50SZSINGLE-PACKAGEDHEAT PUMP UNITS2 to 5 Nominal TonsProduct Data Single-Packaged Heat Pump for Residential and Light Commercial Applications• Low Sou
1050SZ50SZ Corner weights ( In Pounds)I Determine cooling and heating requirements at design conditions:Given:Required Cooling Capacity (TC) . . . .
1150SZPerformance dataCOOLING EXTENDED PERFORMANCE TABLEHEATING EXTENDED PERFORMANCE TABLE -10–20HEATING EXTENDED PERFORMANCE TABLE 30–60See Legend an
1250SZPerformance data (cont)COOLING EXTENDED PERFORMANCE TABLEHEATING EXTENDED PERFORMANCE TABLE -10–20HEATING EXTENDED PERFORMANCE TABLE 30–60See Le
1350SZPerformance data (cont)COOLING EXTENDED PERFORMANCE TABLEHEATING EXTENDED PERFORMANCE TABLE -10–20HEATING EXTENDED PERFORMANCE TABLE 30–60See Le
1450SZPerformance data (cont)COOLING EXTENDED PERFORMANCE TABLEHEATING EXTENDED PERFORMANCE TABLE -10–20HEATING EXTENDED PERFORMANCE TABLE 30–60See Le
1550SZPerformance data (cont)COOLING EXTENDED PERFORMANCE TABLEHEATING EXTENDED PERFORMANCE TABLE -10–20HEATING EXTENDED PERFORMANCE TABLE 30–60See Le
1650SZPerformance data (cont)COOLING EXTENDED PERFORMANCE TABLEHEATING EXTENDED PERFORMANCE TABLE -10–20HEATING EXTENDED PERFORMANCE TABLE 30–60See Le
1850SZPerformance data (cont)ECONOMIZER 1-in. FILTER PRESSURE DROP (in. wg)MULTIPLICATION FACTORSExample: 20 kW (at 240v) heater on 230v= 20.0 (.92 mu
1950SZWET COIL AIR DELIVERY UNIT 50SZ024-060**Air delivery values are based on operating voltage of 230 v, wet coil, without filter or electric heater
250SZ ambient kit is available as a field-installed accessory and does not require a special motor. Corporate thermostats work with Carrier’s small p
2050SZINDOORTHERMOSTATDISCONNECTPER NECFROMPOWERSOURCERETURNAIRTOP COVERTypical piping and wiring
2150SZCondensate trap — A 2-in. condensate trap must be fieldsupplied.Ductwork — Secure downflow discharge ductwork to roofcurb. For horizontal discharg
2250SZElectrical Data*Heater capacity (kW) based on heater voltage of 208v, 240v, & 480v. If power distribution voltage to unit varies from rated
2350SZElectrical Data Legend452=5v457=7v455=2vLEGENDFLA — Full Load AmpsLRA — Locked Rotor AmpsMCA — Minimum Circuit AmpsMOCP — Maximum Overcurrent Pr
2450SZ
2550SZSequence of operationWhen power is supplied to unit, the transformer (TRAN) isenergized.On units with crankcase heater, heater is also energized
2650SZPackaged Heat PumpsConstant Volume ApplicationHVAC Guide SpecificationsSize Range: 2 to 5 Tons, Nominal CoolingCarrier Model Number: 50SZPart 1—
2750SZ2. All fan motors shall have permanently lubricatedbearings, and inherent, automatic reset, thermaloverload protection.3. Condenser fan motor sh
Copyright 2005 Carrier Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 Printed in U.S.A. edition date: 01/06Manufacturer reserves the right to cha
350SZ Model number nomenclatureARI* capacities COOLING CAPACITIES AND EFFICIENCIES 50SZ 024Model No. 50SZ – Single Packaged Heat Pump Nomi
450SZ OUTDOOR SOUND: OCTAVE BAND DATA—DECIBELS Physical data * Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg. UNIT 50S
550SZ Factory-installed optionsLouvered grille provides hail and vandalism protection. A wire grille is standard on all models. See model number nom
650SZECONOMIZERFILTER RACK MANUAL OUTSIDE AIR DAMPERDAMPERBLADEMANUAL OUTSIDEAIR HOODREPLACEMENTPANEL
750SZBase unit dimensions—50SZ024-030REQUIRED CLEARANCE FOR OPERATION AND SERVICINGINCHES [mm]EVAP. COIL ACCESS SIDE...
850SZBase unit dimensions—50SZ036-060REQUIRED CLEARANCE FOR OPERATION AND SERVICINGINCHES [mEVAP. COIL ACCESS SIDE...
950SZAccessory dimensionsNOTES:1. Roof curb must be set up for unit being installed.2. Seal strip must be applied, as required, to unit being installe