Carrier AQUAZONE RDS006-060 User Manual

Browse online or download User Manual for Heat pumps Carrier AQUAZONE RDS006-060. Carrier AQUAZONE RDS006-060 Product data

  • Download
  • Add to my manuals
  • Print
  • Page
    / 40
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Copyright 2004 Carrier Corporation Form 50RHE-C1PD
Single-Package Horizontally Mounted
Water Source Heat Pumps with Elec-
tronic Controls.
High efficiency design with
environmentally friendly HFC-407C
refrigerant
Performance rated in accordance
with ISO 13256-1
Wide application use with an
operating temperature range of
6.7Cto43.3C
Thermostatic expansion valve
(TXV) provides efficient and reliable
refrigerant flow
Available mute package for extra-
quiet operation
Three service panels for
compressor section for easy
maintenance
Spring-mounted compressors for
quiet operation
Ease of installation with factory
mounted flow regulators and control
valves
Flexible and reliable controls
accommodate all systems
Features/Benefits
Carrier’s Aquazone high
efficiency water source heat
pumps are a flexible
alternative for all boiler/tower
and geothermal design
applications
Operating efficiency
Carrier horizontal water source heat
pumps are designed for quality and
high performance over a lifetime of
operation. Aquazone high efficiency
units offer cooling COP to 4.6 and
heating COPs to 4.7. Efficiencies
stated are in accordance with standard
conditions under ISO (International
Organization for Standardization)
Standard 13256-1 and provide among
the highest ratings in the industry.
Aquazone
50RHE006-060
Water Source Heat Pumps
Horizontal Unit
50 Hz, CE Mark
R-407C
1.5to13.7NominalkW(Cooling)
1.8 to 16. 8 Nominal kW (Heating)
Product
Data
TM
Page view 0
1 2 ... 40

Summary of Contents

Page 1 - Features/Benefits

Copyright 2004 Carrier Corporation Form 50RHE-C1PDSingle-Package Horizontally MountedWater Source Heat Pumps with Elec-tronic Controls.• High efficien

Page 2 - Table of contents

1050RHE00681 L/S NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissible, extrapolation is not.2. All entering air conditions are 27 C db (dry bul

Page 3 - Features/Benefits (cont)

1150RHE009113 L/S NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissible, extrapolation is not.2. All entering air conditions are 27 C db (dry bu

Page 4 - Model number nomenclature

1250RHE012140 L/S NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissible, extrapolation is not.2. All entering air conditions are 27 C db (dry bu

Page 5 - ISO* 13256-1 capacity ratings

1350RHE015212 L/S NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissible, extrapolation is not.2. All entering air conditions are 27 C db (dry bu

Page 6 - Options and accessories

1450RHE019264 L/S NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissible, extrapolation is not.2. All entering air conditions are 27 C db (dry bu

Page 7 - Physical data

1550RHE024307 L/S NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissible, extrapolation is not.2. All entering air conditions are 27 C db (dry bu

Page 8 - Unit Hanger Detail

1650RHE030349 L/S NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissible, extrapolation is not.2. All entering air conditions are 27 C db (dry bu

Page 9

1750RHE036431 L/S NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissible, extrapolation is not.2. All entering air conditions are 27 C db (dry bu

Page 10 - Performance data

1850RHE042530 L/S NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissible, extrapolation is not.2. All entering air conditions are 27 C db (dry bu

Page 11 - 50RHE009

1950RHE048630 L/S NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissible, extrapolation is not.2. All entering air conditions are 27 C db (dry bu

Page 12 - Performance data (cont)

2High quality construction and testingAll units are manufactured to meet ex-tensive quality control protocol from start to finish through an automated

Page 13 - 50RHE015

2050RHE060790 L/S NOMINAL AIRFLOWLEGEND NOTES:1. Interpolation is permissible, extrapolation is not.2. All entering air conditions are 27 C db (dry bu

Page 14

21CORRECTION FACTORS — AIRFLOW — 50RHE UNITSCORRECTION FACTORS — ENTERING AIR — 50RHE UNITSLEGEND*Sensible capacity equals total capacity.% OFNOMINALA

Page 15 - 50RHE024

2250RHE BLOWER PERFORMANCELEGEND NOTES:1. Units factory shipped on medium speed. Other speeds requirefield selection.2. For dual voltage units, airflo

Page 16

2350RHE UNITSRADIATED SOUND POWER DATANOTES:1. Data based on sound measurements made in a reverberant room on represen-tative units from each cabinet

Page 17 - 50RHE036

2450RHE UNITS WITH MUTE PACKAGE OPTIONRADIATED SOUND POWER DATANOTES:1. Data based on sound measurements made in a reverberant room onrepresentative u

