Carrier 50DD028 Specifications

Browse online or download Specifications for Heat pumps Carrier 50DD028. Carrier 50DD028 Specifications User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 64
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ...................2
INSTALLATION .............................2-30
Rigging and Unit Placement ..................2
Roof Curb ...................................2
Roof Mount ..................................2
Slab Mount ..................................2
Alternate Unit Support Methods ...............8
Positioning ..................................8
Field-Fabricated Ductwork ....................8
MODELS 50DJ,DK VERTICAL SUPPLY/RETURN
MODELS 50DW,DY HORIZONTAL SUPPLY/
RETURN
Condensate Drain ............................8
Outdoor-Air Inlet Adjustments ................8
MANUAL OUTDOOR-AIR DAMPER
ECONOMIZER SETTINGS
Install Outdoor-Air Hoods ...................12
25% OUTDOOR-AIR HOOD
ECONOMIZER HOODS
BAROMETRIC RELIEF/CONSTANT VOLUME
POWER EXHAUST HOOD
MODULATING POWER EXHAUST HOOD
Static Pressure Control Plastic Tubing .......15
Field Wire Routing ..........................15
ROUTING THROUGH BOTTOM OF UNIT
ROUTING THROUGH SIDE OF UNIT
Field Electrical Connections .................16
POWER WIRING
CONTROL WIRING, CV UNITS (DJ,DW)
CONTROL WIRING, VAV UNITS (DK,DY)
START-UP ................................30-44
Unit Preparation ............................30
Compressor Mounting .......................30
Internal Wiring ..............................30
Refrigerant Service Valves ...................30
Crankcase Heaters ..........................30
Compressor Oil .............................30
Unit Voltage ................................31
Leak Test and Dehydration ..................31
Evaporator Fan, Belt, and Sheaves ...........31
Condenser Fans and Motors .................31
Return-Air Filters ...........................31
Economizer Inlet Screens ...................31
Economizer Dampers and Potentiometer
Settings ..................................31
25% Outdoor-Air Damper ....................37
Switch and Potentiometer Settings, VAV Units
Only .....................................37
Quick Test Program, VAV Units Only .........39
Variable Air Volume Units (50DK,DY)
Cooling ...................................42
Variable Air Volume Units, Warm-Up Heat (50DK,DY
Units with Optional Electric Heat) ..........42
Operating Sequences .......................42
CONSTANT VOLUME UNITS (50DJ,DW)
VARIABLE VOLUME UNITS (50DK,DY)
BUILDING PRESSURIZATION MODE, ALL UNITS
SMOKE PURGE MODE, ALL UNITS
VARIABLE VOLUME UNITS EQUIPPED WITH THE
STATIC PRESSURE CONTROL OPTION
VENTILATION AIR CIRCULATION
(CONTINUOUS FAN)
AUTOMATIC CHANGEOVER USING AUTOMATIC
CHANGEOVER THERMOSTAT
Head Pressure Control ......................44
SERVICE ..................................44-52
Service Access .............................44
COMPRESSORS
EVAPORATOR-FAN MOTORS, PULLEYS, AND
BELTS
UNIT CONTROL BOX
ELECTRIC HEAT CONTROL BOX
HEATER BOX
ECONOMIZER DAMPER MOTOR
25% OUTDOOR-AIR DAMPER
POWER EXHAUST MOTOR
MODULATING POWER EXHAUST DAMPER
MOTOR
RETURN-AIR FILTERS
CONDENSER FANS AND FAN MOTORS
INLET GUIDE VANE MOTOR
MODULATING POWER EXHAUST
DIFFERENTIAL PRESSURE SWITCH
INLET GUIDE VANE DIFFERENTIAL PRESSURE
SWITCH
Cleaning ....................................46
Lubrication .................................46
COMPRESSORS
FAN SHAFT BEARINGS
FAN MOTOR BEARINGS
DOOR HINGES
Adjustments ................................47
EVAPORATOR-FAN MOTOR PLATE
BELT INSTALLATION AND TENSIONING
PULLEY ALIGNMENT
INSTALLING ALTERNATE MOTOR PULLEY
CONDENSER FAN
ENTHALPY CONTROL, MAT, AND ECONOMIZER
DAMPER VENT POSITION
25% OUTDOOR-AIR DAMPER
AUXILIARY SWITCH, POWER EXHAUST
DIFFERENTIAL PRESSURE SWITCH SET POINT
AND NULL SPAN (VAV Units Only When Equipped
with Inlet Guide Vane and Static Pressure Control
Option)
DIFFERENTIAL PRESSURE SWITCH SET POINT
AND NULL SPAN (VAV Units Only When Equipped
with Modulating Power Exhaust Option)
REFRIGERANT CHARGE
50DJ,DK,DW,DY024-030
Single-Package Cooling Units
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
Tab 1b
PC 111 Catalog No. 565-027 Printed in U.S.A. Form 50D-2SI Pg 1 4-95 Replaces: 50DJ,DK-13SI
Page view 0
1 2 3 4 5 6 ... 63 64

