The Ideal Complement to Your
Ducted System When It Is Impracti-
cal or Prohibitively Expensive to
Use Ductwork
choice of 3 compact, attractive fan
coil types for ultimate flexibility in
any room decor
wide range of accessories avail-
able to meet a variety of installa-
tion requirements
Features/Benefits
An inexpensive and creative
solution to design problems
Carrier’s cooling only duct-free split
systems are a matched combination of
an outdoor condensing unit and one
of 3 decorative indoor fan coil units
connected only by refrigerant tub-
ing and wires. One of the 3 fan coil
choices will fit any application you
might encounter.
The fan coils can be mounted on
the wall, at the ceiling, or in the ceil-
ing. This selection of fan coils permits
inexpensive and creative solutions to
design problems such as:
add-ons to current space (an office
or family room addition)
special space requirements (a com-
puter room)
when changes in the cooling load
cannot be handled by the existing
system (when adding heat-generating
equipment to a currently condi-
tioned space)
when adding air conditioning to
spaces that are heated by hydronic
or electric heat and have no
ductwork
historical renovations or any appli-
cation where preserving the looks
of the original structure is essential
40QNB
40QAB
COOLING
38HDC
40QKB
Product
Data
53QAB/53QKB/53QNB
Duct-Free Cooling Only
Split Systems
3
4
to 5 Nominal Tons
Copyright 1997 Carrier Corporation Form 53-3PD
Page view 0
1 2 ... 68

Summary of Contents

Page 1 - Features/Benefits

The Ideal Complement to YourDucted System When It Is Impracti-cal or Prohibitively Expensive toUse Ductwork• choice of 3 compact, attractive fancoil t

Page 2 - Table of contents

Accessories (field installed) (cont)Condensing unitsLow-ambient kit includes a solid-state head pressure con-troller designed to control condenser fan

Page 3 - Features/Benefits (cont)

Physical data — 38AN condensing units*UNIT 38AN 009 012NOMINAL CAPACITY (Tons)3⁄41OPERATING WEIGHT (lb) 55 62REFRIGERANT TYPE R-22Control (Cooling) Ca

Page 4

Physical data — 38HDC condensing unitsUNIT 38HDC 018 024 030 036NOMINAL CAPACITY (Tons) 11⁄2221⁄23OPERATING WEIGHT (lb) 150 154 169 179REFRIGERANT TYP

Page 5 - Model number nomenclature

UNIT 38HDC 048 060NOMINAL CAPACITY (Tons) 45OPERATING WEIGHT (lb) 270 290REFRIGERANT TYPE R-22Control (Cooling) AccuRaterT Piston at Fan Coil UnitFact

Page 6 - ARI* capacities

Physical data — high wall unitsUNIT 40QNB 009* 012*NOMINAL CAPACITY (Tons)3⁄41NOMINAL SIZE (Btuh) 9000 12,000OPERATING WEIGHT (lb) 18.7 24.2MOISTURE R

Page 7 - Accessories (field installed)

UNIT 40QNB 018* 024*NOMINAL CAPACITY (Tons) 11⁄22NOMINAL SIZE (Btuh) 18,000 24,000OPERATING WEIGHT (lb) 38.5 42.9MOISTURE REMOVAL RATE (Pints/Hr) 5.6

Page 8 - FRESH AIR INTAKE KIT

Physical data — ceiling-suspended unitsUNIT 40QAB 018* 024 036 048 060NOMINAL CAPACITY (Tons) 11⁄223 4 5NOMINAL SIZE (Btuh) 18,000 24,000 36,000 36,00

Page 9 - POWER VENTILATION KIT

Physical data — in-ceiling cassette unitsUNIT 40QKB 024 036NOMINAL CAPACITY (Tons) 11⁄23NOMINAL SIZE (Btuh) 18,000 36,000OPERATING WEIGHT (lb) 61.6 10

Page 10 - Fan coils

Base unit dimensions —38AN009,012 outdoor units1. Dimensions in [ ] are in millimeters.2. Direction of airflow.3. Center of Gravity.4. Minimum clearanc

Page 11

Base unit dimensions —38HDC condensing unitsUNIT38HDCABCDEFGHJKLMNRSOPERATINGWTft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm f

Page 12

These compact indoor fan coil unitstake up very little space in the roomand do not obstruct windows. The fancoils are attractively styled to blendwith

Page 13

Base unit dimensions —40QNB009,012 high wall fan coil units1. Dimensions are in inches. Dimensions in [ ] are in millimeters.2. Direction of airflow.3.

