Carrier 50HCQ04---12 User Manual

Browse online or download User Manual for Conditioners Carrier 50HCQ04---12. Carrier 50HCQ04---12 User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 44
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
48/50TC04---28, 50TCQ04---12
48/50HC04---14, 50HCQ04---12
F acto r y Ins talled O ptio n
R T U --- O P E N
Cont ro ls , St art---Up, Operat io n
and Tro uble s hoot ing I ns t r uct io ns
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 2.........................
GENERAL 2.........................................
SENSOR/ACCESSORY INSTALLATION 2................
Sensors and Accessories 4.............................
User Interfaces 4.....................................
Install Analog Sensors 4...............................
Supply Air Sensor (SAT) 4...........................
Outdoor Air Sensor (OAT) 4..........................
Space Temperature Sensor (SPT) 4.....................
CO
2
Sensor(s) (IAQ and OAQ) 6......................
Relative Humidity Sensors 8..........................
Installing Discrete Inputs 8.............................
Compressor Safety 8................................
Humidistat 8......................................
Single Enthalpy (Outdoor Enthalpy) 8..................
Differential Enthalpy 8..............................
Fire Shutdown 9...................................
Filter Status 9......................................
Fan Status 9.......................................
Remote Occupancy 9................................
Communication Wiring--Protocols 10.....................
General 10........................................
I--Vu OPEN 10....................................
BACnet MS/TP 10.................................
Modbus 11.......................................
Johnson N2 11.....................................
LonWorks 11......................................
Local Access 12....................................
START--UP 13........................................
Additional Installation/Inspection 13.....................
Service Test 13......................................
Fan Test 13.......................................
Compressor 1 and Compressor 2 Test 13.................
Heat 1 and Heat 2 Test 13............................
Reversing Valve Test 13.............................
Dehumidification Test 14.............................
Power Exhaust Test 14..............................
Economizer Test 14.................................
Analog Output 2 Test 14.............................
Configuration 14....................................
Setpoint 14.......................................
Unit 14..........................................
Inputs 15.........................................
Service 16........................................
Clockset 16.......................................
USERPW 17......................................
OPERATION 17......................................
Occupancy 17.......................................
Indoor (Supply) Fan 17...............................
Cooling 18.........................................
Economizer 18......................................
Power Exhaust 18....................................
Heating 18.........................................
Indoor Air Quality 19.................................
Dehumidification 19..................................
Demand Limit 19....................................
Unoccupied Free Cooling 19...........................
Optimal Start 20.....................................
Fire Shutdown 20
....................................
Compressor Safety 20.................................
Fan Status 20.......................................
Filter Status 20......................................
Door Switch 20......................................
Linkage 20.........................................
TROUBLESHOOTING 21..............................
General 21.........................................
Thermistor Troubleshooting 21.........................
Software Version 21..................................
Communication LED’s 22.............................
Alarms 24..........................................
Third Party Networking 26.............................
APPENDIX A -- USER INTERFACE MENUS 27............
APPENDIX B -- THIRD PARTY POINTS LIST 36...........
RTU--OPEN START--UP SHEET 41......................
Copyright 2010 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 Printed i n U.S.A. Edition Date: 08/10
Manufacturer reserves the r ight to change, at any time, specifications and designs without notice and without obligations.
Catalog No:48---50HCTQ---01T
Replaces: NEW
Page view 0
1 2 3 4 5 6 ... 43 44

Summary of Contents

Page 1 - TABLE OF CONTENTS

48/50TC04---28, 50TCQ04---1248/50HC04---14, 50HCQ04---12F acto r y Ins talled O ptio nR T U --- O P E NCont ro ls , St art---Up, Operat io nand Tro ub

Page 2

10C10821Fig. 10 -- Enthalpy Switch and Sensor WiringCommunication Wiring--ProtocolsGeneralProtocols are the communication languages spoken bycontrol d

Page 3

11SW3 Protocol SelectionPROTOCOL DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1BACnet MS/TP(Master)Unused OFF OFF OFF ON OFF Select Baud Select BaudModbus(Slave)Unus

Page 4 - Install Analog Sensors

12C10817Fig. 14 -- LON--OC and LON Network WiringLocal AccessBACview6HandheldThe BACview6is a keypad/display interface used toconnect to the RTU--OPEN

