48GP (N) 024-060, 48JZ (N) 024-060
50GL 024-060, 50JZ 024-060
ICM FIOP Installation Instructions
Installation, Start-Up, and Operating Instructions
NOTE: Read the entire instruction manual before starting the
installation.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS .....................................................1
INTRODUCTION ..........................................................................2
RECEIVING AND INSTALLATION ..........................................2
ICM FIOP PRE-START-UP..........................................................2
Electrical Connections ..............................................................2
Control Voltage Connections ..............................................2
Standard Connection............................................................2
Easy Select™—48GP..........................................................2
48GP Sequence of Operation..............................................4
Easy Select™—48JZ...........................................................5
48JZ Sequence of Operation...............................................7
Easy Select™—50GL & 50JZ............................................7
50GL & 50JZ Sequence Of Operation...............................9
ICM FIOP START-UP ................................................................10
48GP Start-Up (ICM FIOP) ...................................................10
48JZ Start-Up (ICM FIOP) ....................................................10
50GL: Start-Up (ICM FIOP)..................................................11
50JZ: Start-Up (ICM FIOP) ...................................................11
ELECTRICAL DATA & SCHEMATICS—ICM FIOP.............12
Physical Data & Electrical Schematics..................................12
Tables For System Set-Up......................................................12
CARE AND MAINTENANCE...................................................12
TROUBLESHOOTING ...............................................................13
START-UP CHECKLIST............................................................13
NOTE TO INSTALLER READ THESE INSTRUCTIONS
CAREFULLY AND COMPLETELY before installing this unit.
Also, make sure the Owner’s Manual and Service Instructions are
left with the unit after installation.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified personnel should install, repair, or service
air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of
cleaning coils and filters. All other operations should be performed
by trained service personnel. When working on air-conditioning
equipment, observe precautions in the literature, tags, and labels
attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguisher
available for all brazing operations.
Improper installation, adjustment, alteration, service, mainte-
nance, or use can cause explosion, fire, electric shock, or
other occurrences, which could cause serious injury or death
or damage your property. Consult a qualified installer or
service agency for information or assistance. The qualified
installer or agency must use only factory-authorized kits or
accessories when modifying this product.
Recognize safety information. This is the safety-alert symbol .
When you see this symbol on the product or in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAU-
TION, and NOTE. Danger identifies the most serious hazards,
which will result in severe personal injury or death. Warning
indicates a condition that could cause serious personal injury or
death. Caution is used to identify unsafe practices, which would
result in minor personal injury or product and property damage.
NOTE is used to highlight suggestions which will result in
enhanced installation, reliability, or operation.
The power supply (volts, phase, and hertz) must correspond to that
specified on unit rating plate.
The electrical supply provided by the utility must be sufficient to
handle load imposed by this unit. Electrical supply must match the
voltage requirements listed on unit rating plate.
This installation must conform with local building codes and with
NEC (National Electrical Code). Refer to provincial and local
plumbing or waste water codes and other applicable local codes.
Fig. 1—Puron® Unit (48GP Shown)
C99088
Visit www.carrier.com
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 1a 1a
PC 101 Catalog No. 534-80085 Printed in U.S.A. Form 48–21SI Pg 1 10-01 Replaces: 48–20SI
Page view 0
1 2 3 4 5 6 ... 29 30

Summary of Contents

Page 1 - 50GL 024-060, 50JZ 024-060

48GP (N) 024-060, 48JZ (N) 024-06050GL 024-060, 50JZ 024-060ICM FIOP Installation InstructionsInstallation, Start-Up, and Operating InstructionsNOTE:

Page 2 - Connections

value. If circuit R to G is open (0–v.) for super dehumidifymode, the motor delivers reduced airflow to maximize thehumidity removal of the system whi

Page 3

(2.) COOLING MODE—Press MODE button on the Thermidistat™ until COOLicon is displayed. Cooling begins within 10 sec. andremains on for 4 minutes. Obser

Page 4 - De-Humidify Mode-48GP

cooling cycle remains ‘‘on’’ until the room temperature drops topoint that is slightly below the cooling control setting of the roomthermostat. At thi

Page 5

f. Loosen set-screw that secures wheel to motor shaft, removescrews that secure motor mount brackets to blower housing,and slide motor and motor mount

Page 6 - De-Humidify Mode-48JZ

Fig. 14—ICM FIOP Electric Schematic—Unit 48GPC0103514

Page 7

Table 4—ICM FIOP Physical Data—Unit 48JZTHIS DATA APPLIES TO 48JZ UNITS WITH THE ICM INDOOR MOTOR FIOPUNIT SIZE 48JZ 024040 030040 030060 036060 03609

