48/50PD05,06Single Package Displacement Ventilationor Single Zo ne Variable Air flow Rooftop UnitsElectric Cooling/Gas Heating with PURONR (R--410A)Re
10Fan StatusIf a Fan Status accessory was field installed, the unit must beconfigured for it by setting Configuration→UNIT→FN.SW tonormally open (1) o
100GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES1. Static pressure losses from accessories and options(economizer, etc.) must be added to external sta
101APPENDIX D -- ADDITIONAL STAR T--UP DATATable 60 – Air Quantity Limits (50PD Units)UNIT50PDCOOLING (cfm)HEATING (cfm)OPTIONAL ELECTRIC HEAT051200 2
102CONTROL SET POINT AND CONFIGURATION LOGModel Number: _____________________________Serial Number: ______________________________Date: ______________
103Table 65 — MODE - CONFIGURATION (cont)ITEM EXPA NSION RANGE UNITS DEFAULTCCNTABLE/SUB--- TABLECCN POINT ENTRYHEAT Heating Configuration HEAT_CFGHT.
104Table 65 — MODE - CONFIGURATION (cont)ITEM EXPA NSION RANGE UNITS DEFAULTCCNTABLE/SUB--- TABLECCN POINT ENTRYAIR.Q Air Quality Config. IAQ_CFGIA.CF
105Table 65 — MODE - CONFIGURATION (cont)ITEM EXPA NSION RANGE UNITS DEFAULTCCNTABLE/SUB--- TABLECCN POINT ENTRY(GENERIC = CCN only) GENERICSPOINT 01
106UNIT START-UP CHECKLISTMODEL NO.:DATE: ______________SERIAL NO: _____________________________________TECHNICIAN: __________________________________
107Copyright 2009 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 6/09Manufacturer reserves the right to c
11Table 4 – Setting an Occupied Time Schedule - Weekdays Only for 7:30 to 22:30DISPLAYMENUSUB--SUBMODEKEYPADENTRYITEM DISPLAY ITEM EXPANSION COMMENTTI
12SER VICE TESTThe Service Test function can be used to verify proper operation ofcompressors, heating stages, indoor fan, outdoor fans, powerexhaust
13Fire ShutdownThe fire shutdown input is provided for unit shutdown in responseto a fire alarm or smoke detector. The Fire Shutdown Switchconfigurati
14RH Sensor On OAQ Input (RH.S)This configuration identifies if a space relative humidity sensor isinstalled on the outdoor air quality (OAQ) input. A
15When the space sensor has a setpoint slider adjustment, the cooland heat setpoints (occupied) can be offset by sliding the bar fromone side to the o
16When the unit is in cooling or unoccupied free cooling mode, thesupply fan will modulate between the configured Supply FanMaximum Speed (Configurati
17 Time OCSP OCSP - 0.5 F OCSP + FS.CD Cooling Speed Demand Window - Unit Supply Fan Speed Modulates to Move Space Temperature along a Dened Curve to
18Table 6 – Fan Level Control of Outdoor FanFANLEVELFANSPEEDCONDITIONS TO TRANSITION TO NEXTLOWER LEVELCONDITIONS TO TRANSITION TO NEXTHIGHER LEVEL0 O
19When SAT.H = ENBL, the Supply Air Temperature (Temperatures→AIR.T→SAT) sensor reading is displayed at the ScrollingMarquee and the CCN tables during
2TROUBLESHOOTING 25...Complete Unit Stoppage 25...Restart Procedure 26...
