Table 16 — Index of Lead/Lag Circuits and Compressors
LEGEND
*Circuit has only one compressor.
†Units have only one circuit.
Check Compressor Oil Level — After adjusting the
refrigerant charge, allow each circuit to run fully loaded for
20 minutes. Running oil level should be
1
/
8
to
1
/
3
up on the sight
glass. Stop the compressors at the field power supply discon-
nect and check the crankcase oil level. Add oil only if neces-
sary to bring the oil into view in the sight glass. If oil is added,
run the circuit for an additional 10 minutes, then stop and check
oil level. If the level remains low, check the piping system for
proper design for oil return; also, check the system for leaks.
If the initial check shows too much oil (too high in the sight
glass) remove oil to proper level. See Preliminary Oil Charge
section on page 40 for proper procedure for adding and remov-
ing oil.
When the above checks are complete, repeat the procedure
with the unit operating at minimum load conditions.
UNITS 38AH044-084,124, AND 134 — For this minimum
load check, run the lead compressor of each refrigeration cir-
cuit fully unloaded with the lag compressor not operating.
Unload the compressor(s) by turning the control set point
adjustment nut counterclockwise until the adjustment nut
stops. The unloader is now at 0 psig (0 kPa) set point. If
electrically actuated unloaders are installed, energize the sole-
noid to unload the compressor. Recheck the compressor oil lev-
el as described earlier in Check Compressor Oil Level.
Return unloader to original setting after checks are
complete.
UNITS 38AH094,104 For this minimum load check, the
lead compressor (A1, B1) of each refrigeration circuit is un-
loaded. See Table 16. The lag compressor (A2, B2 38AH104
only) of each refrigeration circuit must not be operating.
Unload the compressor(s) by turning the control set point
adjustment nut counterclockwise until the adjustment nut
stops. The unloader is now at 0 psig (0 kPa) set point. If electri-
cally actuated unloaders are installed, energize the solenoid to
unload the compressor.
Return unloader to original setting after checks are
complete.
Final Checks — Ensure all safety controls are operating,
control panel covers are on, and the service panels are in place.
UNIT
38AH
044-084
STD
044-084
OPT
094 104 124 134
LEAD CIRCUIT AAAA
Module
124A
Module
134A
Compressor, Lead A1 A1 A1 A1 A1 A1
Compressor; Lag *A2A2A2A2A2
LAG CIRCUIT B†BB
Module
124B
Module
134B
Compressor, Lead B1 B1 B1 A1 A1
Compressor; Lag * * B2 A2 A2
OPT Optional Single-Circuit Units
STD Standard Dual-Circuit Units
Fig. 35 — Charging Chart — Unit 38AH044; 50/60 Hz — Dual Circuit