Carrier 50LJ User Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 38
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
TBI
EQUIP GND
EQUIP Equipment
GND — Ground
LEGEND
NEC — National Electrical Code
TB — Terminal Block
Fig. 13 — Field Power Wiring Connections
CONTROL WIRING Install a Carrier-approved acces
sory thermostat assembly according to the installation
instructions shipped with the accessory. Locate thermostat
assembly on a solid wall in the conditioned space to sense
average temperature (where airflow is stable and thermostat
is not in direct line of supply-air duct). Route thermostat
cable or equivalent leads of no. 18 AWG (American Wire
Gage) colored wire from subbase terminals to 24-v terminal
strip (PI). The terminal strip is located on the constant
volume control board on units with no economizer and on
the economizer board on units with the economizer option
(see Fig. 14).
The total wire length between the unit and the thermostat
and the return wire from the thermostat to the unit should
not exceed the following limits: 50 ft of 18 AWG, 80 ft of
16 AWG or 125 ft of 14 AWG. See Fig. 15 for field wiring
connections between the thermostat and the unit 24-v ter
minal block.
There are no required 115-v field wiring connections, there
fore, no provisions have been made in the unit for running
115-v wiring. If any of the field-installed options requiring
115-v connections are desired, the unit must be modified in
the field for 115-v wiring.
Options requiring 24-v or 115-v control wiring are listed
below.
Building Pressurization or Smoke Purge Mode Refer to
Building Pressurization Mode section and Smoke Purge Mode
section on page 24 for additional information. See Fig. 16
and unit wiring label for wiring details.
1. Firestat or smoke detector (field-supplied switch 1).
Remove factory-installed jumper wire and wire a field-
supplied firestat or smoke deteetor between terminals
2 and 3 on terminal block 2 (TB2) in the unit eontrol
box (see Fig. 14 for the location of TB2 in the control
box).
2. Switch to supply 24-v power to the economizer motor
during building pressurization or smoke purge (field-
supplied switch 5). Wire a normally-open switch
between terminal 3 on TB2 and terminal T1 in the econ
omizer motor.
3. Switch to open economizer outdoor air damper during
building pressurization or smoke purge (field-supplied
switch 6). Wire a field-supplied switch between termi
nals 8 and 9 on the economizer motor (in the top of
economizer motor). When this switch is manually opened,
it will drive the outside air damper fully open.
115-V Connections:
1. Building pressurization switch (field-supplied switch 2).
Wire a field-supplied switeh between terminal 4 on
TB2 and the Cl connection on the evaporator-fan con
tactor coil (IFCl on unit label diagram).
2. Smoke purge switch (field-supplied switch 4). Wire
a field-supplied switch between terminal 4 on TB2 (in
the unit control box) and the Cl conneetion on the power
exhaust eontactor coil (PECl on unit label diagram).
3. Switch to isolate evaporator-fan motor from power
exhaust motor during building pressurization or smoke
purge (field-supplied switch 3). Wire a field-
supplied switch in series with the wire from the Cl
eonnection on the IFCl to the red wire on the econo
mizer damper motor end switch (EDMS on unit label
diagram).
Convenience Outlet
115-V Connection: Convenience outlet can be mounted on
panel containing control circuit breakers CB3 and 4. (See
Fig. 14.) Remove sheet metal cover that conceals 2%
by
lVi6 in. hole and install outlet in hole. Wire between
terminals 4 and 5 on TB2 in the unit control box (see
Fig. 17). The convenience outlet should be ground fault
protected. Convenience outlet is to be used only when the
unit is not operating.
24-V Connections:
17
Page view 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 37 38

Comments to this Manuals

No comments