Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata
103. Install the inside coupling half over the gasket and theninstall the outer half. Connect with nuts and bolts. Tightenthe nuts equally on both sid
11120110080e Drop (kPa)4060Water Pressure2000 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15Liters/second12 354403035154322530Drop ()1520Water Pressure 51000 10
121203100180e Drop (kPa)4060Water Pressure200012345678910111213Liters/second1234505101520253035400 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150
13Step 6 — Fill the Chilled Water LoopWATER SYSTEM CLEANING — Proper water systemcleaning is of vital importance. Excessive particulates in thewater
14Ensure the following when filling the system:1. Remove temporary bypass piping and cleaning/flushingequipment.2. Check to make sure all drain plugs
15EXAMPLE: Supply voltage is 240-3-60.AB = 243 vBC = 236 vAC = 238 vAverage Voltage =243 + 236 + 2383= 239 vDetermine maximum deviation from average
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata
2INSTALLATIONLocation — Do not store units in an area exposed to weath-er because of sensitive control mechanisms and electronicdevices. Locate unit i
352.301328[]STD UNIT 55.001397[]OPTIONAL SOUND ENCLOSURE 57.00 [1448]29.13740[]STD UNIT 32.00813[]62.501588[]OPTIONAL SOUND ENCLOSURE 32.12 [816]MO
4Fig. 5 — Dimensions — 30MPW015-045 UnitsNOTES:1. Operating weight includes weight of water and refrigerant.2. Denotes center of gravity.3. Dimen
5Table 1A — 30MPA Air-Cooled and 30MPW Liquid-Cooled Units — English* With optional hot gas bypass. NOTES:1. Operating weight includes refrigerant ope
6Table 1B — 30MPA Air-Cooled and 30MPW Liquid-Cooled Units — SI* With optional hot gas bypass. NOTES:1. Operating weight includes refrigerant operatin
7Step 3 — Place the UnitNOTE: These units are not suitable for unprotected outdooruse.Carrier recommends that these units be located in the base-ment
8NOTES:1. Chiller must be installed level to maintain proper compressor oil return.2. Wiring and piping shown are general points-of-connection guides
9NOTES:1. Chiller must be installed level to maintain proper compressor oilreturn.2. Wiring and piping shown are general points-of-connection guideson