Page 14

Base unit dimensions —40QNB018,024 high wall fan coil units1. Dimensions in ( ) are in millimeters.2. Direction of airflow.3. Refrigerant, drain, and p

Page 15

Base unit dimensions —40QAB ceiling-suspended fan coil unitsNOTES:1. Dimensions in [ ] are millimeters.2. Direction of airflow.3. Facing unit discharge

Page 16

Base unit dimensions —40QKB in-ceiling cassette fan coil unitsUNIT 40QKBOPERATING WEIGHTLb Kg024 61.6 28NOTES:1. indicates airflow.2. Dimensions in. [

Page 17

Base unit dimensions —40QKB in-ceiling cassette fan coil units (cont)UNIT40QKBOPERATING WEIGHTLb Kg036 105.8 48NOTES:1. Indicates airflow.2. Dimensions

Page 18 - Base unit dimensions —

Selection procedure (with example)I Determine the type of fan coil which best suitsthe application (refer to Systems Index table onpage 26).Duct-free

Page 19 - 38HDC condensing units

Performance dataSYSTEMS INDEX TABLESYSTEM MODEL NO. FAN COIL TYPE INDOOR SECTION OUTDOOR SECTION NET COOLING (Btuh)* INDEX NO.53QNB009 High Wall 40QNB

Page 20

COOLING CAPACITIESSYSTEM 1* — 53QNB009 HIGH WALL SYSTEM (38AN009 WITH 40QNB009)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/BF184/0

Page 21

Performance data (cont)COOLING CAPACITIES (cont)SYSTEM 2* — 53QNB012 HIGH WALL SYSTEM (38AN012 WITH 40QNB012)Temp (F)Air EnteringCondenser(Edb)Air Ent

Page 22

COOLING CAPACITIES (cont)SYSTEM 3* — 53QNB018 HIGH WALL SYSTEM (38HDC018 WITH 40QNB018)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm

Page 23

Features/Benefits (cont)The totally-enclosed condenser-fanmotor means greater reliability un-der rain conditions, ensuring depend-able performance for

Page 24

Performance data (cont)COOLING CAPACITIES (cont)SYSTEM 4* — 53QNB024 HIGH WALL SYSTEM (38HDC024 WITH 40QNB024)Temp (F)Air EnteringCondenser(Edb)Air En

Page 25

COOLING CAPACITIES (cont)SYSTEM 5* — 53QAB018 CEILING-SUSPENDED SYSTEM (38HDC018 WITH 40QAB024†)Temp (F)Air EnteringCondenser(Edb)Air Entering Evapora

Page 26 - Performance data

Performance data (cont)COOLING CAPACITIES (cont)SYSTEM 6* — 53QAB024 CEILING-SUSPENDED SYSTEM (38HDC024 WITH 40QAB024)Temp (F)Air EnteringCondenser(Ed

Page 27 - COOLING CAPACITIES

COOLING CAPACITIES (cont)SYSTEM 7* — 53QAB030 CEILING-SUSPENDED SYSTEM (38HDC030 WITH 40QAB036)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporat

Page 28 - Performance data (cont)

Performance data (cont)COOLING CAPACITIES (cont)SYSTEM 8* — 53QAB036 CEILING-SUSPENDED SYSTEM (38HDC036 WITH 40QAB036)Temp (F)Air EnteringCondenser(Ed

Page 29 - COOLING CAPACITIES (cont)

COOLING CAPACITIES (cont)SYSTEM 9* — 53QAB048 CEILING-SUSPENDED SYSTEM (38HDC048 WITH 40QAB048)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporat

Page 30

Performance data (cont)COOLING CAPACITIES (cont)SYSTEM 10* — 53QAB060 CEILING-SUSPENDED SYSTEM (38HDC060 WITH 40QAB060)Temp (F)Air EnteringCondenser(E

