Carrier EACB1614 Instruction Manual Page 8

  • Download
  • Add to my manuals
  • Print
  • Page
    / 14
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 7
8
Remove
Soak
Rinse
Drip Dry
Replace
Note Air Flow
Direction Arrow
C02035
Fig. 11 -- Typical Call and Prefilter Cleaning
MAINTENANCE OF CELLS
Washing Cells and Prefilters
Regular washing is necessary to ensure proper performance (see
Fig. 11). A thorough wash ing once every two months will be
adequate for most installations. More frequent washing (once a
month) may be necessary on some installations (new homes for
example) where there is new carpeting, plaster dust, or excessive
cigarette smoke.
To remove cells and prefilter
1. Push air cleaner switch to the OFF position. Wait 15
seconds. Open door access panel.
2. Carefully remove cells and prefilter(s) and set aside in a safe
place.
3. Do not drop the ionizing--collector cell. This could cause
damage to the cell plates or ionizing wires and cause
excessive arcing and noise.
To wash cells and prefilter(s)
To wash cells and prefilter(s) We suggest that you follow the
instructions below to properly and thoroughly clean your collector
cells.
1. Place enough hot water in a utility tub to cover the first cell.
Dissolve 2 to 4 oz. of granulated automatic dishwasher
detergent (not laundry detergent) in the water.
2. Allow the cell to soak for 30 minutes. Agitate it up and
down in the solution until it appears clean and remove.
3. Repeat with second cell.
4. Agitate the prefilters up and down in the solution until they
appear clean.
5. With a hose, rinse the cells and prefilters. The hose should
be held about 10” (254 mm) from the cell plates and at a
slight angle for better cleaning results. Be careful not to
spray the ionizing wires directly with the hose. The water
pressure can cause the wire to snap and break. The cell
frame should be thoroughly rinsed along the edges to
dislodge any trapped lint or dirt. Carefully wipe a damp
cloth or sandpaper (not emery cloth) along the ionizing
wires.
6. Stand cells and prefilters up to drain. Let dry two hours.
You may experience a slight discoloration of the aluminum
collector cells after washing. This is a normal chemical
reaction and will not harm your unit or affect its
performance.
To replace cells in air cleaner
1. Replace prefilter and cells in cabinet. Check that arrow on
cells points in same direction as air flows through the duct
(If you have to force it past the positioning screw on
bottom, it is probably in the wrong position).
2. Replace access door (engage tabs on lower edge of door
into slots in cabinet). Carefully close door.
3. Turn air cleaner switch to ON.
TROUBLESHOOTING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
The following procedures could expose hazardous live
components. Only a trained, experienced service person
should install this electronic air cleaner. When the circuit has
been de--energized, always discharge any residual current in
the secondary with an insulated handle screwdriver. Always
ground power supply and ionizing--collecting cell when bench
testing. Before performing installation, service or maintenance
operations on unit, turn off all power to unit. TAG
DISCONNECT SWITCH WITH LOCKOUT TAG.
!
WARNING
Recommended Service Tools
1. Screwdriver, 8” common with insulated handle (plastic)
2. Screwdrivers Phillips #1 and #2 with plastic insulated
handles
3. Needle nose pliers
4. Multimeter
5. High voltage probe
Indication of Electrical Trouble
The air clean er is equipped with a Red CELL ENERGIZED light
for indicating proper unit operation. When the unit is in normal
operation (with the HVAC system fan running, access door in place
and rocker switch in the ON position) and the Red CELL
ENERGIZED light is not lit, the problem is a shorted secondary.
Although failure of the indicating light itself should not be
overlooked, this condition is unusual and rather remote.
Primary Circuit with Blower Operating
If there is supply line voltage at the connections and no input
voltage to the power supply, the outage can be located by checking
operation of the safety switch and the interconnecting wiring with a
multimeter . Refer to Circuit Diagram, to check operation of the
switches. Following these steps to test for proper operation of the
circuit board and power supply assembly:
1. Ensure that the circuit breaker controlling the furnace
blower is in the ON position and the main fuse is not open.
2. The power supply board has a built-- in internal fuse to
protect the 24V transformer . It can be checked visually by
inspecting the fuse. If the fine wire inside the fuse is broken,
this indicates a problem in the 24V circuit of the power
supply board. Do NOT replace this fuse. The entire power
supply board must be replaced. The purpose of the fuse is
not to protect the power supply board, but to function as a
troubleshooting feature of the product and to protect the
transformer from damage.
EACB
Page view 7
1 2 3 4 5 6 7 8 9 10 11 12 13 14

Comments to this Manuals

No comments