Carrier 48SX024-048 User Manual Page 3

  • Download
  • Add to my manuals
  • Print
  • Page
    / 31
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 2
-45 1/2'
OPTIONAL RETURN
AIR OPENING
REQ’D CLEARANCES FOR SERVICING, in (mm)
Duct panel
Unit top
Side opposite ducts
Compressor access ...
(Except for NEC requirements)
. . 0
36 (914)
36 (914)
36 (914)
REQ’D CLEARANCES TO COMBUSTIBLE MATL in (mm)
Maximum extension of overhangs
Unit top . .
Duct side of unit . ...
Side opposite ducts . .
Bottom of unit
Flue panel
NEC REQ’D CLEARANCES in (mm)
Between units, control box side
Unit and ungrounded surfaces, control box side
Unit and block or concrete walls and other grounded
surfaces, control box side
7/8' (22.2) OIA
CONTROL ENTRY
48 (1219)
14 (356)
. 0
9 (229)
. . .0
30 (762)
42 (1067)
36 (914)
42 (1067)
52 49 9/16'
(1320.8) (1259 3)
^1 13/16'
(46 2)
OPTIONAL SUPPLY
AIR OPENING
I 5/8' (41 3) DIA
GAS ENTRY
1/2' - 14 NPT
GAS CONNECTION
REAR VIEW
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(Ib/kg)
UNIT HEIGHT
(in./mm)
lb
kg
A B
C D E
48SS018040 208/230-1-60
296 135
87/40 68/31
82/37 59/27
27.4/697
48SS024040 208/230-1-60
327
149 103/47 49/22
129/59 46/21 27 4/697
48SS024060 208/230-1-60
339 155
106/48 52/24
132/60 49/22 27 4/697
48SS030040 208/230-1-60, 208/230-3-60
344 157 106/48 53/24
132/60 53/24 27 4/697
48SS030060/080 208/230-1-60, 208/230-3-60
356
162
102/46 71/32
123/56 60/27 27 4/697
48SS036060/080 208/230-1-60, 208/230-3-60, 460-3-60, 575-3-60
360 164 92/42 82/37
117/53
69/31 27.4/697
48SS036100/120 208/230-1-60, 208/230-3-60, 460-3-60, 575-3-60
372
169 95/43 85/39
120/55 72/33
27 4/697
48SS042060/080
208/230-1-60, 208/230-3-60, 460-3-60 399 181 101/46 92/42
125/57
81/37
31 4/798
48SS042100/120 208/230-1-60, 208/230-3-60, 460-3-60 411
187 104/47
95/43
128/58 84/38 31.4/798
UNIT
F
in./mm
G
in./mm
CENTER OF GRAVITY in./mm
X
Y Z
48SS018040
19%/504.8 22W565 4
25 04/636 22 72/577
13 16/334 3
48SS024040 26 90/683 3 20 17/512 3
48SS024060 26 82/681 2 20.22/513 6
48SS030040
26 57/674.9 20.1/509.3
48SS030060/080
26 93/684
21 1/535.4
48SS036060/080
27.31/693 7 21 0/532 6
48SS036100/120 27 23/691 6 21 0/533 1
48SS042060/080
23%/606 4 26V4/666 8
26 87/682 5 21 0/533 1
14 96/380
48SS042100/120
26.81/681 21 0/533 7
LEGEND
CG Center of Gravity MAT’L — Material
COND Condenser NEC — National Electrical Code
LV Low Voltage REQ'D Required
NOTE: Clearances must be maintained to prevent recirculation of
air from outdoor-fan discharge
Fig. 3 — 48SS018-042 With Optional Base Rail Unit Dimensions