39NC
39NC Rooftop Central Station Air Handler
Model 39NC
3,500-46,000 cfm, sizes 7-92
Carrier’s 39NC Rooftop Air Handling Unit is available in nominal airflow ranges from 3,500
to 46,000 cfm. The units may be curb mounted or pier mounted and set the standard for
water-tight integrity. The unit is designed to withstand water leakage at cabinet pressures of
-5" w.g. while subject to a rainfall rate of 13 inches per hour. The 39NC is available in draw-thru
or blow-thru configurations. Heating and cooling flexibility is achieved with DX, chilled water,
hot water, or steam coils. Indoor air quality features include double-walled construction and
sloped, stainless steel drain pans.
Features
Double-walled construction, with 2", 3 lb
mineral wool insulation.
Internally isolated fan sled assemblies -
reduce vibration transmission.
Gasketing between overlapping panels -
ensures leak-free performance.
Casing withstands 5" w.g. negative pressure
and 9" w.g. positive pressure.
Water-tight design.
16 gauge exterior panels.
Double-walled access doors.
Double-walled condensate drain
pan with stainless steel liner.
ARI 410 certified heating and
cooling coils.
ARI 430 fan and cabinet system.
Small footprint.
Coil tracks to allow slide-out coil
removal.
Component and accessory flexibility
to meet a wide variety of applications.
Curb or pier mounted.
ETL agency approved.
Nominal Capacity Coil
Model 50Hz 60Hz Area
L/s cfm
39NC07 1650 3500 6.7
39NC09 2123 4500 9
39NC11 2595 5500 10.5
39NC13 3067 6500 13
39NC17 4010 8500 16.2
39NC21 4954 10500 20.8
39NC26 6133 13000 25.8
39NC32 7549 16000 32.5
39NC39 9200 19500 38.8
39NC49 11560 24500 49.2
39NC61 14390 30500 60.8
39NC74 17457 37000 73.8
39NC92 21703 46000 91.6
Carrier’s 39NC Rooftop Air Handler sets the standard for quality construction and water-tight
integrity. This unit design has undergone rigorous testing in order to ensure a weathertight
unit interior and thus promote healthy IAQ. Units may be supplied as standard with forward
curved or air foil fan systems.
The 39NC is a horizontal draw thru or blow thru unit. The entire unit is ARI 430 certified and
the coils are ARI 410. In addition, the unit is agency approved to the latest safety standards
by ETL.
Note: Airway length and weight are dependent
upon unit configuration. Check product
catalog for component dimensions