20Economizer Actuator CommunicationThe economizer actuator used with the 48/50PD units is aMulti-- Function Technology (MFT) actuator. This allows the
21The shape of the Economizer Minimum Position vs. Fan Speedcurve is determined by the configuration parameters: Econ Min at25% Fan speed (Configurati
22IAQ (Analog Input)The ComfortLinkt control is configured for indoor air qualitysensors which provide 4 to 20 mA signal for 0 to 2000 ppm CO2.If the
23IAQ (Switch Input)Indoor air quality can also be measured using a switch input. Forthe purpose of specifying the type of switch input, low CO2levels
24Temperature Compensated Start LogicThe following conditions must be met for the algorithm to run:S Unit is in unoccupied state.S Next occupied time
25Loadshed Group Number (S.GRP)This corresponds to the loadshed supervisory devices that resideelsewhere on the CCN network and broadcast loadshed and
26Restart ProcedureBefore attempting to restart the machine, check the alarm list todetermine the cause of the shut down. If the shutdown alarm for ap
27Alert Code T092 -- Circuit A Suction Pressure TransducerFailureThis alert occurs when the board does not properly read thetransducer voltage. A circ
28Alert Code T17 9 -- Loss of Communication with theEconomizer Control BoardThis alert occurs when the MBB cannot communicate with theECB. Economizer
29Alert Code T414There are 6 different alerts under this one alert code. Pressing enterand esc on the marquee or navigator to expand the T414 alert wi
3FIRE, EXPLOSION HAZARDFailure to follow this warning could result in personalinjury, death and/or property damage.Improper installation, adjustment,
30Table 7 – ComfortLink™ Alarm CodesALARMOR ALERTNUMBERDESCRIPTIONACTION TAKEN BYCONTROLRESETMETHODPROBABLE CAUSET051Digital Compressor Control Board
31Table 8 – LEN and CCN Communication ResistancesDeviceBoard SerialNumber(LEN) Resistance between Pins/Connector(CCN) Resistance between Pins/Connecto
32Table 9 – Cooling Service AnalysisPROBLEM CAUSE REMEDYCompressor and Fan Will Not Start Power failure. Call power company.Fuse blown or circuit brea
33POWER LED (green) ⎯ indicates voltage is present at the24VAC power terminal. When the 2 minute anti--short cycle timeris active, the green LED will
34Table 10 – DSC Red LED Flash CodesLED FlashCodeDescription Action Takenby ControlResetMethodProbable Cause1FlashReserved for Future Use N/A N/A N/A2
35Table 11 – Economizer Service AnalysisPROBLEM POSSIBLE CAUSE REMEDYDamper Does Not Move. Indoor Fan is off. Check for proper VFD connections. Check
36Heating TroubleshootingUse the unit Scrolling Marquee display or a CCN device to viewthe heating status display and the heating diagnostic display (
37LEGENDIDM -- Induced-Draft MotorIGC -- Integrated Gas Unit ControllerNOTE: Thermostat Fan Switch in the “AUTO” position.C07014Fig. 9 -- IGC Service
38Table 13 – IGC Board LED Alarm CodesLEDFLASHCODEDESCRIPTIONACTION TAKEN BYCONTROLRESET METHOD PROBABLE CAUSEOn Normal Operation— — —Off Hardware Fai
39Thermistor TroubleshootingThe electronic control uses thermistors to sense temperatures usedto control operation of the unit. Resistan ces at variou
4Run StatusService TestTemperaturesPressuresSetpointsInputsOutputsConfigurationTime ClockOperating ModesAlarmsENTERESCMODEAlarm StatusTIMEEWTLWTSETP12
40Sensor TrimCorrective offsets can be applied to the space temperature and thesupply air temperature sensor readings. These corrections are set inthe
41Table 15 – Temperature (_F) vs Resistance/Voltage Drop Values forRAT, OAT, SAT, and SPT Thermistors (10K at 25_C Resistors)TEMP VOLTAGE RESISTANCE T
42Table 16 – Temperature (_F) vs. Resistance/Voltage Drop Values for SCT Sensors (5K at 25_C Resistors)TEMP(F)VOLT AGEDROP (V)RESISTANCE(Ohms)TEMP (F)
43Table 17 – Temperature vs Resistance Values for the DTT Thermistor(86K at 25_C Resistors)Degree C Degree F Resistance (k Ohms)--- 4 0 --- 4 0 2889.6
44Table 18 – Pressure (psig) vs. Voltage Drop Values for Suction Pressur e TransducersPRESSURE(psig)VOLT AGEDROP (V)PRESSURE(psig)VOLT AGEDROP (V)PRES
45C08582Fig. 13 -- 48PD Control Wiring Schematic48/50PD
46C08583Fig. 14 -- 50PD Control Wiring Schematic48/50PD
47C08584Fig. 15 -- 48/50PD Power Wiring Schematic and Legend48/50PD
48C08657Fig. 16 -- Typical Unit Component Arrangement48/50PD
49Main Base Board (MBB)See Fig. 17 and Table 19. The MBB is the center of theComfortLink control system. It contains the major portion of theoperating
5Table 2 – Scrolling Marquee Mode and Menu Display StructureRUNSTATUSSERVICETESTTEMPERATURES PRESSURES SETPOINTS INPUTS OUTPUTS CONFIGURA TIONTIMECLOC
50Table 19 – MBB ConnectionsDISPLAYNAMEPOINT DESCRIPTION SENSOR LOCATION TYPE OF I/OCONNECTIONPIN NUMBERINPUTSInput power from TRAN1 control box 24 VA
51Economizer Control B oard (ECB)The ECB controls the economizer actuator. (See Fig. 18 and Table20.) The control signal from the ECB uses either the
52Table 20 – ECB ConnectionsDISPLAYNAMEPOINT DESCRIPTION SENSORLOCATIONTYPE OF I/O CONNECTIONPIN NUMBERINPUTSInput power from MBB control box 24 VAC J
53Modulation Board (AUX1)The AUX1 board controls the compressor capacity and the indoorfan speed (See Fig. 19 and Table 21.) It outputs a 1 -- 5vdc an
54Digital Scroll Control Board (DSC)The DSC board controls the compressor’s capacity. (See Fig. 20and Table 22.) It receives a 1--5vdc signal from the
55Variable Frequency Drive (VFD)The VFD varies the frequency of the AC voltage supplied to theindoor fan. (See Fig. 21 and Table 23.) This causes the
56Integrated Gas Control (IGC) BoardThe IGC is provided on gas heat units. (See Fig. 22 and Table 24.)The IGC controls the direct spark ignition syste
57Low Voltage Terminal Strip(TB1)This circuit board provides a connection point between the majorcontrol boards and a majority of the field-installed
58Scrolling Marquee DisplayThis device is the keypad interface used to access rooftopinformation, read sensor values, and test the unit. (See Fig. 24.
