Carrier 38BK-018 Specifications

Browse online or download Specifications for Heat pumps Carrier 38BK-018. Carrier 38BK-018 Specifications User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 28
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Installation, Start-Up
and Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS
.....................1
GENERAL ....................................1,2
INSTALLATION ..............................2-14
Step 1 − Complete Pre-Installation Checks .......2
UNPACK UNIT
INSPECT SHIPMENT
Step 2 − Select Location
.......................2
Step 3 − Mount Mounting Bracket on Wall ........5
Step 4 − Connect Refrigerant Piping .............5
Step 5 − Connect Condensate Drain Line ........11
Step 6 − Make Electrical Connections ...........12
Step 7 − Make Connections to Outdoor Unit .....13
COOLING-ONLY SYSTEMS
HEAT PUMP SYSTEMS
Step 8 − Install Fan Coil Unit Onto Mounting
Bracket
....................................13
START-UP .................................14-17
40QN Control System .........................14
After Extended Shutdowns .....................15
Seasonal Changeovers ........................15
To Turn The Unit On and Off ...................15
Adjusting Airflow .............................15
Operating Mode Memory .......................15
Automatic Operation (Auto) Mode ...............15
Operating Fault Diagnosis .....................15
Microprocessor Control Operation ..............15
CLEANING AND MAINTENANCE ...............18,19
Lubrication ..................................18
To Install or Replace Remote Controller
Batteries ...................................18
To Set the Current Time .......................19
To Remove and Clean or Replace Air Filters ......19
TO REMOVE AIR FILTERS
TO CLEAN OR REPLACE FILTERS
To Clean Indoor Unit Front Panel
...............19
To Clean Indoor Coil ..........................19
To Clean Outdoor Coil (Outdoor Unit) ...........19
Cleaning Condensate Drains ...................19
SERVICE ....................................20
Diagnostic Codes .............................20
System Tests ................................20
THERMISTOR TESTS
THERMISTORS
COMPRESSOR FAILURE
REVERSING VALVE FAILURE (38BK Only)
System Safeties and Interlocks
.................20
INDOOR FAN FAILURE
COMPRESSOR SHORT-CYCLING PROTECTION
INDOOR COIL FREEZE PROTECTION
(Cooling or Dehumidification Mode Only)
INDOOR COIL HIGH-TEMPERATURE
PROTECTION (Heat Pump Systems Only)
TROUBLESHOOTING
........................20-26
START-UP CHECKLIST ..................CL-1,CL-2
SAFETY CONSIDERATIONS
Installing and servicing air-conditioning equipment can be
hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install or service air-conditioning equipment.
Untrained personnel can perform basic maintenance, such
as cleaning and replacing filters. All other operations should
be performed by trained service personnel. When working
on air conditioning equipment, observe precautions in lit-
erature and on tags and labels attached to unit.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for brazing operations. Have fire ex-
tinguisher available. Read these instructions thoroughly. Con-
sult local building codes and National Electrical Code (NEC)
for special installation requirements.
Before installing or servicing system, always turn off
main power to system. There may be more than one dis-
connect switch. Turn off indoor fan coil power if ap-
plicable. Electrical shock can cause personal injury.
GENERAL
The Carrier 40QNH heat pump high wall fan coil units
(Fig. 1) come with supplemental electric heat. If your ap-
plication requires heating, heat pump units must be used, both
outdoors and indoors. See Table 1 for recommended system
combinations.
Fig.1—Typical 40QNH High Wall Fan Coil Unit
40QNB,QNH
018,024
High Wall Fan Coil Units
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 3e 2f
PC 111 Catalog No. 534-003 Printed in U.S.A. Form 40QN-4SI Pg 1 5-99 Replaces: 40QN-1SI
Page view 0
1 2 ... 28

Summary of Contents

Page 1 - Installation, Start-Up

Installation, Start-Upand Service InstructionsCONTENTSPageSAFETY CONSIDERATIONS...1GENERAL ...1,2IN

Page 2 - INSTALLATION

Table 4F — Physical Data — 40QNH High Wall Fan Coil UnitsUNIT 40QNH 018 024NOMINAL CAPACITY (Tons) 11⁄22NOMINAL SIZE (Btuh) 18,000 24,000OPERATING WEI

Page 3

Step 5 — Connect Condensate Drain Line —Observe all local sanitary codes when installing condensatedrains.1. Connect drain line by inserting a5⁄8-in.

Page 4

Step 6 — Make Electrical Connections — Be surefield wiring complies with local building codes and NEC,and unit voltage is within limits shown in Table

Page 5

Step 7 — Make Connections to the Outdoor UnitCOOLING-ONLY SYSTEMS — To connect the 38HDC,HDL or HDS condensing unit to the fan coil unit(s) so thatthe

Page 6

START-UPComplete the following checks and the Start-Up Check-list on page CL-1 before system start-up. Refer to outdoorunit installation, start-up and

Page 7

After Extended Shutdowns — If the system has beenturned off for more than 12 hours, turn on the indoor andoutdoor unit disconnect switches to supply p

Page 8

• Cooling Mode — When the Cooling mode is selected, theindoor fan will operate continuously at the selected speedif the speed is high, medium, or low.