Page 18

2550RHE UNITS WITH MUTE PACKAGE OPTION (cont)RADIATED SOUND POWER DATA (cont)NOTES:1. Data based on sound measurements made in a reverberant room onre

Page 19 - 50RHE048

26LEGEND50RHEUNITVOLTS-PHASE(50 Hz)VOLTAGEMIN/MAXCOMPRESSOR FANMOTORFLATOTALUNITFLAMINCIRCUITAMPMAXFUSE/HACRRLA LRA006 220/240-1 197/254 2.3 15.0 0.4

Page 20

27Typical piping and wiringThermostatWiringWater InWater OutBall Valve with optionalintegral P/T plug (typical for supply andreturn piping)Unit PowerD

Page 21

28Typical wiring schematicsRED BLUL(3)M(2)H(1)POWER SUPPLYREFER TODATA PLATEUSE COPPERCONDUCTORSONLYEARTH (GRD)N (NEUTRAL)LRED220VORG240VBLKYELBLU24VS

Page 22

29(CAP-TUBEUNITS) ORLUGT3T2T1CCPBBR1BR2TRANSCOMPONENT LOCATIONCXMSEE NOTE 5TYPICALT- STATYOGRCLCOMPR.COOLINGFAN24VACLOW TEMPALARMSEE NOTE 6 FORDRY ALA

Page 23 - 50RHE UNITS

3 All components are carefully de-signed and selected for endurance, durability, and carefree day-to-dayoperation. The Aquazone™ unit is shipped t

Page 24

30Typical wiring schematics (cont)FAN ENABLERELAYPOWER SUPPLYREFER TODATA PLATEUSE COPPERCONDUCTORSONLYSEE NOTE 8EARTH (GRD)N (NEUTRAL)L123456G/YG/YYE

Page 25

31POWER SUPPLYREFER TODATA PLATEUSE COPPERCONDUCTORSONLYEARTH (GND)N (NEUTRAL)L3L2L1CBYEL24VRED(220V)BLKBLKG/YBLKBLKBLKBLKORG(240V)YEL ORWHTBRNYELBLKB

Page 26 - Electrical data

32Water loop systemWater loop (or boiler/tower) system applications typicallyinclude a number of units plumbed to a common pipingsystem. For optimal p

Page 27 - UNIT HANGER ISOLATION DETAIL

33Trapping — Condensate trapping is essential on everywater source heat pump unit. A trap is provided to preventthe backflow of moisture from the cond

Page 28 - (SINGLE-PHASE UNITS)

34OCTAVE BAND SOUND PRESSURE LEVEL (Lp) ASSOCIATED WITH NC CURVESWSHP sound controlThe analysis of the projected sound level in the conditionedspace c

Page 29 - (3-PHASE UNITS)

35R-407CPackaged Water Source Heat PumpsHVAC Guide SpecificationsSize Range: 1.5 to 13.7 kWCooling Capacity1.8 to 16.8 kWHeating CapacityCarrier Unit:

Page 30 - N (NEUTRAL)

36D. Refrigerant Components:1. Units shall have a sealed refrigerant circuitincluding a high efficient scroll, rotary or recip-rocating compressor des

Page 31

373. Unit Controls:a. Safety controls including a high-pressureswitch, a low-pressure sensor, and a lowwater and low air temperature sensor.Access fit

Page 32 - Application data

38d. Programmable 5-Day Thermostat offers2 stage heat, 2 stage cool, auto changeover,5-minute built-in compressor protection, lock-ing cover included.

Page 34 - Application data (cont)

4Model number nomenclatureAirflow Configuration*Normal Static, All SizesCode Return DischargeS Left RightE Left BackZ Right LeftB Right Back50RHE006SF

Page 35 - Guide specifications

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Pg 4

Page 36 - Guide specifications (cont)

550RHE WATER LOOP APPLICATIONSLEGENDNOTES:1. A water-to-air heat pump using water or brine circulating in a common pipingloop functioning as a heat so

Page 37

6Factory-installed optionsCupronickel heat exchangers are available for highercorrosion protection for applications such as open tower,geothermal, etc

Page 38

7Physical dataAQUAZONE 50RHE006-060 UNITSLEGENDPSC — Permanent Split CapacitorNOTES:1. All units have spring compressor mountings, TXV (thermostatic e

Page 39

8DimensionsRight Return Left DischargeFrontNPBlowerOutletMOLegendCAP=Control Access PanelCSP=Compressor Service PanelBSP=Blower Service PanelASP=Alter

Page 40 - Tab 5a 5 a

9I Determine the actual cooling and heatingloads at the desired dry bulb and wet bulbconditions.Assume cooling load at desired dry bulb 27 C andwet bu