Summary of Contents

Page 1 - Service Instructions

Installation, Start-Up andService InstructionsCONTENTSPageSAFETY CONSIDERATIONS ...2INSTALLATION ...2-30Rigg

Page 2

UNIT50DW,DYWEIGHT* A B C D ELb Kg mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in.024 2650 1202 1549.4 5-1 2182.0 7-17⁄8682.0 2-27⁄83909.0 12-97⁄8533

Page 3 - Fig. 1 — Rigging Label

Fig. 4 — Drain Location SelectionFig. 5 — Condensate Drain LocationROOF MOUNT DRAINSLAB MOUNT DRAINFig. 7 — Condensate Drain Piping DetailsFig. 8 — Ou

Page 4

Install Outdoor-Air Hoods25% OUTDOOR-AIR HOOD — This hood is shipped sepa-rately from the base unit, in a carton marked 50DJ900411.This carton contain

Page 5

ECONOMIZER HOODS — These hoods are shipped sepa-rately from the base unit, in a crate marked 50DJ900051.This carton contains:3 — preassembled economiz

Page 6 - Deg in. Deg in. Deg in

economizer hood assembly.) Once economizer hood as-sembly is in place, secure it using 10 of the screws fromthe fastener package (5 per side).10. Usin

Page 7

Cartons contain:1 — preassembled hood/damper/motor assembly1 — fastener package (taped to inside of hood)The fastener package contains:6 — screws,1⁄4A

Page 8 - Outdoor Air Inlet Adjustments

Field Electrical ConnectionsIMPORTANT: The VAV units (50DK,DY) generate,use, and can radiate radio frequency energy. If unitsare not installed and use

Page 9

Unit failure as a result of operation on improper line volt-age or excessive phase imbalance constitutes abuse and maycause damage to electrical compo

Page 10

Table 2 — Electrical Data — 50DJ,DW024NOMINALV-PH-HZVOLTAGERANGECOMPRNO. 1COMPRNO. 2OFM IFMPOWER EXHAUSTFAN MOTOR*ELECTRICHEATPOWER SUPPLYMin Max RLA

Page 11 - SLAB MOUNT DRAIN

Table 3 — Electrical Data — 50DJ,DW028NOMINALV-PH-HZVOLTAGERANGECOMPRNO. 1COMPRNO. 2OFM IFMPOWER EXHAUSTFAN MOTOR*ELECTRICHEATPOWER SUPPLYMin Max RLA

Page 12 - Install Outdoor-Air Hoods

Refrigerant Feed Components ...51Thermostatic Expansion Valve (TXV) ...51Moisture/Liquid Indicator ...51Filter Drie

Page 13

Table 4 — Electrical Data — 50DJ,DW030NOMINALV-PH-HZVOLTAGERANGECOMPRNO. 1COMPRNO. 2OFM IFMPOWER EXHAUSTFAN MOTOR*ELECTRICHEATPOWER SUPPLYMin Max RLA

Page 14

Table 5 — Electrical Data — 50DK,DY024NOMINALV-PH-HZVOLTAGERANGECOMPRNO. 1COMPRNO. 2OFM IFMPOWER EXHAUSTFAN MOTOR*ELECTRICHEATPOWER SUPPLYMin Max RLA

Page 15 - Fig. 16) —

Table 6 — Electrical Data — 50DK,DY028NOMINALV-PH-HZVOLTAGERANGECOMPRNO. 1COMPRNO. 2OFM IFMPOWER EXHAUSTFAN MOTOR*ELECTRICHEATPOWER SUPPLYMin Max RLA

Page 16 - Field Electrical Connections

Table 7 — Electrical Data — 50DK,DY030NOMINALV-PH-HZVOLTAGERANGECOMPRNO. 1COMPRNO. 2OFM IFMPOWER EXHAUSTFAN MOTOR*ELECTRICHEATPOWER SUPPLYMin Max RLA

Page 17 - GND — Ground

LEGENDC—Compressor ContactorCB — Circuit BreakerCCB — Control Circuit BreakerCV — Constant VolumeDU — Dummy TerminalECON — EconomizerEQUIP — Equipment

Page 18

Fig. 19 — Field Control Thermostat Wiring,50DJ,DW CV UnitsSwitch 1 — Firestat or smoke detector — normally closed.Switch 2 — Building pressurization s

Page 19 - (208/230, 460 V Only)

CONTROL WIRING, VAV UNITS (DK,DY) — A switchor timeclock (field-supplied) must be wired in to control whenunit will go into and out of occupied mode. C

Page 20

NOTES:1. CB must trip amps are equal to or less than 140% FLA.2. If any of the original wire furnished must be replaced, it must be replacedwith type

Page 21

LEGENDHIR — Heating Interlock RelaySW — SwitchNOTES:1. SW1 — Field-supplied switch (or timeclock) used to move unit inand out of the occupied mode.2.

