30RA/RY - 30RH/RYH Series
PRO-DIALOG
Control
Operation and maintenance instructions
AQUASNAP
Page view 0
1 2 3 4 5 6 ... 35 36

Summary of Contents

Page 1 - Control

30RA/RY - 30RH/RYH SeriesPRO-DIALOG ControlOperation and maintenance instructionsAQUASNAP

Page 2

10CHANGING THE OPERATING TYPEBUTTON ACTIONContinually press the operating typeselection button for more than 4 seconds.Hold down the Start/Stop button

Page 3

114.3 - Menus4.3.1 - Selecting a menuThe MENU button authorises you to select a menu from the 10main menus that are available. Each time you press thi

Page 4

120011 6.01 6.01 5.91 5.81 5.71 5.7MODIFYING THE VALUE OF A PARAMETEROPERATION PRESS BUTTON MENU LED ITEM NUMBER ITEM VALUE2-DIGIT DISPLAY 4-DIGIT DIS

Page 5

13STATUS TEMPERATURES PRESSURES SETPOINTS INPUTS OUTPUTS CONFIGURATION ALARMS ALARMS HISTORYALARMSUSER[USEr]SERVICE[SErviCE]FACTORY[FACtorY]RUNTIME 1[

Page 6

14MENUMenu tree structureLegend* Displayed if the configuration requires it** Displayed if the alarm exists- Not in useITEM012345678910111213141516STA

Page 7

15INFORMATION MENU (3)ITEM FORMAT UNITS0±nn.n °CLOFF -L-On -L-Sc -CCn -rEM -MASt -OFF -rEADY -dELAY -StOPPing -running -triPout -OvErridE -dEFrOSt -OC

Page 8

16DESCRIPTIONThe delay at start-up operates after the unit has been switched on. If the delay has not expired, the mode is active.The delay is configu

Page 9 - MENU BLOCK

17SETPOINTS MENU [2]ITEM FORMAT UNITS RANGE0 ±nn.n °C See table below1 ±nn.n °C See table below2 nnn °C See table below3 [1] nnn °C See table below4 [

Page 10

18INPUTS MENU [2]ITEM FORMAT UNITS0 oPEn/CLoS -1 [1] oPEn/CLoS -2 oPEn/CLoS -3 oPEn/CLoS -4 [1] oPEn/CLoS -5 [1] oPEn/CLoS -6 [1] oPEn/CLoS -7 oPEn/CL

Page 11

194.3.10 - Description of the Outputs/Tests menu4.3.10.1 - GeneralThis menu displays the status of the controller outputs. Moreo-ver, when the machine

Page 12

2TABLE OF CONTENTS1 - SAFETY CONSIDERATIONS...

Page 13 - MENU STRUCTURE

20OUTPUTS STATUS & TESTS MENU [2] [3] continuedITEM FORMAT UNITS11 [1] nnntESt %12 [1] nnntESt %13 [1] b1b2tESt14 [1] b1b2b3b4tESt15 [1] YES -no -

Page 14 - Menu tree structure

21The table below describes the different sequences of theautomatic test.TEST NUMBER012345, 67, 8, 910, 1112, 13, 1415, 16, 171819, 20, 21222324252627

Page 15

22The table below describes the faults that can be displayedduring the automatic test.TEST FAULT1234567891011, 12, 13; 14, 1516, 17, 18, 19, 202122, 2

Page 16

23SUB-MENU USER CONFIGURATION* only displayed if configuration requires.NOTE: The items in brackets show what is displayed on theuser interface.SCHED

Page 17

244.3.11.3 - Description of the User 1 Configuration sub-menu1 This item shall be masked when not used.2 Access to menu is read/write.USER 1 CONFIGURA

Page 18

254.3.11.4 - Description of the User 2 Configuration sub-menuThis menu is only accessible if the unit is equipped with anoptional CCN/clock board4.3.1

Page 19

26PERIOD X CONFIGURATION SUB-MENUS (X = 1 TO 8)ITEM # FORMAT COMMENTS0 Period X Menu Indicates the period (X) you are going to configure.When selected

Page 20

27BROADCAST CONFIGURATION SUB-MENUITEM # FORMAT COMMENTS0 broAdCASt MEnu When selected this item authorises a return to the main menu.1 YES/no Determi

Page 21

28ITEM #0 [1]1 [1]2 [1]3 [1]4 [1]5 [1]FORMAT X ALArMrESEt ALArM1 to 551 to 551 to 551 to 551 to 55COMMENTSX alarms are activeReset of alarms is reques

Page 22

295 - PRO-DIALOG PLUS CONTROL OPERATION5.1 - Start/stop controlThe table below summarises the unit control type and stop orgo status with regard to th

Page 23 - CONFIGURATION

3GENERAL LEGENDEach of the following drawings is replaced in the whole document by the corresponding explanation:Start/stop buttonReturn keyDown arrow

Page 24

30CHIL_S_S------Disable----Disable------Enable----EnableREMOTESTART/STOPCONTACT----Off----Off-----On coolingOn heatingOn auto--On coolingOn heatingOn

Page 25

315.3 - Evaporator water pump controlThe unit can control one or two evaporator water pumps. Theevaporator water pump is turned on when this option is

Page 26

32The following table summarises the possible selectionsdepending on the control types (local, remote or CCN) and thefollowing parameters:- Setpoint s

Page 27

335.6.2 - ResetReset means that the active setpoint is modified so that lessmachine capacity is required (in cooling mode, the setpoint isincreased, i

Page 28

345.11 - Defrost functionDefrost is activated, when the unit is in heating mode, in orderto reduce frost build-up on the air heat exchanger. The defro

Page 29

35ALARMCODE123567910111213141516171821222324ALARM NAMECompressor A1 failureCompressor A2 failureCompressor A3 failureCompressor B1 failureCompressor B

Page 30 - HEATING STANDBY COOLING

Order No. 13048-76, 07.2000. Supersedes order No. 13048-76, 01.2000 Manufactured by: Carrier s.a., Montluel, France.Manufacturer reserves the right to

Page 31

41 - SAFETY CONSIDERATIONS1.1 - GeneralInstallation, start-up and servicing of equipment can behazardous if certain factors particular to the installa

Page 32

53 - HARDWARE DESCRIPTION3.1 - GeneralFigure 13.2 - Electrical supply to boardsAll boards, except the PD-RCPM board, are supplied from acommon 24 V a.

Page 33 - % Building load

63.6 - Connections at the user's terminal block3.6.1 - General descriptionThe contacts below are available at the user's terminal block onth

Page 34

7DescriptionAlarm relay outputcircuit AAlarm relay outputcircuit BBoiler relay outputContact 1:start/stop/heat/coolContact 2:start/stop/heat/coolConta

Page 35 - ALARM CODE DESCRIPTIONS

83.6.2 - Volt-free contact on/off/cooling/heating withoutmultiplexingIf the automatic heating/cooling changeover function is notselected (see sections

Page 36

9MAIN INTERFACEBUTTON NAME DESCRIPTIONMenu Permits the selection of a main menu. Each main menu is represented by an icon. The icon is lit if active.U