ProductData 38YSA (60 Hz)Heat Pump Sizes 024 thru 048 Copyright 1997 Carrier Corporation Form 38YSA-2PD The 38YSA Outdoor Sections of high efficienc
10Detailed cooling capacities* See notes on pg. 11.EVAPAIRCONDENSER ENTERING AIR TEMPERATURES °F75 85 95 105 115 125CFM EWBCapacityMBtuh†TotalSysKw**C
11Detailed cooling capacities* continued* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/
12Heat pump heating performance See notes on pg. 13.INDOORAIROUTDOOR COIL ENTERING AIR TEMPERATURES °F–3 7 172737475767EDB CFMCapacity(MBtuh)TotalPwrC
13Heat pump heating performance continued* The Btuh heating capacity values shown are net ‘‘integrated’’ values from which the defrost effect has been
14Matched systemA97114AIR CLEANERHEAT PUMPCOMFORT VENTILATORHUMIDIFIERCOMFORT ZONE IICONTROL CENTERFAN COIL
15System Design1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-i
Carrier Corporation • Indianapolis, IN 46231 5-97Manufacturer reserves the right to discontinue, or change at any time, specifications or designs with
2 scroll compressor which is significantly more efficient than conventional compressors, especially in the heating mode at low-ambient temperatures. It
3 CERTIFICATION APPLIES ONLY WHEN THE COMPLETE SYSTEM IS LISTED WITH ARI. CERTIFICATION OF MANUFACTURING SITE Physical data * Tube sizes are for r
4 Accessories * Isolation relay required. † Fan motor with ball bearings required.‡ Consult low-ambient Installation Instructions for application. **
5 Accessory description and usage (Listed alphabetically) 1. Ball Bearing Fan Motor A fan motor with ball bearings which permits speed reduction wh
6Electrical data* Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit
7Dimensions2 1/2"1 9/16"AIR DISCHARGE4 3/16"3/8 IN. DIA.LIQUID LINECONN1 3/4"2 15/16"FIELD POWER SUPPLY CONN7/8 IN. DIA HO
838YSA BALANCE POINT WORKSHEETBUILDING HEAT LOSS, 1000 BTU/HRUNIT INTEGRATED HEATING CAPACITY, 1000 BTU/HRPrinted in U.S.A.OUTDOOR TEMPERATURE, °F-
9Combination ratings* Outdoor section/indoor section combination tested in accordance with DOE test procedures for heat pumps. Ratings for other combi