Page 22

LEGENDDPS — Differential Pressure SwitchECR — Economizer RelayHIR — Heating Interlock RelayIFC — Evaporator (Indoor) Fan ContactorMIR — Modulating Int

Page 23

NOTICE TO RIGGERSUNIT50WEIGHT A B CECONOMIZER(Without Hood)lb kg in. mm in. mm in. mm lb kgDJ,DK024 2440 1107 66.14 1680 49 1244.6 44 1117.6 130 59.1D

Page 24

The following options require 24-v connections. Refer toFig. 22 for terminal block locations and to unit label dia-grams for wiring details.Timeclock

Page 25 - 50DJ,DW CV Units

See Carrier Standard Service Techniques, Refrigerants sec-tion, for procedures to add or remove oil.If oil charge is above sight glass, do not remove

Page 26

Table 9A — Evaporator-Fan Pulley Data —Constant Volume Units (50DJ,DW) and Standard VAV Units (50DK,DY)UNIT 50FANRPMMOTOR PULLEY BLOWER PULLEY BELTSNo

Page 27

Table 9B — Evaporator-Fan Pulley Data —VAV Units with Inlet Guide Vane and Static Pressure Control OptionUNIT 50FANRPMMOTOR PULLEY BLOWER PULLEY BELTS

Page 28

Table 11 — Fan Performance — 50DJ Units and 50DK Units Without Inlet Guide VanesUNIT50DJ,DKAIRFLOW(Cfm)AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)0.2

Page 29

Table 12 — Fan Performance — 50DW Units and 50DY Units Without Inlet Guide VanesUNIT50DW,DYAIRFLOW(Cfm)AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)0.2

Page 30

Table 13 — Fan Performance — 50DK Units with Inlet Guide Vanes (cont)UNIT50DKAIRFLOW(Cfm)AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)0.2 0.4 0.6 0.8 1.

Page 31

Table 15 — Component Pressure Drops (in. wg)COMPONENTCFM6000 7000 8000 9000 10,000 11,000 12,000ECONOMIZERAll Units 0.18 0.20 0.25 0.28 0.32 0.36 0.40

Page 32

Table 16 — Configuration Header Jumper DescriptionJUMPER NO. FUNCTION SETTING MEANING1,2 Unit Type Mm VAV Rooftop3,4,5No. ofCompressorsmMMMmMmmM2 compr

Page 33

P4 (Demand Limit) — Usable only if demand limit is used.If demand limit is used, dip switch 5 must be in the ONposition. The valid range is 0 to 100%

Page 34

Table 1A — Physical Data, Constant Volume UnitsUNIT 50 DJ024 DW024 DJ028 DW028 DJ030 DW030OPERATING WEIGHT (lb)* 2440 2650 2900 3100 2930 3140COMPRESS

Page 35 - Bhp — Brake Horsepower

IMPORTANT: Once quick test is initiated, display but-ton must be pressed at least once every 10 minutes forcontrol to remain in quick test mode. If bu

Page 36

Table 18 — Quick Test, Thermistor and Potentiometer CheckQUICKTESTSTEP NO.NORMALDISPLAYDESCRIPTIONTHERMISTOR ORPOTENTIOMETER1.411 — Thermistor OK0 — T

Page 37

Table 20 — Sensor Resistance ValuesTEMP(F)RESISTANCE(Ohms)TEMP(F)RESISTANCE(Ohms)TEMP(F)RESISTANCE(Ohms)−60 362,640 45 11,396 150 1,020−55 297,140 50

Page 38 - Fig. 29 — Processor Board

Condenser fans are energized with compressor no. 1. Theno. 1 fan runs continuously while the unit is on mechanicalcooling; the no. 2 fan is cycled on

Page 39

With smoke purge mode, it is necessary to interrupt powerto unit control circuit as described above for building pres-surization.All switches and wiri

Page 40

EVAPORATOR-FAN MOTORS, PULLEYS, AND BELTS— Access to these components is through the 2 doors la-beled FAN SECTION on the left side of the unit (when f