Page 31

COOLING CAPACITIES (cont)SYSTEM 11* — 53QKB018 IN-CEILING CASSETTE SYSTEM (38HDC018 WITH 40QKB024)Temp (F)Air EnteringCondenser(Edb)Air Entering Evapo

Page 32

Performance data (cont)COOLING CAPACITIES (cont)SYSTEM 12* — 53QKB024 IN-CEILING CASSETTE SYSTEM (38HDC024 WITH 40QKB036)Temp (F)Air EnteringCondenser

Page 33

COOLING CAPACITIES (cont)SYSTEM 13* — 53QKB030 IN-CEILING CASSETTE SYSTEM (38HDC030 WITH 40QKB036)Temp (F)Air EnteringCondenser(Edb)Air Entering Evapo

Page 34

Features/Benefits (cont)HIGH WALL FAN COILS —40QNB (3⁄4- 2 Tons)High walls are the most cost-effective duct-free split systems. They can be usedfor sim

Page 35

Performance data (cont)COOLING CAPACITIES (cont)SYSTEM 14* — 53QKB036 IN-CEILING CASSETTE SYSTEM (38HDC036 WITH 40QKB036)Temp (F)Air EnteringCondenser

Page 36

Electrical data38HDC CONDENSING UNITSUNITSIZE38HDCV-PH-HzOPERATINGVOLTAGEMINIMUM*OPERATINGVOLTAGEMAXIMUM*COMPRLACOMPFLAFANFLAPOWERMCA MOCP FLA018208/2

Page 37

Typical piping and wiring —high wall systems, 9,000 and 12,000 BtuhLEGENDNEC — National Electrical Code*Standard.†Field supplied.NOTES:1. All piping m

Page 38

Typical piping and wiring —high-wall systems, 18,000 and 24,000 BtuhLEGENDNEC — National Electrical CodePipingLine Voltage24 VThermistor*Standard.†Fie

Page 39

Typical piping and wiring —ceiling-suspended systemsLEGENDf — PhaseNEC — National Electrical CodePipingLine Voltage24 VThermistor*Standard.†Accessory

Page 40

Typical piping and wiring —in-ceiling cassette systemsLEGENDf — PhaseNEC — National Electrical CodePipingLine Voltage24 V*Standard.†Accessory item.**F

Page 41 - Electrical data

Application dataUnit selectionSelect equipment to either match or be slightly less thananticipated peak load. This provides better humidity con-trol,

Page 42 - Typical piping and wiring —

FAN COIL UNITSCONDITION 40QNB 40QAB 40QKBMaximum RoomTemperature (F)84 84 95Minimum RoomTemperature (F)64 64 55Maximum Return Air (F)Dry-Bulb 85 85 85

Page 43

Application data (cont)Long-lines applications, 38HDC units:1. Liquid lines on all 38HDC units should be3⁄8in. only.DO NOT resize liquid lines for add

Page 44

FITTING LOSS IN EQUIVALENT FT FOR ELBOWSTUBE SIZEO.D. (in.)90-DEGREESHORTRADIUS90-DEGREELONGRADIUS45-DEGREESHORTRADIUS5⁄81.6 1.0 0.83⁄41.8 1.2 0.97⁄82

Page 45

Model number nomenclature53 SERIES COOLING ONLY DUCT-FREE SPLIT SYSTEMS38 SERIES COOLING ONLY CONDENSING UNITS40 SERIES COOLING ONLY FAN COILS*System

Page 46 - Application data

Application data (cont)CHANGE IN INDOOR UNIT PISTON SIZEFOR ELEVATIONOUTDOOR UNIT ABOVE INDOOR UNITFt Piston Change0-25 026-50 -351-75 -576-100 -7101-

Page 47 - Refrigerant lines

ControlsWired 24 v controls (40QAB, 40QKB)1. A 24-v thermostat is supplied for operation of all in-ceiling and cassette systems.2. Controller can only

Page 48 - Application data (cont)

Application data (cont)Sound dataCONDENSING UNIT SOUND RATINGSUNIT SOUND RATING (Decibels) FREE FIELD dBA*38AN009 65 55.738AN012 65 55.738HDC018 70 59

Page 49 - EFFECTIVE CAPACITY LOSS

SOUND POWER DATA OCTAVE BANDS — A WEIGHTEDUNITFANSPEEDOCTAVE BAND DATA (dBA)125 250 500 1000 2000 4000 800038AN009 H 48.9 54.9 58.3 59.1 54.9 49.1 39.

