Carrier 59MN7A Instruction Manual Page 41

  • Download
  • Add to my manuals
  • Print
  • Page
    / 90
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 40
41
A furnace shall not be connected to a chimney flue serving a
separate appliance designed to burn solid fuel.
Other gas appliances with their own venting system may also use
the abandoned chimney as a raceway providing it is permitted by
local code, the current edition of the National Fuel Gas Code and
the vent or liner manufacturer’s installation instructions. Care must
be taken to prevent the exhaust gases from one appliance from
contaminating the combustion air of other gas appliances.
Do not take combustion air from inside the chimney when using
ventilated combustion air or single pipe vent option.
These furnaces can be vented as either direct vent furnace or as
ventilated combustion air system. Each type of venting system is
described below. Common venting between furnaces or other
appliances prohibited.
Materials
U.S.A.
Combustion air and vent pipe, fittings, primers, and solvents must
conform to American National Standards Institute (ANSI)
standards and American Society for Testing and Materials (ASTM)
standards. See Table 11 for approved materials for use in the
U.S.A.
Canada
Special Venting Requirements for Installations in Canada
Installation in Canada must conform to the requirements of
CAN/CSA B149 code. Vent systems must be composed of pipe,
fittings, cements, and primers listed to ULC S636.
Venting Systems
A factory accessory KGAVT vent termination kit must be used for
all direct vent terminations. Termination kits are available for 2--in.
or 3--in. pipe. See Table 10 for available options.
Table 10 Vent Termination Kit for Direct Vent (2--pipe)
Systems
DIRECT VENT
(2 --- PIPE)
TERMINATION KIT
TERMINATION
SYSTEM
DIAM. OF COMB US-
TION AIR AND VENT
PIPES --- IN. (mm)
2 --- i n . ( 5 1 m m )
Concentric Vent Kit
Single Penetration of
Wall or Roof
1, 1---1/2, 2, or 2---1/2
(24, 36, 51, 64 mm)
3 --- i n . ( 7 6 m m )
Concentric Vent Kit
Single Penetration of
wall or Roof
2---1/2, 3 or 4
(64, 76, 102 mm)
2 --- i n . ( 5 1 m m )
Termination Bracket
Kit
2 ---Pipe Termination
System
1, 1---1/2 or 2
(25, 36, 51 mm)
3 --- i n . ( 7 6 m m )
Termination Bracket
Kit
2 ---Pipe Termination
System
2---1/2, 3 or 4
(64, 76, 102 mm)
Direct Vent / 2-Pipe System
In a direct-vent (2-pipe) system, all air for combustion is taken
directly from outdoor atmosphere, and all flue products are
discharged to outdoor atmosphere. Combustion-air and vent pipes
must terminate together in the same atmospheric pressure zone,
either through the roof or a sidewall (roof termination preferred). A
factory accessory vent termination kit MUST be used in a direct
vent (2-pipe) system. See Fig. 44 for required clearances.
Ventilated Combustion Air Systems
In a ventilated combustion air option, the vent terminates and
discharges the flue products directly to the outdoors similar to a
direct vent system. See Fig. 45 for required clearances.
All air for combustion is piped directly to the furnace from a space
that is well ventilated with outdoor air (such as an attic or crawl
space) and the space is well isolated from the living space or
garage. Combustion air requirements for this option are the same as
the requirements for providing outside air for combustion for a
single pipe vent system. Refer to the “Air For Combustion and
Ventilation Section.
Provisions for adequate combustion, ventilation, and dilution air
must be provided in accordance with:
U.S.A. Installations: Section 9.3 NFPA 54/ANSI Z223.1-2009,
Air for Combustion and Ventilation and applicable provisions of
the local building codes.
Canadian Installations: Part 8 of CAN/CSA-B149.1-10. Venting
Systems and Air Supply for Appliances and all authorities having
jurisdiction.
Locating the Vent Termination
General
NOTE: Termination Requirements for the Provinces of
Alberta and Saskatchewan are located at the end of this
section.
Combustion--air (direct vent/2--pipe system only) and vent pipe
must terminate outside structure, either through sidewall or roof.
For vent termination clearance, refer to Fig. 44 for Direct
Vent/2--Pipe system and Fig. 45 for Non--direct Vent/1--Pipe
system. For exterior termination arrangements, refer to Fig. 46 for
Direct Vent/2--Pipe system and Fig. 47 for Non-- Direct/1--Pipe
system.
Roof termination is preferred since it is less susceptible to damage
or contamination, and it has less visible vent vapors. Sidewall
terminations require sealing or shielding of building surfaces with a
corrosive resistance material due to corrosive combustion products
of vent system.
NOTE: (Direct Vent/2--Pipe system ONLY) A factory accessory
termination kit MUST be used. See Table 10 for available options.
When determining appropriate location for termination, consider
the following guidelines:
1. Comply with all clearance requirements stated in Fig. 44 or
Fig. 45 per application.
2. Termination or termination kit should be positioned where
vent vapors will not damage plants/shrubs or air condi-
tioning equipment.
3. Termination or termination kit should be positioned so that
it will not be affected by wind eddy, such as inside building
corners, nor by recirculation of flue gases, airborne leaves,
or light snow.
4. Termination or termination kit should be positioned where it
will not be damaged by or subjected to foreign objects such
as stones, balls, etc.
5. Termination or termination kit should be positioned where
vent vapors are not objectionable.
Direct Vent / 2-Pipe System
Direct vent (2--pipe) vent and combustion air pipes must terminate
outside the structure. Follow all clearances as shown Fig. 44.
Allowable vent and combustion air terminations are shown in Fig.
46.
Ventilated Combustion Air
The vent pipe for a Ventilated Combustion Air System must
terminate outdoors. Follow all vent termination clearances shown
in Fig. 45. Allowable vent terminations are shown in Fig. 47. The
combustion air pipe terminates in a well--ventilated attic or crawl
space. Follow the clearances as shown in Fig. 49. When the
furnace is installed in a well ventilated attic or crawlspace, install
the combustion air pipe as shown in Fig. .43
The combustion air pipe cannot terminate in attics or crawl spaces
that use ventilation fans designed to operate in the heating season.
If ventilation fans are present in these areas, the combustion air
pipe must terminate outdoors as a Direct Vent System.
Termination Requirements for the Provinces of Alberta and
Saskatchewan
The Provinces of Alberta and Saskatchewan require a minimum
unobstructed distance of 4 ft. (1.2 M) from the foundation to the
property line of the adjacent lot for vent termination of any
appliance with an input over 35,000 btuh. If there is less than 4 ft.
59MN7A
Page view 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 ... 89 90

Comments to this Manuals

No comments