Single-Piece Installation — For single-piece installa-
tion, perform the following procedure.
1. Turn off all power to equipment.
2. If an existing thermostat is being replaced:
a. Remove existing control from wall.
b. Disconnect wires from existing thermostat, one at a
time.
c. As each wire is disconnected, record wire color and
terminal marking.
d. New or additional wires may be needed to accom-
modate added humidity outputs.
e. Discard or recycle old control.
3. Remove cover from equipment control module by pressing
the two tabs on the bottom edge and pulling away.
4. Route wires through large hole in equipment control mod-
ule base. Level base against the wall (for aesthetic purposes
only, the equipment control module does not need to be
leveled for proper operation) and mark wall through two
mounting holes.
5. Drill two
3
/
16
-in. mounting holes in wall where marked.
The equipment control module may be mounted on the
junction box, if desired. Make sure that the hole pattern on
base matches junction box mounting holes.
6. During thermostat installation provide sufficient excess
wiring behind the mounting plate. Coil the wiring creating
a service loop and place in mounting box or behind the
wall to remove strain against the terminal strip. See Fig. 4
on page 3.
7. Secure base to wall with two screws and anchors provided.
Additional mounting holes are available for more secure
mounting if needed. Make sure that all wires extend
through hole in mounting base.
8. Adjust length and routing of each wire to reach proper con-
nector block and terminal on mounting base with extra
1
/
4
-in. wire.
9. Connect equipment wiring to the terminals on the equip-
ment control module, being careful not to over-tighten the
screws. See Fig. 10.
10. Seal hole in wall to prevent air leaks. Leaks can affect oper-
ation and cause incorrect temperature and/or humidity
measurement.
11. Connect red wire of the pigtail to V+ terminal on the equip-
ment control board. Pigtail is packed loose in the box from
the factory. Pigtail is attached to the back of the display
module via 2-pin, keyed connector. Connect black wire of
the pigtail to Vg terminal on the equipment control board.
Correct polarity must be observed when connecting. If
wires are connected incorrectly, the display module will
not operate.
NOTE: The 2-wire pigtail is not intended to support the weight
of the user interface. Do not hang the display module from the
equipment control module screw terminals.
12. Attach 2-wire pigtail to display module.
RELAYS
OAT
RRS
SRTN
HUM
D1
D2
V+
Vg
Rc
Rh
W1
G
Y2
C
O/W2/B
Y1
CONNECT
TO USER
INTERFACE
DRY
CONTACT
OAT/RRS
RETURN
JW6
TWIST
OFF
SEPARATE
RC/RH BY
BLACK
BREAKING
JW6 ON
CONTROL
MODULE
BOARD.
RED
LEGEND
OAT Outdoor Air Temperature Sensor
RRS Remote Room Temperature Sensor
Fig. 10 — Control Module Connector Block Terminals
a33-9170
Fig. 11 — Cover Installed on Equipment Control
Module