Installation Instructions
Part No. 30RA-900---058, 30RA-900---059
SAFETY CONSIDERATIONS
Installation of this accessory can be hazardous due to sys-
tem pressures, electrical components, and equipment location
(such as a roof or elevated structure).
Only trained, qualified installers and service mechanics
should install and service this equipment.
When installing this accessory, observe precautions in the
literature, labels attached to the equipment, and other safety
precautions that apply.
Follow all safety codes.
Wear safety glasses and work gloves.
Use care when handling and installing this accessory.
GENERAL
The ground-fault circuit interrupter convenience outlet
(GFI-CO) accessory provides two auxiliary 115 v, 60 Hz out-
lets for portable computers, lights, small hand tools and other
devices. The current output is limited to 4 amps. See Table 1
for specific package applications.
Table 1 — Accessory Package Usage
Check each item for shipping damage. If any damage is
found, file a claim with the shipping agent immediately. If any
item is missing or if any part does not assemble properly, notify
your Carrier representative. Table 2 lists the contents of the
accessory kits.
Table 2 — Package Contents
INSTALLATION
Sizes 30RAP010-030, 38APS,APD025-030
1. Open and tag all electrical disconnects.
2. Open the unit control box door.
3. Locate the bag of screws and fuses (30RA-900---058
only) supplied with the accessory.
4. Remove transformer box cover. Save screws.
5. Verify correct primary connections are made.
NOTE: The 30RA-900---059 kits are shipped with cor-
rect wiring for 575 v. The 30RA-900---058 kits are
shipped with correct wiring for 460 v. Operation at 208/
230 v WILL
require a wiring change and change of pri-
mary fuses to FNQ-R-3
1
/
2
. See Table 3. Rejection type
fuses are installed one way only. Make sure they are se-
cure in the fuse holder clips.
Table 3 — Primary Connections
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all discon-
nect locations to alert others not to restore power until work
is completed.
UNIT PACKAGE REQUIRED
30RAP010-150, 38APS025-065,
38APD025-130
(208/230, 230, 460 V)
30RA-900---058
30RAP010-150, 38APS025-065,
38APD025-130 (575 V)
30RA-900---059
ACCESSORY
PART NO.
DESCRIPTION QTY
30RA-900---058
Transformer/Convenience Outlet Assem-
bly Assembly, 38APFSCLG--600
1
Screws,
1
/
4
-in.
1
/
2
-in. long 4
230v: Primary fuse FNQ-R-3
1
/
2
(FU5 and
FU6)
2
460v: Primary fuse FNQ-R-2
1
/
2
(FU5 and
FU6)
2
Secondary fuse FNM-6 (FU4) 1
Wire Ties 4
30RA-900---059
Transformer/Convenience Outlet Assem-
bly Assembly, 38APFSCLG--100
1
Screws,
1
/
4
-in.
1
/
2
-in. long 4
Primary fuse FNQ-R-2
1
/
2
(FU5 and FU6) 2
Secondary fuse FNM-6 (FU4) 1
Wire Ties 4
WARNING
Before beginning installation of this equipment, be sure all
power to the unit is disconnected, and that tags are properly
placed to alert others. Electrical shock can cause personal
injury and death.
VOLTAGE PRIMARY CONNECTIONS
575 V H1, H2
460 V H1, H4
230 V H2, H4
208 V H3, H4
30RAP010-150, 38APS025-065, 38APD025-130
Ground-Fault Interrupter
Convenience Outlet Accessory
Page view 0
1 2 3 4 5 6 7 8

Summary of Contents

Page 1 - Installation Instructions

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Page 2 - CONVENIENCE

26. Install the GFI-CO accessory box in the location shownin Fig. 1. Use the included sheet metal screws to fastenbox to the basepan.7. Using the scre

Page 3 - FIOP/ACCESSORY

39. In the control box, attach the black wire labeled 1 to the11 connection on the A1 compressor contactor. Attach theblack wire labeled 2 to the 12 c

Page 4

4Sizes 30RAP035-060, 38APS040,050, 38APD040-0601. Open and tag all electrical disconnects.2. Open the unit right control box door and remove innercove

Page 5

5CONVENIENCEOUTLETFig. 6 — Accessory Convenience Outlet Wire Routing — 30RAP035-060 (Shown),38APS040,050, 38APD040-060 UnitsFig. 7 — Accessory Conveni

Page 6

6Sizes 30RAP070-150, 38APS065,38APD070-1301. Open and tag all electrical disconnects.2. Open the unit middle control box door and remove innercover.3.