . . . . . . . . . . . . . . . . . . . . . . . 2
MODEL NUMBER NOMENCLATURE . . . . . . . . . . . . . . . . . 3
ARI CAPACITY RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
HEATING TABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
FACTORY OPTIONS AND ACCESSORIES . . . . . . . . . . . . 10
OPTIONS & ACCESSORY WEIGHTS . . . . . . . . . . . . . . . . . 11
BASE UNIT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 12
CURB DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
SELECTION PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . 15
COOLING CAPACITY DATA . . . . . . . . . . . . . . . . . . . . . . . . 16
INDOOR FAN DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
TYPICAL WIRING SCHEMATICS . . . . . . . . . . . . . . . . . . . . 24
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . 27
APPLICATION DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
FEATURES AND BENEFITS
The Centurion 48/50PD rooftop units use Puron® (R-410A)
refrigerant and ComfortLink™ DDC controls. These units are
intended to be used in a either a displacement ventilation or a
single-zone variable air volume application. In addition the
standard features and benefits of a Centurion rooftop unit, the PD
units include a factory installed variable capacity compressor and
variable frequency drive indoor fan motor.
PERFORMANCE FEATURES INCLUDE:
• Puron (R-410A) HFC refrigerant
• SEER up to 15.2, EER up to 12.8
• ARI certified outdoor sound levels as low as 72 db
• Fully hermetic, digital scroll compressors with capacity
modulation provide any capacity between 15 and 100%.
• ComfortLINK Direct Digital Controls (DDC)
• Phase loss and compressor reverse rotation protection
• TXV refrigerant metering system on each circuit
• High Pressure, Low Pressure/Loss of charge, and Freeze
protection.
• Solid core liquid line filter drier on each circuit.
• Ambient cooling operation from 0
o
F up to 125
o
F
• Foil faced insulation throughout entire unit
• Pre-painted exterior panels and primer-coated interior panels
tested to 500 hours ASTM B117 (scribed specimen)salt spray
protection
• Rust-proof, internally sloped condensate pan conforms to
ASHRAE 62 standards
• Evaporator fan motor system with high performance belt drives
and variable speed motors from 20% to 100%
• Internally protected, shaft down totally enclosed condenser motors
• 2 inch filter standard, field convertible to 4 inch capability
• 24 volt control system with resettable circuit breakers
• Induced draft combustion (gas units)
• Redundant gas valves with up to two stages of heating (gas units)
• Models 48/50PD 05-06 units are ENERGY STAR qualified
MAINTENANCE FEATURES:
• Single slab, single pass evaporator and condenser coils with dual
side access panels
• Hinged access doors with, quick turn latches and door retainers
• Slide out indoor fan assembly for added service convenience
• Dedicated, fully insulated compressor compartment
• Rust-proof, slide out evaporator condensate pan
• Permanently lubricated evaporator, condenser and inducer motors
INSTALLATION FEATURES:
• Thru the bottom and side weather tight electrical access plate
• Thru the bottom and side gas connection capabilities
• Single point electrical and gas connections
• Return and supply duct fits between 24” on center joist
• Field convertible from vertical to horizontal airflow
• Single piece outdoor air hoods
• Full perimeter base rail with built-in rigging adapters and fork
truck slots
FACTORY INSTALLED OPTIONS INCLUDE:
• Supply and/or return air smoke detectors
• Powered or non-powered 115 volt convenience outlet
• Non-fused disconnect switch or circuit breaker
• Dry bulb or enthalpy economizer with/without return air CO
2
sensor
• Two-position motorized outdoor damper
• Barometric relief damper
• Power Exhaust
• Condenser coil guard
• Copper/Copper coils
• Pre-coated condenser coil
• E-coated coils
• Fan status and filter status switches
• High static indoor fan and drive systems
• Factory or field installed electric heaters (electric heat units)
• Stainless steel gas heat exchanger (gas units)
• Low NOx models that meet California Air Quality Management
requirements (gas units)
Page view 0
1 2 ... 40

Summary of Contents

Page 1 - Advanced Product Data

148PD and 50PD-05, 06 Displacement Ventilation or Single-Zone Variable Airflow Rooftop Units Single Package, Electric Cooling, Gas or Optional Electr

Page 2 - SINGLE-ZONE VAV SUMMARY

10 48PD 05-06FIOP and Accessory Table Category ITEM STANDARD FEATURE OPTION* ACCESSORY† Cabinet Hinged Access Panels X X

Page 3

11Accessory Weight Adders 05 06 48PD Accessory Weights lbs kg lbs kg 2-position damper 30 14 30 14 4-in Filter Capability No Additional Weight Ba

Page 6

40ACCESSORY DIMENSIONS -- 48PG03--07Roof Curb05-0605-0648PD48PDC0731348PG

Page 7 - 48PD PHYSICAL DATA TABLE

1548/50PD SELECTION PROCEDURE I. Determine cooling and heating requirements at design conditions given the following data: Vertical or Horizontal sup

Page 8

1648PD05 AND 50PD05 (4 Tons) — MAXIMUM COOLING CAPACITY TABLE Evaporator Entering Air (CFM) Condenser 1200 1600 2000 Air Temp Evaporator Enter

Page 9 - 50PD PHYSICAL DATA TABLE

1748PD06 AND 50PD06 (5 Tons) — MAXIMUM COOLING CAPACITY TABLE Evaporator Entering Air (CFM) Condenser 1200 2000 2500 Air Temp Evaporator Enter

Page 10 - Table

18INDOOR FAN DATA 48PD and 50PD Fan Motor and Drive Data Vertical Supply/Return UNIT SIZE 05 06 Voltage (volts) 208/230 and 460 208/230 and 460 L