59Space Temperature Sensor (T--58)The T--58 space temperature sensor (part no. 33ZCT58SPT) is afield-installed accessory. The T--58 sensor communicate
6Conventions Used in This ManualThe following conventions for discussing configuration points forthe local display (Scrolling Marquee or Navigator™ ac
60TO MAINBASE BOARDREDBLKREDBLKREDBLKSENSOR 1SENSOR 2SENSOR 3REDBLKSENSOR 6SENSOR 5REDBLKSENSOR 4REDBLKREDBLKREDBLKSENSOR 8SENSOR 7 SENSOR 91REDBLKTB1
61Carrier Accessory KitsThere are specific accessory kits sold for various field installedaccessories. These kits vary based on model, size, voltage,m
62UNIT OPERATION AND SAFETY HAZARDFailure to follow this warning could cause personalinjury, death and/or equipment damage.Puronr (R--410A) refrigeran
63UNIT RELIABILITY HAZARDFailure to follow this caution may result in reduced unitperformance.High velocity water from a pressure washer, garden hose,
64To inspect blower wheel, open heat section door. Using aflashlight, look into the flue exhaust duct to inspect. If cleaning isrequired, remove motor
657. Realign fan and motor pulleys:a. Loosen fan pulley setscrews.b. Slide fan pulley along fan shaft.c. Make angular alignment by loosening motor fro
66Condenser-Fan Adjustment1. Shut off unit power supply.2. Remove condenser-fan assembly (grille, motor, motorcover, and fan) and loosen fan hub setsc
67To Use the Cooling Charging ChartUse the temperature and pressure readings, and find theintersection point on the cooling charging chart. If interse
688. Once desired pressure is established, set unit setting for nocall for heat, turn off main gas valve, removepressure-measuring device, and replace
69Filter DrierReplace filter drier whenever refrigerant system is exposed toatmosphere. Only use factory specified liquid-line filter driers withworki
7On 3-phase units, it is important to be certain the compressors arerotating in the proper direction. To determine whether or notcompressors are rotat
70APPENDIX A - LOCAL DISPLAY AND CCN TABLESTable27–MODE- RUN STATUSITEM EXP ANSION RANGE UNITSCCNTABLE/SUB --- TABLECCN POINTCCN WRITESTATUSRUN STATUS
71APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)Table 27 — MODE - RUN STATUS (cont)ITEM EXPANSION RANGE UNITSCCNTABLE/SUB--- TABLECCN POINTCCN WRITE
72APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)Table 28 – MODE - SERVICE TESTITEM EXPANSION RANGE UNITS DEFAULT CCN TABLE/SUB --- TABLE CCN POINTCC
73APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)Table 31 – MODE - SET POINTSITEM EXPANSION RANGE UNITS DEFAULT CCN TABLE/SUB--- TABLE CCN POINTSETPO
74APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)Table 34 – MODE - CONFIGURATIONITEM EXPA NSION RANGE UNITS DEFAULTCCNTABLE/SUB--- TABLECCN POINTPAGE
75APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)Table 34 — MODE - CONFIGURATION (cont)ITEM EXPA NSION RANGE UNITS DEFAULTCCNTABLE/SUB--- TABLECCN PO
76APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)Table 34 — MODE - CONFIGURATION (cont)ITEM EXPA NSION RANGE UNITS DEFAULTCCNTABLE/SUB--- TABLECCN PO
77APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)Table 34 — MODE - CONFIGURATION (cont)ITEM EXPA NSION RANGE UNITS DEFAULTCCNTABLE/SUB--- TABLECCN PO
78APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)Table 35 – MODE - TIME CLOCKITEM EXPANSION RANGE UNITS DEFAULTCCNTABLE/SUB--- TABLECCN POINTTIME CLO
79APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)Table 3 7 – MODE - OPERATING MODESITEM EXPANSION RANGE UNITSCCNTABLE/SUB--- TABLECCN POINTCCNWRITEST
8Gas Heat (48PD Only)Inspect the gas heat section of the unit. Verify the number ofburners match the number of heat exchanger openings and theburner a
80APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)Table 37 — MODE - OPERATING MODES (cont)ITEM EXPANSION RANGE UNITSCCNTABLE/SUB--- TABLECCN POINTCCNW
81APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)Table 37 — MODE - OPERATING MODES (cont)ITEM EXPANSION RANGE UNITSCCNTABLE/SUB--- TABLECCN POINTCCNW
82APPENDIX B - VFD INFORMATIONOn 48/50PD units, the supply fan speed is controlled by a 3-- phaseVFD. The VFD is located in the supply fan section beh
83APPENDIX B - VFD INFORMATION (CONT)Table 40 – VFD CONFIGURATIONSAPPLICATION CRITICAL DRIVE PARAMETERS FOR ABB ACH 550 DRIVESParameter GroupParameter
84APPENDIX B - VFD INFORMATION (CONT)VFD OperationThe VFD keypad is shown in Fig. 42. The function of SOFTKEYS 1 and 2 change depending on what is dis
85APPENDIX B -- VFD INFORMATION (CONT)To adjust the speed in HAND mode, press the UP or DOWNbuttons (the reference changes immediately). The reference
86Download Application ParametersTo download application parameters only to the control panel fromthe VFD, perform the following procedure:1. Install
87HistoryFor reference, the last three fault codes are stored into parameters0401, 0412, 0413. For the most recent fault (identified byparameter 0401)
88APPENDIX B - VFD INFORMATION (CONT)Table41–FAULTCODESFAULTCODEFAULT NAME IN PANEL DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION1OVERCURRENTOutput cu
89APPENDIX B - VFD INFORMATION (CONT)Table 41 — FAULT CODES (cont)FAULTCODEFAULT NAME IN PANEL DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION1000PAR HZ
9Table 3 – Application Specific ConfigurationsITEM EXPANSION DEFAULT UNITSDISPLACEMENTVENTILATIONSINGLE ZONEVAVSASP Cool Supply Air Setpoint 65 dF 65
90APPENDIX B - VFD INFORMATION (CONT)Table 42 – ALARM CODESALARMCODEALARM NAMEIN PANELDESCRIPTION AND RECOMMENDED CORRECTIVE ACTION2001 --- Reserved20
91APPENDIX B - VFD INFORMATION (CONT)Main Fan ReplacementThe main cooling fan of the VFD has a life span of about 60,000operating hours at maximum rat
92APPENDIX C -- START--UP DATATable 44 – Fan Performance - 48PDD05 Vertical UnitsAIRFLOW(Cfm)AVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0
93Table 46 – Fan Performance - 48PDF05 Vertical UnitsAIRFLOW(Cfm)AVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0Rpm Bhp Rpm Bhp Rpm Bhp Rpm
94Table 48 – Fan Performance - 48PDE06 Vertical UnitsAIRFLOW(Cfm)AVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0Rpm Bhp Rpm Bhp Rpm Bhp Rpm
95Table 50 – Fan Performance - 48PDD05 Horizontal UnitsAIRFLOW(Cfm)AVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0Rpm Bhp Rpm Bhp Rpm Bhp Rp
96Table 52 – Fan Performance - 48PDF05 Horizontal UnitsAIRFLOW(Cfm)AVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0Rpm Bhp Rpm Bhp Rpm Bhp Rp
97Table 54 – Fan Performance - 48PDE06 Horizontal UnitsAIRFLOW(Cfm)AVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0Rpm Bhp Rpm Bhp Rpm Bhp Rp
98Table 56 – Fan Performance - 50PD05 Vertical UnitsAIRFLOW(Cfm)AVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0Rpm Bhp Rpm Bhp Rpm Bhp Rpm B
99Table 58 – Fan Performance - 50PD05 Horizontal UnitsAIRFLOW(Cfm)AVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0Rpm Bhp Rpm Bhp Rpm Bhp Rpm
Comments to this Manuals