40MVQ009 with 38MV Q009
Comfortt Series High W all Duct---Free Split Syste m
Heat Pump with Puronr Refrigerant
Submittal Data
Job Data:_________________________________________________ Location:________________________________________
Buyer:________________________________________ Buyer P.O.#_______________________ Carrier # _________________
Unit Number:__________________________________ Model Number: _____________________________________________
Performance Data Certified By: _________________________________________ Date: _______________________________
the environmentally sound refrigerant
FEATURES
S
13 SEER / 7.7 HSPF
S Wireless remote standard
S Low voltage controls
S 35 VDC indoor fan motor
S User selectable fan speeds (auto, low med., high)
S Indoor unit is powered from the outdoor unit
S Auto restart
S Diagnostics
S Dehumidification mode
S Sleep mode
S Auto swing
S Timer
S Cleanable filters
S Limited Warranty: 1--year on all parts/5--years on
compressor
Indoor Unit -- 40MVQ / Outdoor Unit -- 38MVQ
(Unless otherwise indicated, data applies to both indoor and outdoor models)
SYSTEM SIZE 009...........................................
REFRIGERANT R--410A......................................
PERFORMANCE
Nominal Capacity 9,000.....................................
SEER 13..................................................
HSPF 7.7.................................................
Airflow (Low/Med/High) 340 / 365 / 425.........................
Performance at actual conditions: Attached j Not Attached j
SOUND PRESSURE dBA
Indoor (Low/Med/High) 33 / 36 / 43............................
Outdoor 55................................................
SOUND POWER dBA
Indoor (Low/Med/High) 44 / 47 / 54............................
Outdoor 66................................................
ELECTRICAL
System Voltage 115 V........................................
MCA (outdoor) 12..........................................
MOCP (outdoor) 20.........................................
Fan Motor (Indoor) (FLA) 1.1.................................
Motor Watts 20.............................................
CONTROLS
Control Remote Wireless.....................................
Control Voltage Low Voltage.................................
Interconnecting (indoor to outdoor) Wiring (0--50 ft.) 18 AWG........
Interconnecting (indoor to outdoor) Wiring (50 --65 ft.) 16 AWG.......
REFRIGERANT LINES (Insulate both lines)
Mixed Phase Line (in.) OD 1/4................................
Vapor Line (in.) OD 3/8.....................................
Metering/Control Device Capillary tube in outdoor unit.............
Condensate Pump: Required j Not Required j
Low Ambient Controls: Required j Not Required j
Crankcase Heater: Required j Not Required j
Wind Baffle: Required j Not Required j
Optional:
Compressor extended warranty 6--10 years: Required j Not Required j
All parts & labor 2--5 years: Required j Not Required j
All parts & labor 2--5 years + Compressor 6--10 years: Required j Not Required j