
24ANB6
Infinityr Air Conditioner with Puronr Refrigerant
1---1/2 to 5 Nominal Tons (Siz e 18---60)
Wiring Diagram
1. Compressor and fan motor furnished with inherent thermal protection.
2. To be wired in accordance with National Electric Code (N.E.C.) and local codes.
3. N.E.C. Class 2, 24V circuit, min. 40VA required, 60VA on units installed with LLS.
4. Use copper conductors only from disconnect to unit suitable for at least 75ºC (165ºF).
5. For communicating control only.
6. If indoor section has a transformer with a grounded secondary, connect the grounded side to "C" on
the circuit board.
7. If any of the original wire, as supplied, must be replaced, use the same or equivalent wire.
8. Check all electrical connections inside control box for tightness.
9. Do not attempt to operate unit until service valves have been opened.
10. Symbols are electrical representation only.
11. When start relay and start Capacitor are installed, start Thermistor is not used.
12. In case of non-communicating Indoor system, disconnect factory provided wires from A,B,C, and D
terminals. Using factory provided wires, connect to R, C and/or Y Terminals per installation
instructions. Connect field 24V wires to factory provided wires, cap or remove unused factory provided
wires.
* MAY BE FACTORY OR FIELD INSTALLED
+t°
*
ST
* CHS
*
CH
23
R
C
S
5
2
1
L1
ODF
ODFR
L2
23
CONT
ODF
CAP
F
C
COMP
H
*
SC
*
SR
GND
EQUIP
21
11
L1
CONT
THIS CONTROL BOARD
CONTAINS A FIVE
MINUTE SHORT CYCLE
PROTECTOR.
A FIVE MINUTE DELAY
WILL OCCUR BETWEEN
COMPRESSOROFF/ON
CYCLES.
NOTE
C
*
HPS
R
LLSR
CONT
OAT
OCT
LPS
INPUT
OUTPUT
L
O
G
I
C
ODFR
LLSR
K4
LS
Y
L1
VS
VR
A
B
C
D
CB
K4
(NOTE #5)
YEL / BLU
VIO
COMP
ODF
BRN
BLK
YEL
S
C
R
BLU
BLK
YEL
RED or BLK
CONT
208/230 1Ø
POWER
SUPPLY
EQUIP
GND
L1
L2
BLU
CAP
H
C
F
YEL
*
ST
+
t
BLU
YEL
YEL
*
SC
*
CHS
*
SR
(NOTE #12)
1
2
5
*
CH
BLK
BLK
or
RED
BLK
BRN
BLK
BRN / YEL
YEL
PL4 PL3
PL2
OCT
OAT
PL5
BRN
BRN
BLK
BLK
BLU
*
LPS
*
HPS
YEL/PNK
BLU/PNK
BLU/PNK
YEL/PNK
11
21
23
23
C
C
OPTIONAL 2-WIRE
LS
Y
C
R
TO INDOOR UNIT
NOTE #12
CC
13
LPS
1
HPS
12
2
VS
VR L1 ODF
1
2
3
4
5
OCT
OAT
A
B
C
D
LS
Y
C
R
UTIL
TO INDOOR UNIT
COMM
STATUS
CB
P1
HK38EA004
3-WIRE
(NOTE #5)
NOTE #12
OPTIONAL
RED
GRN
YEL
WHT
AS PROVIDED BY
MANUFACTURER
NOTES:
SCHEMATIC DIAGRAM (LADDER FORM)
LEGEND
FACTORY POWER WIRING
FACTORY CONTROL WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
CONDUCTOR ON CIRCUIT BOARD
COMPONENT CONNECTION
1/4 - INCH QUICK CONNECT TERMINALS
FIELD SPLICE
JUNCTION
PLUG RECEPTACLE
CONNECTION DIAGRAM
1. Compressor damage may occur if system is over charged.
2. This unit is factory charged with R-410A in accordance with the amount shown
on the rating plate. The charge is adequate for most systems using matched
coils and tubing not over 15 feet long. Check refrigerant charge for maximum
efficiency. See Product Data Literature for required Indoor air Flow Rates and
for use of line lengths over 15 feet.