Page 11 - Accessory Weight Adders

19ELECTRICAL DATA 48PD 05 - 06 WITHOUT POWERED CONVENIENCE OUTLET NOMINAL POWER SUPPLY VOLTAGE RANGE COMP. OFM IFM POWER SUPPLYDISCONNECT SIZE 48

Page 12

2UNIT SUMMARY There are two key elements that separate a Centurion PD unit from other Centurion units; the use of a variable speed fan and a modulat

Page 13

20ELECTRICAL DATA – CONT’D 50PD-05 WITHOUT POWERED CONVENIENCE OUTLET VOLTAGE RANGE COMP. OFM PWR EXH IFM ELECTRIC HEAT POWER SUPPLY DISCONNECT SI

Page 14 - Roof Curb

21ELECTRICAL DATA – CONT’D 50PD-06 WITHOUT POWERED CONVENIENCE OUTLET VOLTAGE RANGE COMP. OFM PWR EXH IFM ELECTRIC HEAT POWER SUPPLY DISCONNECT SI

Page 15 - 48/50PD SELECTION PROCEDURE

22ELECTRICAL DATA – CONT’D 50PD-05 WITH POWERED CONVENIENCE OUTLET VOLTAGE RANGE COMP. OFM PWR EXH IFM ELECTRIC HEAT POWER SUPPLY DISCONNECT SIZE

Page 16

23ELECTRICAL DATA – CONT’D 50PD-06 WITH POWERED CONVENIENCE OUTLET VOLTAGE RANGE COMP. OFM PWR EXH IFM ELECTRIC HEAT POWER SUPPLY DISCONNECT SIZE

Page 20 - ELECTRICAL DATA – CONT’D

2748/50PD Sequence of Operation GENERAL The 48PD and 50PD rooftop units use Puron® (R-410A) refrigerant and ComfortLink™ DDC controls. The PD units

Page 21

28 Reset of the Cooling Supply Air Set Point is set by the configuration variables SASP Maximum Reset Down (SASPMAXD) and SASP Maximum Reset Up (SASP

Page 22

29 Cooling Mode Using Space Temperature Sensor T55, T56 or T58 and Humidistat Enhanced dehumidification can be provided when a humidistat (HL38MG029

Page 23

348PD and 50PD Model Number Nomenclature

Page 24

30APPLICATION DATA Ductwork Ductwork should be attached to the curb on all units. Ductwork should NOT be attached to the unit. Interior installatio

Page 25

31 Low Ambient Applications In most low ambient cooling situations, the optional Carrier economizer can adequately cool the space by bringing in low

Page 26

32GUIDE SPECIFICATIONS 48PD - Packaged Rooftop Electric Cooling Unit with Gas Heat Variable Capacity, Variable Air Volume Cooling Constant Air Volume

Page 27 - Temperature

333. Induced--draft blower shall be of the direct driven, single inlet, forward--curved, centrifugal type. It shall be made from aluminized steel wit

Page 28 - Supply Air Temperature

343. Optional MERV-8 pleated filters of commercially available sizes shall be available. 4. Standard 2-in. filter rack shall be field convertible to

Page 29 - Fig. 3 – Economizer Logic

355. * Manual Outdoor Air Damper: a. The damper shall admit up to 33% outdoor air. b. Shall include hood, damper plate, and screen. c. Shall be avail

Page 30 - APPLICATION DATA

36 GUIDE SPECIFICATIONS 50PD Packaged Rooftop Electric Cooling Unit with Optional Electric Heat Variable Capacity, Variable Air Volume Cooling Consta

Page 31 - 2, is a factory

37thermally protected, and be of a shaft down design to protect from direct contact from harsh environments. 3. Induced-draft blower shall be of the

Page 32 - GUIDE SPECIFICATIONS

38h. Configurable alarm light shall be provided which activates when certain types of alarms occur. i. Compressor minimum run time (3 minutes) and mi

Page 33

398. Single Enthalpy Sensor: The enthalpy sensor shall provide economizer control based on outdoor air enthalpy. The economizer control shall include

Page 34

4ARI CAPACITY RATINGS Model Nominal Tons * Cooling Capacity (MBTUH) SEER EER Rated CFM SOUND RATING (dB) 48PD 05 4 47,500 15.2 12.8 1,60

Page 36

548PD 05-06 GAS HEAT CAPACITIES AND EFFICIENCIES VERTICAL & HORIZONTAL SUPPLY UNITS (NATURAL GAS) - SINGLE PHASE 48PD Standard Stainless Steel

Page 37

650PD 05-06 ELECTRIC HEAT CAPACITIES Volt-Ph-HzHeater NumberFLANom. kW-0.0-CRHEATER208A00 10.0 3.8-CRHEATER209A00 15.0 5.6-CRHEATER210A00 20.0 7.5-C

Page 38

748PD PHYSICAL DATA TABLE 48PD--05 48PD--06NOMINAL CAPACITY (TONS)45OPERATING WEIGHT (lbs) *BASE UNIT 901 921Economizer Vertical / Horizontal 40 /

Page 39

848PD PHYSICAL DATA TABLE – CONT’D GAS HEAT SECTION# of Gas Valves 1 1Gas Supply Line Pressure Range (in. wg.) 5.0 - 13.0 5.0 - 13.0Gas Supply Line

Page 40

950PD PHYSICAL DATA TABLE 50PD--05 50PD--06NOMINAL CAPACITY (TONS)45OPERATING WEIGHT (lbs)Base Unit * 901 921Economizer Vertical / Horizontal 40 / 5