I Determine cooling and heating requirements
at design conditions.
Given:
Required Gross Cooling
Capacity (TC) . . . . . . . . . . . . . . .229,000 Btuh
Gross Sensible Heat
Capacity (SHC) . . . . . . . . . . . . . .178,000 Btuh
Required Heating Capacity . . . . . . .190,000 Btuh
Condenser Entering Air
Temperature . . . . . . . . . . . . . . . . 95 F Summer
Indoor Air Temperature . . . . . .80 F edb, 67 F ewb
Evaporator Air Quantity. . . . . . . . . . . . 8,000 cfm
External Static Pressure . . . . . . . . . . . .1.30 in. wg
Electrical Characteristics (V-Ph-Hz) . . . . . 460-3-60
Optional economizer required. Vertical supply
required.
II Select unit based on required cooling
capacity.
Enter Cooling Capacities table for 48HG024 at
condenser entering temperature of 95 F, evaporator
air quantity of 8,000 cfm, and indoor air tempera-
ture of 67 F. The 48HG024 unit will provide a total
cooling capacity of 261,000 Btuh and a SHC of
195,000 Btuh. For evaporator air temperatures
other than 80 F, calculate SHC correction using for-
mula in notes under cooling capacity tables.
Unit meets design conditions for TC and SHC.
NOTE: Unit ratings are gross capacities and do not
include the effect of indoor fan motor heat. To cal-
culate net capacities, see Step V.
III Select heating capacity of unit to provide
design condition requirement.
In Heating Capacities and Efficiencies table, note
that 48HGD024 (low heat) unit will provide
205,000 Btuh with an input of 250,000 Btuh.
IV Determine fan speed and power require-
ments at design conditions.
Before entering the Fan Performance tables, calcu-
late the total static pressure required based on unit
components. Tabulated fan performance includes
filters and wet evaporator coil. Refer to Accessory/
FIOP Static Pressure — 48/50HG014-028 table
for added pressure drops.
Calculate pressure drop:
Design External Static Pressure 1.30
Economizer Static Pressure + 0.10
1.40 in. wg (ESP)
Enter Fan Performance tables for 48HGD024 (low
heat units, vertical supply) at 8,000 cfm and
1.40 in. wg. The rpm is 1138 and the Bhp is 6.58.
The factory-installed optional 7.5 hp motor
and alternate drive are sufficient for this operation.
V Determine net cooling capacities.
Cooling capacities are gross capacities and do not
include indoor (evaporator) fan motor (IFM) heat. To
determine input power to the motor, enter the Fan
Performance tables for 48HGD024 (low heat units)
at 8,000 cfm and 1.40 in. wg. Input watts to the
motor are 5719.
Determine net cooling capacity and net sensible
cooling capacity using the following formulas:
IFM Heat = Input Watts x 3.412 Btuh/Watt
= 5719 x 3.412
= 19,513 Btuh
Net Capacity = Gross Capacity – IFM Heat
= 261,000 – 19,513
= 241,487 Btuh
Net Sensible Cap. = Gross Sensible Cap. – IFM Heat
= 195,000 – 19,513
= 175,487 Btuh
The calculations show that a 48HGD024 unit is the
correct selection for the given conditions.
VI Select the unit that corresponds to power
source available.
The electrical data table shows that the 460-3-60
unit is available.
Selection procedure (with 48HG024 example)