Carrier 48ES---A Instruction Manual Page 23

  • Download
  • Add to my manuals
  • Print
  • Page
    / 42
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 22
Proceedasfollows:
1.Removecapsfromlow-andhigh-pressureservicefittings.
2.Usinghoseswithvalvecoredepressors,attachlow-and
high-pressuregaugehosesto low- andhigh-pressure
servicefittings,respectively.
3.StartunitinCoolingModeandletunitrununtilsystem
pressuresstabilize.
4.Measureandrecordthefollowing:
a.Outdoorambient-airtemperature(°F[°C]db).
b.Liquidlinetemperature(°F[°C]).
c.Discharge(high-side)pressure(psig).
d.Suction(low-side)pressure(psig)(forreferenceonly).
5.Using"CoolingChargingCharts,"compareoutdoor-air
temperature(°F[°C]db)withthedischargelinepressure
(psig)to determinedesiredsystemoperatingliquidline
temperature(SeeTable7).
6.Compareactualliquidlinetemperaturewithdesiredliquid
linetemperature.Usingatoleranceof- 2°F(-I.I°C),add
refrigerantif actualtemperatureismorethan2°F(I.I°C)
higherthanproperliquidlinetemperature,or remove
refrigerantif actualtemperatureismorethan2°F(I.I°C)
lowerthanrequiredliquidlinetemperature.
NOTE:If theproblemcausingtheinaccuratereadingsis a
refrigerantleak,refertotheCheckforRefrigerantLeakssection.
Indoor Airflow and Airflow Adjustments
[]NIT OPERATION HAZARD
Failure to follow this caution may result in unit damage.
For cooling operation, the recommended airflow is 350 to
450 cfm for each 12,000 Btuh of rated cooling capacity. For
heating operation, the airflow must produce a temperature
rise that falls within the range stamped on the unit rating
plate.
NOTE: Be sure that all supply-and return-air grilles are open,
free from obstructions, and adjusted properly.
ELECTRICALSHOCK HAZARD
Failure to follow this warning could result in personal
iniury or death.
Disconnect electrical power to the unit and install lockout
tag before changing blower speed.
This unit has independent fan speeds for gas heating and cooling.
In addition, this unit has the field-selectable capability to run two
different cooling fan speeds: A normal cooling fan speed (350~400
CFM/Ton) and an enhanced dehumidification fan speed (As low as
320 CFM/Ton) for use with either a dehumidistat or a thermostat
that supports dehumidification.
This unit is factory-set up for use with a single cooling fan speed.
The cooling speed is marked "LOW" on the interface fan board
(IFB)(Fig. 17). The factory-shipped settings are noted in Table 8.
There are 3 additional speed tap wires available for use in either
gas heating or cooling (For color coding on the indoor fan motor
leads, see Table 6). The additional 3 speed tap wires are shipped
loose with vinyl caps and are located in the control box, near the
interface fan board (IFB) (Fig. 17).
Gas Heating Fan Speed Set-up
To change the gas heating speed:
1. Remove the vinyl cap off of the desired speed tap wire
(Refer to Table 6 for color coding). Table 8 shows the
temperature rise associated with each fan speed for a given
static pressure. Make sure that the speed chosen delivers a
temperature rise within the rise range listed on the unit
rating plate.
2. Remove the current speed tap wire from the "GAS HEAT"
terminal on the interface fan board (IFB) (Fig. 17 and place
vinyl cap over the connector on the wire,
3. Connect the desired speed tap wire to the "GAS HEAT"
terminal on the interface fan board (IFB).
Single Cooling Fan Speed Set-up (Dehumidification
feature not used)
To change cooling speed:
1. Remove the vinyl cap off of the desired speed tap wire
(Refer to Table 6 for color coding). Add the wet coil
pressure drop in Table 10 to the system static to determine
the correct cooling airflow speed in Table 8 that will deliver
the nominal cooling airflow as listed in Table 1 for each
size.
2. Remove the current speed tap wire from the "LOW"
terminal on the interface fan board (IFB) (Fig. 17) and place
vinyl cap over the connector on the wire.
3. Connect the desired speed tap wire to the "LOW" terminal
on the interface fan board (IFB).
Two Cooling Fan Speeds Set-up (Dehumidification
feature used)
IMPORTANT: Dehumidification control must open control
circuit on humidity rise above set point.
Use of the dehumidification cooling fan speed requires use of
either a 24 VAC dehumidistat or a thermostat which includes
control of a 24 VAC dehumidistat connection. In either case, the
dehumidification control must open the control circuit on humidity
rise above the dehumidification set point.
1. Remove fan speed tap wire from the "LOW" terminal on
the interface fan board (IFB) (Fig. 17).
2. Determine correct normal cooling fan speed for unit and
application. Add the wet coil pressure drop in Table 10 to
the system static to determine the correct cooling airflow
speed in Table 8 that will deliver the nominal cooling
airflow as listed in Table 1 for each size.
3. Remove the vinyl cap off of the desired speed tap wire
(Refer to Table 6 for color coding) for the normal cooling
fan speed and place desired speed tap wire on "HIGH" on
the interface board.
4. Refer to airflow tables (Table 8) to determine allowable
speeds for the dehumidification cooling fan speed. In Table
8, speeds that are not allowed for dehumidification cooling
are shaded.
5. Remove the vinyl cap off of the desired speed tap wire
(Refer to Table 6 for color coding) for the dehumidification
cooling fan speed and place desired speed tap wire on the
"LOW" connection on the interface board (IFB). Verify
that static pressure is in the acceptable range for the speed
tap to be used for dehumidification cooling.
6. Use any spare vinyl plugs to cap any unused speed tap
wires.
NOTE: For cooling operation, the recommended airflow is 350 to
450 CFM for each 12,000 Btuh of rated cooling capacity.
23
Page view 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 41 42

Comments to this Manuals

No comments