Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 02-38HD0001-SI Printed in U.S.A. Form 38HD-4SI Pg 1 1-06 Replaces: 38HDC-3SI
Book 1 4
Tab 3 e 2 f
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ...................... 1
INSTALLATION ................................ 1-10
Step 1 — Complete Pre-Installation Checks ......1
UNPACK UNIT
INSPECT SHIPMENT
CONSIDER SYSTEM REQUIREMENTS
MATCHING THE CONDENSING UNIT TO AN
INDOOR UNIT
Step 2 — Rig and Mount Unit.....................3
MOUNTING ON GROUND
MOUNTING ON ROOF
RIGGING
Step 3 — Complete Refrigerant Piping
Connections ................................... 3
CHECK ACCURATER CONTROL
FILTER DRIER
MAKE PIPING SWEAT CONNECTORS
PROVIDE SAFETY RELIEF
Step 4 — Make Electrical Connections ........... 6
CONTROL CIRCUIT WIRING
POWER WIRING
CONNECTIONS TO DUCT-FREE FAN COIL UNITS
START-UP ....................................... 11
SERVICE ..................................... 11-14
MAINTENANCE .................................14
TROUBLESHOOTING..........................14,15
SAFETY CONSIDERATIONS
Installing and servicing air conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install or
service air conditioning equipment.
Untrained personnel can perform basic maintenance, such
as cleaning and replacing filters. All other operations should be
performed by trained service personnel. When working on air
conditioning equipment, observe safety precautions in litera-
ture, tags, and labels attached to unit.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations. Have fire
extinguisher available. Read these instructions thoroughly.
Consult local building codes and the National Electrical Code
(NEC) for special installation requirements.
INSTALLATION
Step 1 Complete Pre-Installation Checks
UNPACK UNIT (See Fig. 1) — Move the unit to final loca-
tion. Remove unit from carton, being careful not to damage
service valves and grilles.
INSPECT SHIPMENT — File a claim with the shipping
company if shipment is damaged or incomplete. Check unit
nameplate to ensure unit matches job requirements.
CONSIDER SYSTEM REQUIREMENTS — Consult local
building codes and NEC for special installation requirements.
Allow sufficient space for airflow clearance, wiring, refrig-
erant piping, and servicing unit. See Fig. 2.
Locate unit so that condenser airflow is unrestricted on both
sides. Refer to Fig. 2.
Unit may be mounted on a level pad directly on base legs or
mounted on raised pads at support points. See Fig. 2 for center
of gravity.
MATCHING THE CONDENSING UNIT TO AN
INDOOR UNIT — The 38HDF,HDR units can be matched to
a corresponding indoor unit. The 38HDF018-036 units can be
matched with an in-ceiling cassette or high wall indoor unit.
The 38HDR unit can be matched with under-ceiling and resi-
dential fan coils. Refer to separate indoor unit literature for
more information.
Before installing or servicing system, always turn off main
power to system. There may be more than one disconnect
switch. Turn off accessory heater power if applicable. Elec-
trical shock can cause serious personal injury.
Puron® (R-410A) refrigerant systems operate at higher
pressures than standard R-22 systems. Do not use R-22 ser-
vice equipment or components on Puron refrigerant equip-
ment. If service equipment is not rated for Puron refrigerant,
equipment damage or personal injury may result.
38HDF018-036
Duct Free Condensing Units
38HDR018-060
Ducted Condensing Units
Fig. 1 — 38HDF,HDR Unit
Page view 0
1 2 3 4 5 6 ... 15 16

Summary of Contents

Page 1 - Service Instructions

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Page 2

10LEGENDNOTES:1. Compressor and fan motors are thermally protected.2. Wire in accordance with National Electrical Code (NEC) and local codes. Replacea

Page 3 - Step 2 — Rig and Mount Unit

11START-UPPreliminary Checks1. Check that all internal wiring connections are tight andthat all barriers, covers, and panels are in place.2. Field ele

Page 4

12To troubleshoot:1. Apply voltmeter across crankcase heater leads to see ifheater voltage is on. Do not touch heater. Carefully feelarea around crank

Page 5

13Table 4 — Pressure vs. Temperature Chart — Puron® Refrigerant (R-410A)Subcooling Method — For 38HDR units only, the sub-cooling method is used to ch

Page 6 - 38HDR UNITS

14Table 5 — Subcooling Charging TableCompressor Lockout Switch — The 38HDR unitsare provided with a compressor lockout protective device. Ifthe compre

Page 7

15Fig. 9 — Troubleshooting the Cooling Cycle

Page 8

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Page 9 - 38HDF OPERATION SEQUENCE

2(FIELD PROVIDED AND INSTALLED)Fig. 2 — 38HDF,HDR Unit DimensionsNOTE: Dimensions shown in feet-inches. Dimensions in ( ) are millimeters.UNIT MODELSC

Page 10 - 38HDR OPERATION SEQUENCE

3Step 2 — Rig and Mount UnitMOUNTING ON GROUND — Mount unit on a solid, levelconcrete pad. Position unit so water or ice from roof does notfall direct

Page 11

4Only use factory specified liquid-line filter driers with ratedworking pressures less than 600 psig.NOTE: Do not install a suction-line filter drier

Page 12 - Refrigerant Charging

5Table 1B — 38HDR018-060 Physical DataLEGEND *Unit shipped with full factory charge. See ARI (Air Conditioningand Refrigeration Institute) capacity ta

Page 13

6Step 4 — Make Electrical ConnectionsCONTROL CIRCUIT WIRING — Control voltage is 24 v(40 va minimum). See Fig. 5 and unit label diagram for field-supp

Page 14 - TROUBLESHOOTING

7Table 2 — 38HDF Electrical DataLEGEND*Permissible limits of the voltage range at which unit will operatesatisfactorily.NOTES:1. Control circuit is 24

Page 15

8Table 3 — 38HDR Electrical DataLEGEND*Permissible limits of the voltage range at which unit will operatesatisfactorily.NOTES:1. Control circuit is 24

Page 16 - Tab 3 e 2 f

9LEGENDNOTES:1. Compressor and fan motors are thermally protected.2. Wire in accordance with National Electrical Code (NEC) and local codes. Replacean