3. Relieve pressure and recover all refrigerant before system repair or final
disposal. Use all service ports and open all flow-control devices, including
solenoid valves.
4. Never vent refrigerant to atmosphere. Use approved recovery equipment.
CAUTION
CONDENSING UNIT CHARGING INSTRUCTIONS
For use with units using R-410A refrigerant
COOLING ONLY
CHARGING PROCEDURE
1. Only use subcooling charging method
when OD ambient is greater than 70ºF
and less than 100ºF, indoor temp is
greater than 70ºF and less than 80ºF,
and line set is less than 80 ft.
2. Operate unit a minimum of 15 minutes
before checking the charge.
3. Measure liquid service valve pressure
by attaching an accurate gauge to the
service port.
4. Measure the liquid line temperature by
attaching an accurate thermistor type
or electronic thermometer to the
liquid line near the outdoor coil.
5. Refer to unit rating plate for required
subcooling temperature.
6. Find the point where the required
subcooling temperature intersects the
measured liquid service valve pressure.
7. To obtain the required sub-cooling
temperature at specific liquid line
pressure, add refrigerant if liquid line
temperature is higher than indicated.
When adding refrigerant, charge in
liquid form using a flow restricting
device into suction service port.
Recover refrigerant if temperature is
lower. Allow a tolerance of +/- 3ºF.
REQUIRED LIQUID LINE TEMPERATURE
Required Subcooling
Temperature (ºF)
Liquid
Pressure
at Service
Valve (psig)
68
10
12 14
16
251
259
266
274
283
291
299
308
317
326
335
345
354
364
374
76 74 72 70 68
78 76 74 72 70
80 78 76 74 72
82 80 78 76 74
84 82 80 78 76
86 84 82 80 78
88 86 84 82 80
90 88 86 84 82
92 90 88 86 84
94 92 90 88 86
96 94 92 90 88
98 96 94 92 90
100 98 96 94 92
102 100 98 96 94
104 102 100 98 96
384
395
406
416
427
439
450
462
474
106 104 102 100 98
108 106 104 102 100
110 108 106 104 102
112 110 108 106 104
114 112 110 108 106
116 114 112 110 108
118 116 114 112 110
120 118 116 114 112
122 120 118 116 114
78
80
82
84
86
88
90
92
94
96
98
100
102
104
106
108
110
112
114
116
118
120
122
124
CAP
CB
CAPACITOR (DUAL RUN)
CIRCUT BOARD
*CH
*CHS
COMP
CONT
*HPS
*LPS
OAT
OCT
ODFR
ODF
*SC
*SR
*ST
CRANKCASE HEATER
CRANKCASE HEATER SWITCH
COMPRESSOR
CONTACTOR
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
THERMISTOR (OUTDOOR AIR)
THERMISTOR COIL
OUTDOOR FAN RELAY
OUTDOOR FAN
START CAPACITOR
START RELAY
START THERMISTOR
FLASH
CODE
FAULT DEFINITION
FAULT DEFINITION
On, No Flash
1, Pause
16
31
32
45
46
53
Standby (3 or 4 Wire Only)
Normal Operation
System Communications Failure
High Pressure Switch
Low Pressure Switch
Control Fault
Brown out (24V)
Outside Temp Sensor
55
56
72
73
74
82
83
84
Coil Temp Sensor
Thermistor Range Error
Thermal Cutout
Contactor Shorted
No 240V at Compressor
Thermal lockout
Low pressure lockout
High pressure lockout
FLASH
CODE
337786-101 REV. A
Fig. 1 – Wiring Diagram — Model sizes 1--1/2 -- 5 tons, 208/230--1
Comments to this Manuals