Page 5

13START--UPIMPORTANT: Follow the base unit’s start-up sequencedocumented in its specific instructions. Use the baseunit’s start-up check list when per

Page 6 - Sensor(s) (IAQ and OAQ)

14Dehumidification TestFor units with the factory Reheat option, thedehumidification relay is used to change the output statusto operate the circuits

Page 7 - Field Wiring

15Vent Dmpr Pos / DCV Min Pos – Minimum damperposition for ventilation during the occupied periodRange = 95-150_F Default = 120_FDCV Max Vent Damper P

Page 8 - Installing Discrete Inputs

16Input 5 -- This input is a discrete input and can beconfigured to be one of six different functions: NoFunction, Fire Shutdown, Fan Status, Filter S

Page 9 - Remote Occupancy

17USERPWThis submenu screen allows you to change the userpassword to a four number password of choice. The Userpassword change screen is only accessib

Page 10 - BACnet MS/TP

18CoolingThe compressor outputs are controlled by the CoolingControl PID Loop and Cooling Stages Capacity algorithm.They will be used to calculate the

Page 11 - LonWorks

19If all of the above conditions are met, the controller uses aPID logic loop to energize or de--energize heat outputs tosatisfy the heat demand. If t

Page 12 - Local Access

2SAFETY CONSIDERATIONSInstallation and servicing of air-conditioning equipmentcan be hazardous due to system pressure and electricalcomponents. Only t

Page 13 - START--UP

20Optimal StartThe RTU--OPEN may utilize Optimal Start, which adjuststhe effective setpoints to achieve the occupied setpointsby the time scheduled oc

Page 14 - Configuration

21TROUBLESHOOTINGGeneralThe RTU--OPEN controller acts as an intelligentimbedded thermostat to the rooftop unit, but can bemonitored and controlled fro

Page 15

22C10825Fig. 16 -- Example ModstatCommunication LED’sThe LED’s indicate if the controller is speaking to thedevices on the network. The LED’s should r

Page 16 - Clockset

23Table 4 – RTU--OPEN AlarmsPOINT NAMEBACnet ObjectNAMEACTION TAKEN BYCONTROLRESET METHOD PROBABLE CAUSESafety Chain safety_alarm Immediate Shutdown A

Page 17 - OPERATION

24AlarmsAlarms are provided to indicate a possible problem withthe controller or unit. Alarms can be checked through anetwork and/or the local access

Page 18 - Power Exhaust

25The following values are related to the Space Temperaturealarm:Alarming Temperature – This variable displays thevalue of the space temperature that

Page 19 - Unoccupied Free Cooling

26Airside Linkage AlarmThis alarm indicates that RTU-OPEN was connected to azoned system called Linkaget and it lostcommunications with its linkage ma

Page 20 - Linkage Air Source Modes

27APPENDIX A -- USER INTERFACE MENUSField Assistant NavigationPropertiesEquipmentStatusConfigurationUnit ConfigurationSetpointsAlarm ConfigurationServ

Page 21 - TROUBLESHOOTING

28APPENDIX A -- USER INTERFACE MENUS (CON’T)Standby BACview Screen and Login ScreenBACview MENU POINT NAME BACnet OBJECT VALUESTANDBY R T U --- O P E

Page 22 - Communication LED’s

29APPENDIX A -- USER INTERFACE MENUS (CON’T)Status MenusBACview MENU POINT NAME BACnet OBJECT RANGEFIELD ASSISTANTMENUHOME Select function below Prope

Page 23 - Table 4 – RTU--OPEN Alarms

3C10818Fig. 1 -- RTU--OPEN Control Module

Page 24

30APPENDIX A -- USER INTERFACE MENUS (CON’T)Configuration MenusBACview MENU POINT NAMEBACnetOBJECTRANGE DEFAULT FIELD ASSISTANT MENUHOME Select functi

Page 25

31APPENDIX A -- USER INTERFACE MENUS (CON’T)Configuration Menus (con’t)BACview MENU POINT NAMEBACnetOBJECTRANGE DEFAULT FIELD ASSISTANT MENUHOME Selec

Page 26 - Third Party Networking

32APPENDIX A -- USER INTERFACE MENUS (CON’T)Configuration Menus (con’t)BACview MENU POINT NAMEBACnetOBJECTRANGE DEFAULT FIELD ASSISTANT MENUHOME Selec

