Alarm
NO.
Steps Alarm/Cause Corrective Action
59 DATALOGGER (DataLink data recorder) NOT RECORDING
TRIGGER–ON: No data is being recorded by the DataLink data recorder.
UNIT CONTROL: Engine and Standby Operation: alarm only.
RESET CONDITION: Alarm may be manually reset via keypad.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (See Note 1 page 72.) Operate the unit through the appropriate modes to see if any active alarm
occurs. Continue with the steps below as necessary.
1 Clear Alarm
a. Clear Active Alarm(s). Alarms Clear.
b. Check for Active Alarm
re-occurrence.
If Inactive, download all data & retain.
If Active, go to next step.
2 Microprocessor Defective
a. Download previous data using
Download PC Card, or
ReeferManager Program.
Data retrieval OK.
b. Replace microprocessor & set
Configurations, Functional
Parameters, Enter hours from
removed microprocessor, set
Maintenance Hour Meters, and
DataLink data recorder Setup.
New microprocessor in place.
NOTE: Specific configurations may be found on the TransCentral Website (Authorized Carrier Transicold
Dealers only.)