Page 8

Table 5—ICM FIOP Physical Data—Unit 48JZ (Continued)THIS DATA APPLIES TO 48JZ UNITS WITH THE ICM INDOOR MOTOR FIOPUNIT SIZE 48JZ 048090 048115 048130

Page 9

Fig. 15—ICM FIOP Electric Schematic—Unit 48JZC0110117

Page 10

Table 7—ICM FIOP Physical Data—Unit 50GLTHIS DATA APPLIES TO 50GL UNITS WITH THE ICM INDOOR MOTOR FIOPUNIT SIZE 024 030 036 042 048 060NOMINAL CAPACIT

Page 11

Table 8—50GL with ICM FIOP Electrical DataUNITSIZE 50GLV-PH-HZVOLTAGERANGECOMPRESSOROUTDOORFANMOTORINDOORFANMOTORELECTRICHEATSINGLE POINTPOWER SUPPLYM

Page 12

Approved for outdoor installation on wood flooring or on class A,B or C roof covering materials.Before performing service or maintenance operations on

Page 13

Fig. 16—ICM FIOP Electrical Schematic—50GLC0103720

Page 14

Table 9—ICM FIOP Physical Data—Unit 50JZTHIS DATA APPLIES TO 50JZ UNITS WITH THE ICM INDOOR MOTOR FIOPUNIT SIZE 50JZ024 50JZ030 50JZ036 50JZ042 50JZ04

Page 15

Table 10—50JZ with ICM FIOP Electrical DataUNITSIZE 50JZV-PH-HZVOLTAGERANGECOMPRESSOROUTDOORFANMOTORINDOORFANMOTORELECTRICHEATSINGLE POINTPOWER SUPPLY

Page 16

Fig. 17—ICM FIOP Electrical Schematic—50JZc0103623

Page 17

Table 11–48GP & 48JZ Cooling (and Heat Pump Heating-48JZ only)Dry Coil ICM AirflowSmall CabinetUNITSIZECFM ADJUSTPIN SELECTLO PIN NOM PIN HI PINEX

Page 18

Table 13—48GP & 48JZ Gas Heating ICM AirflowSmall CabinetEASY SELECT™BOARD SETTING (CFM)700 800 1100 1250UnitSizeExternalStaticPressure0.0–0.4 0.4

Page 19 - Multiplication Factors

Table 16—50GL/50JZ Cooling & Heating Dry Coil ICM AirflowSmall CabinetUNITSIZECFM ADJUSTPIN SELECTLO PIN NOM PIN HI PINEXTERNAL STATICPRESSURE RAN

Page 20

Table 19—ELECTRIC HEAT PRESSURE DROP TABLE (in. wg)Small CabinetSTATICCFM500 600 700 800 900 1000 1100 1200 1300 1400 1500 16005kW 0.00 0.00 0.00 0.00

Page 21

ICM QUICK REFERENCE GUIDEc01034EASY SELECTHEATER/MOTORAUX HEAT KW/CFM0-301075SEC1 SEC2J1AC/HP SIZE036 030 024 018ACHP-COMFORTHP-EFFNOM HIENHLOSYSTEM T

Page 22

c01999START-UP CHECKLIST(Remove and Store in Job File)I. Preliminary InformationMODEL NO.:_________________________________SERIAL NO.:________________

Page 23

The ICM motor uses the selected taps to modify its operation to apre-programmed table of airflows.The unit must be configured to operate properly with

Page 24 - Heat Pump Efficiency

Copyright 2001 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 4821siManufacturer reserves the right to discontinue, or change at any time

Page 25

(2.) AC/HP Size-Factory selected to match system size, pleaseverify.(3.) SYSTEM TYPE-Factory selected on 48GP system AC-AIR CONDITIONER.(4.) AC/HP CFM

Page 26

b. COOLING MODE(1.) If indoor temperature is above temperature set point andhumidity is below humidity set point, thermostat closescircuits R to G, R

Page 27 - = 11.25 capacity at 208-v

(4.) ENH (enhanced) selection provides a 30 sec. cooling &heat pump on delay with no airflow, plus 150 seconds at 70percent airflow and no off del

Page 28 - QUICK REFERENCE GUIDE

to a level which causes the Thermidistat™ to close its contacts.When the contacts close, the airflow will return to 100 percentof selected cooling air

Page 29

and continuous operation. (See Tables 16, 17 & 18 for airflowdelivery and minimum CFM.) Note that airflow marked is theairflow which will be suppl

Page 30 - Book 1 4

This configuration provides the following comfort enhance-ments:(a.) A 30 sec blower on delay with 150 sec at 70 percentairflow to allow the indoor co

Comments to this Manuals

No comments