Carrier Pro-Dialog CONTROL 4 User Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 28
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
17

 
    
    
Cooling csp 1 - - - Cooling setpoint 1
Cooling csp 2 - - - Cooling setpoint 2
Cooling auto Activated Open Unoccupied Ice storage setpoint
Cooling auto Activated Closed Unoccupied Cooling setpoint 2
Cooling auto - - Occupied Cooling setpoint 1
Cooling auto Deactivated - Unoccupied Heating setpoint 2
Heating hsp 1 - - - Heating setpoint 1
Heating hsp 2 - - - Heating setpoint 2
Heating auto - - Occupied Heating setpoint 1
Heating auto - - Unoccupied Heating setpoint 2

 
    
    
Cooling csp control - - - Control setpoint
Cooling - - - csp 1 (open) Cooling setpoint 1
Cooling - - - csp 2 (closed) Cooling setpoint 2
Cooling - Activated - Open Cooling setpoint 1
Cooling - Activated Open Closed Ice storage setpoint
Cooling - Activated Closed Closed Cooling setpoint 2
Heating - - - Open Heating setpoint 1
Heating - - - Closed Heating setpoint 2

 
   
   
Cooling - - - Occupied Cooling setpoint 1
Cooling - - - Unoccupied Cooling setpoint 2
Cooling - Activated Open Unoccupied Ice storage setpoint
Cooling - Activated Closed Unoccupied Cooling setpoint 2
Heating - - - Occupied Heating setpoint 1
Heating - - - Unoccupied Heating setpoint 2
* Only with energy management option
5.6.2 - Reset
Reset means the active setpoint is modified so that less
machine capacity is required (in cooling mode the setpoint
is increased, in heating mode it is decreased). This modifica-
tion is in general a reaction to a drop in the load. For the
Pro-Dialog control system, the reset source can be con-
figured in the menu Status => User: it can be provided
either by the outdoor temperature (gives a measure of the
load trends for the building) or by the return water tempe-
rature (∆T - gives an average building load) or by the reset
setpoint (only available with the energy management
option). In response to a drop in outdoor temperature or
to a drop in ∆T, the cooling setpoint is normally reset
upwards to optimise unit performance:
In the three cases the reset parameters, i.e. slope, source and
maximum value, are configurable in the Setpoint menu.
Reset is a linear function based on three parameters.
A reference at which reset is zero (outdoor temperature
or ∆T - no reset value).
A reference at which reset is maximum (outdoor tem-
perature or ∆T - full reset value).
The maximum reset value.



A Maximum reset value
B OATorΔTforzeroreset
C OATorΔTforfullreset
D Building load
Reset value
Outdoor temperature (OAT)
EvaporatorΔT
% Building load
Page view 16