51
Table 11 – Unit Wire Sizing Data with Factory--Installed HACR Breaker
UNIT
NOM.
V --- P h --- H z
IFM TYPE
NO C.O. or UNPWR C.O. w/ PWRD C.O.
NO P.E. w/ P.E. (pwrd fr/ unit) NO P.E. w/ P.E. (pwrd fr/ unit)
MCA
HACR
BRKR
DISC. SIZE
MCA
HACR
BRKR
DISC. SIZE
MCA
HACR
BRKR
DISC. SIZE
MCA
HACR
BRKR
DISC. SIZE
FLA LRA FLA LRA FLA LRA FLA LRA
48HC*A/B/F04
208/230---1---60
}
D D --- S T D 30 45 29 88 32 45 31 90 34 50 34 93 36 50 36 95
STD 27 40 26 93 29 45 28 95 32 45 31 98 34 45 34 100
MED 27 40 26 93 29 45 28 95 32 45 31 98 34 45 34 100
208/230---3---60
D D --- S T D 22 30 22 82 24 30 24 84 27 30 27 87 29 35 29 89
STD 19 25 19 87 21 30 21 89 24 30 24 92 26 30 26 94
MED 19 25 19 87 21 30 21 89 24 30 24 92 26 30 26 94
HIGH 20 25 19 105 22 30 21 107 24 30 25 110 26 30 27 112
4 6 0 --- 3 --- 6 0
D D --- S T D 12 15 12 43 13 15 13 44 14 20 14 45 15 20 16 46
STD 10 15 10 45 11 15 11 46 13 15 12 47 14 15 13 48
MED 10 15 10 45 11 15 11 46 13 15 12 47 14 15 13 48
HIGH 11 15 10 54 12 15 11 55 13 15 13 56 14 20 14 57
5 7 5 --- 3 --- 6 0
D D --- S T D 10 15 10 42 12 15 12 44 11 15 12 44 13 15 14 46
STD 8 15 7 43 10 15 9 45 9 15 9 45 11 15 11 47
MED 8 15 7 43 10 15 9 45 9 15 9 45 11 15 11 47
HIGH 8 15 7 49 10 15 9 51 9 15 9 51 11 15 11 53
48HC*A/B/F05
208/230---1---60
}
D D --- S T D 37 50 35 127 38 50 37 129 41 60 41 132 43 60 43 134
STD 34 50 32 132 36 50 35 134 39 60 38 137 41 60 40 139
MED 34 50 32 132 36 50 35 134 39 60 38 137 41 60 40 139
208/230---3---60
D D --- S T D 26 30 26 93 28 40 28 95 31 40 31 98 33 45 34 100
STD 24 30 23 98 26 30 25 100 29 40 29 103 31 40 31 105
MED 24 30 23 105 26 30 26 107 29 40 29 110 31 40 31 112
HIGH 26 30 26 142 28 40 28 144 31 40 32 147 33 45 34 149
4 6 0 --- 3 --- 6 0
D D --- S T D 13 15 13 47 14 20 14 48 15 20 15 49 16 20 16 50
STD 11 15 11 49 12 15 12 50 13 15 13 51 14 20 14 52
MED 12 15 11 52 13 15 12 53 14 20 14 54 15 20 15 55
HIGH 13 15 12 71 14 15 13 72 15 20 15 73 16 20 16 74
5 7 5 --- 3 --- 6 0
D D --- S T D 11 15 11 39 13 15 13 41 13 15 13 41 15 20 15 43
STD 9 15 9 40 11 15 11 42 11 15 11 42 13 15 13 44
MED 9 15 8 42 11 15 11 44 11 15 10 44 13 15 13 46
HIGH 10 15 10 57 12 15 12 59 12 15 12 59 14 15 14 61
See “Legend and Notes for Tables 10 and 11” on page 53.
}
Single phase models are not availa ble with factory---installed powered convenience outlet.
48HC