Page 9

• Automatic Operation Mode for Cooling Only Systems(38HDC, HDL, and HDS) — The unit samples the air inthe room. Based on the room temperature, the uni

Page 10

CLEANING AND MAINTENANCETo avoid the possibility of electric shock, before per-forming any cleaning and maintenance operations, al-ways turn off power

Page 11

To Set the Current TimeTA1. Press the button (located on the back of the remotecontroller; see Fig. 23) with an instrument screwdriver orsimilar small

Page 12

Table 1 — System Combinations for Indoorand Outdoor UnitsSYSTEM INDOOR UNIT OUTDOOR UNITHigh WallCoolingOnly40QNB018 38HDC,L01840QNB024 38HDC,L024(2)

Page 13

SERVICEWhen servicing unit, turn off all electric power to unitto avoid shock hazard or injury from rotating parts.Do not vent refrigerant to atmosphe

Page 14 - START-UP

Table 10 — 40QN Thermistor Properties*TEMP(F)MINIMUMOHMSNOMINALOHMSMAXIMUMOHMSMINIMUMTHERMISTORVOLTS — DCNOMINALTHERMISTORVOLTS — DCMAXIMUMTHERMISTORV

Page 15

LEGENDNEC — National Electrical CodePipingLine Voltage24 VThermistor*Standard.†Field supplied.NOTES:1. All piping must follow standard refrigerant pip

Page 16

LEGEND AND NOTES FOR FIG. 26-28AGING — For the Burn-In Test (short these terminals)AS, ASS’Y — AssemblyC—ContactorCAP — CapacitorCH — Crankcase Heater

Page 17 - EMER — Emergency Mode

40QNH018, 024 FAN COIL38BK018, 024 OUTDOOR SECTIONFig. 26 — 40QNH Fan Coil Unit with 38BK Outdoor Heat Pump Unit24

Page 18 - Batteries

40QNB018, 024 FAN COIL38HDC018, 024 OUTDOOR SECTION*38HDC018 ONLY.Fig. 27 — 40QNB Fan Coil Unit with 38HDC Cooling Only Outdoor Condensing Unit25

Page 19 - PRESS SET TIME PRESSTA TA

40QNB018, 024 FAN COIL38HDL018, 024 OUTDOOR SECTIONFig. 28 — 40QNB Fan Coil Unit with 38HDL Cooling Only Outdoor Condensing UnitCopyright 1999 Carrier

Page 20 - TROUBLESHOOTING

START-UP CHECKLISTI. PRELIMINARY INFORMATIONOUTDOOR UNIT: MODEL NO.INDOOR UNIT: MODEL NO.SERIAL NO.SERIAL NO.ACCESSORIES: ____________________________

Page 21 - Table 11 — Troubleshooting

START-UP CHECKLIST (cont)HAS PIPING SYSTEM BEEN EVACUATED TO 1000 MICRONS?HAS SYSTEM CHARGE BEEN WEIGHED IN (IF REQUIRED)?HAVE SERVICE VALVES BEEN FUL

Page 22

1. Dimensions in ( ) are in millimeters.2. Direction of airflow.3. Refrigerant, drain, and power connections may be made in unitrear, bottom, left side

Page 23

Table 3 — High Wall Unit Package ContentsITEM QUANTITYUnit Mounting Template 1Unit Mounting Bracket 11-in. Lag Screws For Unit Mounting 8Hollow Wall A

Page 24 - 38BK018, 024 OUTDOOR SECTION

Step 3 — Mount Mounting Bracket on Wall1. Decide how refrigerant will be piped. If necessary, knockout the appropriate pre-punched holes (Fig. 4) on u

Page 25 - *38HDC018 ONLY

d. Install factory-supplied flare connection and Accu-Rater metering device in liquid line at the fan coil uniton 38HDC, HDL and 38BK systems (Fig. 9).

Page 26 - Tab 3e 2f

Table 4A — Physical Data — 38HDC Condensing UnitsUNIT 38HDC 018 024NOMINAL CAPACITY (Tons) 11⁄22OPERATING WEIGHT (lb) 150 154REFRIGERANT TYPE R-22Cont

Page 27 - III. PIPING

Table 4C — Physical Data — 38HDS Condensing UnitsUNIT 38HDS 024 048NOMINAL CAPACITY (Tons) 24OPERATING WEIGHT (lb) 159 292REFRIGERANT TYPE R-22Control

Page 28 - IV. START-UP

Table 4E — Physical Data — 38BK018, 024 Outdoor Heat Pump UnitsUNIT 38BK018* 38BK024*NOMINAL CAPACITY (Tons) 11⁄22OPERATING WEIGHT (lb) 154 167REFRIGE

Comments to this Manuals

No comments