50RHR,50RVR WATER LOOP APPLICATIONS
LEGEND
NOTES:
1. A water-to-air heat pump using water or brine circulating in a common piping
loop functioning as a heat source/heat sink.
2. The temperature of the water or brine loop is usually mechanically controlled
within a temperature range of 60 F to 90 F.
3. Certified in accordance with the ARI/ISO Standard 13256-1 Certification
Program, which replaces ARI Standard-320.
4. Size 006 available as RHR model only.
50RHR,50RVR GROUND LOOP APPLICATIONS
LEGEND
NOTES:
1. A brine-to-air heat pump using a brine solution circulating through a subsur-
face piping loop functioning as a heat source/heat sink.
2. The heat exchange loop may be placed in horizontal trenches or vertical
bores, or be submerged in a body of surface water.
3. The temperature of the brine is related to the climatic conditions and may
vary from 20 F to 110 F.
4. Certified in accordance with the ARI/ISO Standard 13256-1 Certification
Program, which replaces ARI Standard-330.
5. Size 006 available as RHR only.
50RHR,50RVR GROUND WATER APPLICATIONS
LEGEND
NOTES:
1. A water-to-air heat pump using water pumped from a well, lake or stream
functioning as a heat source/heat sink.
2. The temperature of the water is related to the climatic conditions and may
vary from 40 F to 80 F.
3. Certified in accordance with the ARI/ISO Standard 13256-1 Certification
Program, which replaces ARI Standard-325.
4. Size 006 available as RHR only.
ARI/ISO capacity notes
1. Cooling capacities based upon 80.6 F DB (dry bulb),
66.2 F WB (wet bulb) entering-air temperature.
2. Heating capacities based upon 68 F DB, 59 F WB
entering-air temperature.
3. All ratings based upon 208 volt operation.
UNIT
50RHR,RVR
PRESSURE
DROP
GPM CFM
EWT
Cooling 86 F Heating 68 F
PSI Ft TC
EER
Btuh/W
TC COP
006
1.7 3.9 1.50 180 6,200 12.8 7,400 4.2
009
2.9 6.7 2.25 300 8,100 12.8 10,300 4.3
012
8.1 18.7 3.00 375 11,800 12.7 14,600 4.1
015
6.8 15.7 3.75 500 14,100 13.3 16,800 4.6
019
5.6 12.8 4.50 600 18,900 12.5 22,500 3.6
024
5.8 13.5 6.00 800 23,000 12.3 27,600 4.2
030
3.3 7.6 7.50 1000 28,500 13.2 33,300 4.4
036
2.9 6.8 9.00 1200 34,000 13.0 41,700 4.2
042
3.8 8.8 10.50 1400 40,000 13.0 46,700 4.3
048
5.4 12.4 12.00 1600 47,000 12.8 58,000 4.2
060
7.9 18.2 15.00 2000 59,000 12.8 68,000 4.2
COP
Coefficient Performance
EER
Energy Efficiency Ratio
EWT
Entering Water Temperature
TC
Total Capacity
UNIT
50RHR,RVR
PRESSURE
DROP
GPM CFM
EWT
Cooling 77 F Heating 32 F
PSI Ft TC
EER
Btuh/W
TC COP
006
1.7 3.9 1.50 180 5,600 14.3 4,400 3.4
009
2.9 6.7 2.25 300 8,300 14.2 6,200 3.4
012
8.1 18.7 3.00 375 12,100 14.2 8,700 3.4
015
6.8 15.7 3.75 500 14,500 14.8 10,700 3.5
019
5.6 12.8 4.50 600 19,100 13.4 11,800 3.2
024
5.8 13.5 6.00 800 23,000 13.3 16,700 3.3
030
3.3 7.6 7.50 1000 28,700 14.4 20,100 3.4
036
2.9 6.8 9.00 1200 35,200 14.7 25,500 3.4
042
3.8 8.8 10.50 1400 42,000 15.0 29,400 3.4
048
5.4 12.4 12.00 1600 48,500 14.3 35,300 3.3
060
7.9 18.2 15.00 2000 60,600 14.1 44,000 3.2
COP
Coefficient Performance
EER
Energy Efficiency Ratio
EWT
Entering Water Temperature
TC
Total Capacity
UNIT
50RHR,RVR
PRESSURE
DROP
GPM CFM
EWT
Cooling 59 F Heating 50 F
PSI Ft TC
EER
Btuh/W
TC COP
006
1.7 3.9 1.50 180 5,900 17.6 5,500 3.8
009
2.9 6.7 2.25 300 8,800 17.6 7,700 3.8
012
8.1 18.7 3.00 375 12,500 17.6 1,100 3.8
015
6.8 15.7 3.75 500 15,200 17.6 13,500 4.1
019
5.6 12.8 4.50 600 20,100 17.6 16,700 3.4
024
5.8 13.5 6.00 800 26,100 18.2 21,300 3.7
030
3.3 7.6 7.50 1000 31,100 18.6 27,000 3.9
036
2.9 6.8 9.00 1200 37,500 18.2 33,400 3.9
042
3.8 8.8 10.50 1400 48,500 18.6 38,300 3.9
048
5.4 12.4 12.00 1600 54,000 18.1 46,000 3.8
060
7.9 18.2 15.00 2000 64,500 16.8 56,000 3.8
COP
Coefficient Performance
EER
Energy Efficiency Ratio
EWT
Entering Water Temperature
TC
Total Capacity
ARI/ISO capacities