Page 50

Typical wiring schematic,53QNB009,012 systems (012 shown)See Legend and Notes on page 56.54

Page 51 - Fresh air/ducting

Typical wiring schematic,53QNB018,024 systemsRELAY CHARTCOMPRESSOR K13THERMISTOR EQUIVALENCETEMPERATURE RESISTANCE°F °C V95 35 6,50072 22 11,40032 0 3

Page 52

Typical wiring schematics (cont)LEGEND AND NOTES FOR TYPICAL WIRING SCHEMATICS, 53QNBAGING — For Burn-In Test(short terminals)AS — AssemblyC—Contactor

Page 53

Typical wiring schematic — 53QAB systemLEGENDASM — Air Sweep MotorASR — Air Sweep RelayASW — Air Sweep SwitchC—ContactorCAP — CapacitorCLO — Compresso

Page 54 - Typical wiring schematic

Typical wiring schematic — 53QKB systemLEGENDC—ContactorCAP — CapacitorCLO — Compressor LockoutCOMP — CompressorCR — Control RelayCT — Current Transfo

Page 55 - 53QNB018,024 systems

Controls — systems using high-wallfan coils (53QNB)Control system — The 40QNB unit is equipped with amicroprocessorcontrol which operates the system.

Page 56

Model number nomenclature (cont)ARI* capacitiesSYSTEMMODEL NO.(includesvoltagedesignation)†FAN COIL TYPEINDOORSECTION(includesvoltagedesignation)OUTDO

Page 57

Controls — systems using high-wallfan coils (53QNB) (cont)2. If the room temperature is below the selected tempera-ture, the unit operates for 8 minut

Page 58

Controls — systems using ceiling-suspended(53QAB) or cassette (53QKB) fan coilsOperating mode memoryAfter the system is turned off or after a power fa

Page 59 - WIRELESS CONTROLLER

Guide specifications — outdoor unitsCommercial Condensing UnitsHVAC Guide SpecificationsSize Range:3⁄4to 5 Tons Cooling CapacityCarrier Model Number: 38

Page 60

G. Controls and Safeties:Operating controls and safeties shall be factory se-lected, assembled, and tested. The minimum controlfunctions shall include

Page 61 - Operating sequence

Guide specifications — high-wall unitsCommercial High-Wall Fan Coil UnitsHVAC Guide SpecificationsSize Range:3⁄4to 2 Tons Cooling CapacityCarrier Model

Page 62 - Commercial Condensing Units

G. Filters:Unit shall have filter track with factory-supplied clean-able filters.H. Electrical Requirements:Unit shall operate on 115 v (009), 208-v (01

Page 63

Guide specifications —40QAB ceiling-suspended unitsCommercial Ceiling-Suspended Fan CoilsHVAC Guide SpecificationsSize Range: 11⁄2to 5 Tons Cooling Capa

Page 64 - HVAC Guide Specifications

J. Special Features (Field Installed):Certain features are not applicable when the featuresdesignated by * are specified. For assistance in amend-ing t

Page 65

Guide specifications —40QKB in-ceiling cassette unitsCommercial In-Ceiling Cassette Fan CoilHVAC Guide SpecificationsSize Range: 11⁄2to 3 Tons Cooling C

Page 66 - 40QAB ceiling-suspended units

Accessories (field installed)STANDARD FEATURES AND FIELD-INSTALLED ACCESSORIESSTANDARD FEATURE/FIELD-INSTALLEDACCESSORY53QNB(High Wall)53QAB(Ceiling Su

Page 67

Accessories (field installed) (cont)See Standard Features and Field-Installed Accessories table on page 7 for information on system featuresand accesso

Page 68

CHARCOAL FILTER KITCOLLECTORACTIVECARBONFILTERThe charcoal (carbon) filter kit is available for duct-free high wall fancoil units. This accessory impro