Carrier 38AUZ User Manual Page 18

  • Download
  • Add to my manuals
  • Print
  • Page
    / 28
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 17
18
OPERATING SEQUENCE
Base Unit Controls
Indoor (Supply) Fan
The indoor fan contactor (IFC) is remotely located at the fan
coil or fan section. If the thermostat fan operation is selected as
Continuous, the IFC is energized and the indoor (supply) fan
motor runs continuously. If the thermostat fan operation is
selected as Automatic, the IFC will be energized on a call for
Cooling; indoor (supply) fan motor runs. When thermostat call
for Cooling is satisfied, the IFC is de-energized and indoor
(supply) fan motor stops.
Cooling, Unit Without Economizer
On a thermostat call for Cooling, IFC will be energized and
indoor (supply) fan motor runs. Thermostat contact TC1
closes; terminal Y1 at 38AU unit receives 24-v. 24-v received
at CADM terminal Y. If anti-recycle time delay period has not
expired, CADM relay will remain open, preventing
compressor start. When safety pressure switches are closed, the
liquid line solenoid valve opens. When CADM time delay
expires, the compressor contactor is energized; both outdoor
fan motors start and compressor starts.
When space cooling load is satisfied, thermostat contacts TC1
open, removing 24-v at 38AU terminal Y. Compressor and
outdoor fan motors stop. Liquid line solenoid valve is
de-energized and valve closes. CADM begins its three-minute
anti-recycle time delay.
If either the Low Pressure Switch or High Pressure Switch
opens while thermostat contact TC1 remains closed, the
compressor contactor is de-energized (both fan motors and
compressor stop) and liquid line solenoid is de-energized
(valve closes). CADM initiates a TRIP event (cooling demand
sensed at CADM terminal Y but no current is measured at T1,
T2, T3 motor sensors); CADM relay opens and RED LED is
illuminated. TRIP condition maintains lockout of compressor
operation until CADM is manually reset. Reset CADM by
cycling unit main power.
Complete system shutdown may be caused by loss of main
power, open compressor internal overload, open low-pressure
or high-pressure switch, or a fault detected by the CADM
logic. Compressor operation without cooling may indicate the
compressors ASTP feature is active (unit sizes 12 and 14
only); disconnect unit power and allow compressor to cool. See
Service section for further details.
Cooling, Unit With Economizer
Refer to fan coil unit installation instructions and economizer
accessory installation instructions for operating sequences
when system is equipped with accessory economizer.
Heating
Refer to fan coil unit installation instructions and accessory
heating device installation instructions for operating sequences
in heating mode.
ROUTINE SYSTEM MAINTENANCE
These items should be part of a routine maintenance program,
to be checked every month or two, until a specific schedule for
each can be identified for this installation:
Quarterly Inspection (and 30 days after initial
start)
Indoor section
Condenser coil cleanliness checked.
Return air filter replacement
Outdoor hood inlet filters cleaned
Belt tension checked
Belt condition checked
Pulley alignment checked
Fan shaft bearing locking collar tightness checked
Condensate drain checked
Seasonal Maintenance
These items should be checked at the beginning of each season
(or more often if local conditions and usage patterns dictate):
Air Conditioning
Condenser fan motor mounting bolts tightness
Compressor mounting bolts
Condenser fan blade positioning
Control box cleanliness and wiring condition
Wire terminal tightness
Refrigerant charge level
Evaporator coil cleaning
Evaporator blower motor amperage
Heating
Power wire connections
Fuses ready
Manual-reset limit switch is closed
Economizer or Outside Air Damper
Inlet filters condition
Check damper travel (economizer)
Check gear and dampers for debris and dirt
Page view 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 27 28

Comments to this Manuals

No comments