Carrier 38AH044 38AH044-134 Specifications Page 50

  • Download
  • Add to my manuals
  • Print
  • Page
    / 56
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 49
50
Pressure Relief — High-side pressure relief is provided
by a fusible plug in the liquid line at the service valve. For low-
side pressure relief, a fusible plug is inserted in the side of the
accumulator (all units except 38AH044-084 dual-circuit,
constant-volume units). See Fig. 50. The 38AH044-084 dual-
circuit, constant-volume units have a fusible plug in the suction
tubing. A pressure relief valve installed on the compressor re-
lieves at 450 psig (3102 kPa) (see Fig. 3-8).
CONTROL SET POINT — Control set point (cylinder load
point) is adjustable from 0 to 85 psig (0 to 586 kPa). To adjust
the set point, turn the control set point adjustment nut clock-
wise to bottom stop. (See Fig. 51.) In this position, load-up set
point is 85 psig (586 kPa). Turn adjustment counterclockwise
to desired control set point. Every full turn counterclockwise
decreases the load-up set point by 7.5 psig (52 kPa).
PRESSURE DIFFERENTIAL — Pressure differential (dif-
ference between cylinder load and unload points) is adjustable
from 6 to 22 psig (41 to 152 kPa). To adjust, turn pressure
differential adjustment screw counterclockwise to back stop
position. The differential pressure is now adjusted to 6 psig
(41 kPa). Turn the adjustment screw clockwise to adjust the
differential pressure. Every full clockwise turn increases the
differential by 1.5 psig (10 kPa).
Timer Functions — (See Timer Cycle, Fig. 52.) Each
refrigeration circuit is controlled by an independent timer
which allows for the independent operation of each refrigera-
tion circuit.
NOTE: The 38AH044-084 optional single-circuit units have
one timer which controls the lead compressor. Lag compressor
is controlled by CCPS (capacity control pressure switch).
SWITCH A — The timer is energized through contacts A-A1
or A-A2. This establishes the Time Guard function which pre-
vents compressor short-cycling. Start of compressor is delayed
approximately 5
1
/
2
minutes after shutdown.
SWITCH B The compressor is initially energized through
contacts B-B1.
SWITCH D — Contacts D-D1 provide a 2
1
/
2
-minute bypass
of the low-pressure switch at start-up for winter-start control.
On 38AH044-084 optional single-circuit units, contacts D-D2
control start-up of compressor A2.
SWITCH E Contacts E-E1 provide a 2-minute bypass of
the oil pressure switch at start-up. If oil pressure does not build
to the required minimum pressure in 2 minutes, the compressor
shuts down and the control circuit locks out.
On 38AH044-084 dual-circuit and 38AH094,104 units, lag
circuit B start-up is delayed 60 seconds after a call for cooling
is made to the circuit. This prevents compressor(s) in both lead
and lag circuits from starting at the same time.
BYPASS/SPEEDUP PINS — Bypass and speedup shorting
pins are provided for service troubleshooting purposes. Short-
ing the bypass pins will eliminate the 330-second short cycle
time delay. Shorting the speedup pins will decrease all timing
functions by a factor of 8. The bypass and speedup pin jumpers
must be removed after servicing.
Control Circuit Reset — The control circuit locks out
if the unit shuts down because of low oil pressure or excessive
high-side pressure. To reset the control circuit, open and close
the fan circuit breaker (FCB). This resets the timer, and the unit
restarts under Time Guard control. At start-up, if the low-
pressure switch (LPS) does not close after 2
1
/
2
minutes, the unit
shuts down. When the pressure builds enough for the LPS to
cut in, the control circuit is energized automatically and start-
up proceeds under Time Guard control.
38AH044-084 DUAL-CIRCUIT UNITS; 38AH094,104 —
If circuit A operation is insufficient for the cooling require-
ments, the thermostat second stage TC2 closes to bring
circuit B on-line for cooling. This circuit follows the same
sequence of operation as the lead circuit, except a 60-second
time delay relay (TDR) delays compressor start-up for 60 sec-
onds after the call for cooling.
CONDENSER
COIL
FUSIBLE
PLUG
SUCTION
LINE
DISCHARGE
LINE
COMPRESSOR RAIL
ACCUMULATOR
Fig. 50 — Accumulator and Fusible Plug
Fig. 51 — Pressure-Actuated
Capacity Control Valve
NOTE: Black denotes closed contacts.
Fig. 52 — Timer Cycle
a38-190tf
Page view 49
1 ... 49 50 51 52 53 54 55 56

Comments to this Manuals

No comments