Page 41

MODULATING POWER EXHAUST DIFFERENTIALPRESSURE SWITCH — The differential pressure switch islocated in the small control box mounted on the corner postn

Page 42 - Operating Sequences

FAN SHAFT BEARINGS — Lubricate fan shaft bearings atleast once a year with suitable bearing grease. Typical lu-bricants are given below:Manufacturer L

Page 43

CONDENSER FAN — To adjust condenser fans:1. Turn off unit power.2. Remove fan guard and loosen fan hub setscrew.3. See Fig. 28 and adjust fan height u

Page 44 - Service Access —

null span, turn null adjusting screw (Fig. 41) clockwise todecrease span and counterclockwise to increase span. Allswitches leave factory with null sp

Page 45

Table 1B — Physical Data, Variable Volume UnitsUNIT 50 DK024 DY024 DK028 DY028 DK030 DY030OPERATING WEIGHT (lb)* 2440 2650 2900 3100 2930 3140COMPRESS

Page 46 - Lubrication

Fig. 42 — Charging Chart; 50DJ,DK,DW,DY024;System 1Fig. 43 — Charging Chart; 50DJ,DK,DW,DY024;System 2Fig. 44 — Charging Chart; 50DJ,DK,DW,DY028;Syste

Page 47 - Adjustments

Refrigerant Feed Components — Each refrigerantcircuit (2 per unit) has all the necessary refrigerant controls:Thermostatic Expansion Valve (TXV) — Eac

Page 48

Table 21 — Pressure Switch Settings (psig)SWITCH CUTOUT CUT-INHigh 426 6 7 320 6 20Low 27 6 46767Control Circuit, 24 V — This control circuit is pro-t

Page 49 - SET POINT

Table 25 — Economizer Control Board Checkout,Test 3MOTORTESTPROCEDUREEXPECTED RESULTAND RESPONSEATurn mixed-air potenti-ometer to the midpointposition

Page 50

LEGENDC—ContactorMAT — Mixed-Air ThermistorPL — PlugRA — Return-AirSTAT — ThermostatNOTES:1. Relay contacts 1K and 2K are shown in high enthalpy posit

Page 51

4. Turn unit power off and disconnect plug P4 from thecontrol board.5. Turn unit power on and check for continuity acrossPin 6 and Pin 3 at plug P4 on

Page 52 - Economizer —

b. Connect the multimeter to read voltage betweenPin X at plug P1 and ground.c. Turn unit power on and check the multimeter. Withina few seconds the m

Page 53

d. Turn unit power off. Connect a fresh 1.5-v battery toterminals marked CLO2 as shown in Fig. 51.The negative (−Ve) pole of the battery must be con-n

Page 54

TROUBLESHOOTING, VAV UNITSVAV Diagnostic Information —The microproces-sor contains extensive self-diagnostic information. The dis-play board is used t

Page 55

CODES 59 AND 60: LOW-PRESSURE SWITCH — Thesecodes are used to indicate a low-pressure switch failure. Sincethe 50DK,DY024-030 units have low-pressure

Page 56

NOTES:1. Roof curb accessory 50DJ900391 is shippedunassembled.2. Dimensions in ( ) are millimeters.3. Roof curb: 18 gage steel.4. The 028 and 030 unit

Page 57

For both, the control uses only 80% of the total potenti-ometer resistance. If resistance of potentiometer is less than10% or greater than 90%, alarm

Page 58 - VAV Diagnostic Information —

4. Turn power switch to ON position and press display but-ton to enter quick test mode.5. Check voltage between TP20 and each of the followingtest pin

Page 59

RELAY BOARD CHECKOUTStep 1 — Low-voltage relay resistance check.1. Turn switch to OFF position.2. Remove plug connection from terminal strip J6.3. Set

Page 61

START-UP CHECKLISTMODEL NO.:DATE:SERIAL NO.:TECHNICIAN:PRE-START-UPM VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNITM REMOVE ALL SHIPPIN

Page 62 - PACKAGED SERVICE TRAINING

NOTES:1. Roof curb accessory 50DJ900401 is shippedunassembled.2. Dimensions in ( ) are millimeters.3. Roof curb: 18 gage steel.4. The 028 and 030 unit

Page 63

Alternate Unit Support Methods — Where the pre-ferred curb or slab mount cannot be used, support unit withsleepers on perimeter, using curb support ar

Page 64

UNIT50DJ,DKWEIGHT* A B C D E FLb Kg mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in.024 2440 1107 1244.6 4-1 1680.0 5-61⁄83141.0 10-311⁄165

Comments to this Manuals

No comments