Page 27 - Equipment

33APPENDIX A -- USER INTERFACE MENUS (CON’T)Configuration Menus (con’t)BACview MENU POINT NAMEBACnetOBJECTRANGE DEFAULT FIELD ASSISTANT MENUHOME Selec

Page 28 - System Settings Menu

34APPENDIX A -- USER INTERFACE MENUS (CON’T)Maintenance MenuBACview MENU POINT NAME BACnet OBJECT RANGEFIELD ASSISTANTMENUHOME Select function below P

Page 29 - Status Menus

35APPENDIX A -- USER INTERFACE MENUS (CON’T)Alarm MenusBACview MENU POINT NAME BACnet OBJECT RANGEFIELD ASSISTANTMENUHOME Select function below Proper

Page 30 - Configuration Menus

36APPENDIX B -- THIRD PARTY POINTS LIST(IN ALPHABETICAL ORDER)BACnet Modbus N2 LON WorksPoint NameRead/WriteBACnet PointNameOBJECTIDRegisterTyp eRegis

Page 31 - Configuration Menus (con’t)

37APPENDIX B -- THIRD PARTY POINTS LIST (CON’T)(IN ALPHABETICAL ORDER)BACnet Modbus N2 LON WorksPoint NameRead/WriteBACnet PointNameOBJECTIDRegisterTy

Page 32

38APPENDIX B -- THIRD PARTY POINTS LIST (CON’T)(IN ALPHABETICAL ORDER)BACnet Modbus N2 LON WorksPoint NameRead/WriteBACnet PointNameOBJECTIDRegisterTy

Page 33

39APPENDIX B -- THIRD PARTY POINTS LIST (CON’T)(IN ALPHABETICAL ORDER)BACnet Modbus N2 LON WorksPoint NameRead/WriteBACnet PointNameOBJECTIDRegisterTy

Page 34 - Maintenance Menu

4Table 1 – RTU--OPEN Inputs and OutputsPOINT NAMEBACnet OBJECTNAMETYPE OF I/OCONNECTION PINNUMBER(S)DEDICATED INPUTSSpace Temp / Zone Temp zone_temp A

Page 35 - Alarm Menus

40APPENDIX B -- THIRD PARTY POINTS LIST (CON’T)(IN ALPHABETICAL ORDER)BACnet Modbus N2 LON WorksPoint NameRead/WriteBACnet PointNameOBJECTIDRegisterTy

Page 36

41RTU--OPEN START--UP SHEETRTU Model Number: Date:RTU Serial Number:Performed by:RTU--- OPEN Software Version: Company:Protocol and Boad Rate: Network

Page 37

42CONFIGURATION POINTS (CON’T)BACviewMENUPOINT NAMEBACnetOBJECTRANGE DEFAULT ENTRYHOME Select function belowCONFIG CONFIGURATIONUNITUNIT CONFIGURATION

Page 38

43CONFIGURATION POINTS (CON’T)BACviewMENUPOINT NAMEBACnetOBJECTRANGE DEFAULT ENTRYHOME Select function belowCONFIG CONFIGURATIONINPUTINPUT CONFIGURATI

Page 39

44CONFIGURATION POINTS (CON’T)BACviewMENUPOINT NAMEBACnetOBJECTRANGE DEFAULT ENTRYHOME Select function belowCONFIG CONFIGURATIONSERVICESERVICE CON FIG

Page 40

5C10819Fig. 2 -- Typical Factory Option Wiring

Page 41 - CONFIGURATION POINTS

6Resistive Non--Communicating Sensor WiringFor sensor with setpoint adjustment up to 500 ft (152m),use three-conductor shielded cable 20 gauge wire to

Page 42 - CONFIGURATION POINTS (CON’T)

7J2012REDBLKREDREDBLKBLKBLKREDBLKREDSENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4J20REDBLKREDBLKSENSOR 2SENSOR 1REDREDBLKSENSOR 3SENSOR 4BLKBLKREDREDREDBLKBLKSE

Page 43

8Relative Humidity Sensors (Space or DuctMounted)The accessory space humidity sensor or duct humiditysensor is used to measure the relative humidity o

Page 44

9Relative Humidity Sensor(Polarized Male Connector)J4-1 or J4-4 + 24 VDC Supply VoltageJ4-2 or J4-5 (-) 4 to 20 mA Current Loop Outputto RTU-OPEN4-20

Comments to this Manuals

No comments