Duct Free Systems Product Data Digest ¾ to 5 Nominal Tons Console Console Condenser & Mulit-Zone
ARI* CapacitiesSatellite ApplicationsIndoor Outdoor Std. Net Cooling Total SEER EER Heating Heating HeatingSection Section CFM BTUH kW High High HighB
System Cross MatchCooling Only High Wall Heat Pump High WallNominal Indoor Indoor Outdoor Outdoor Nominal Indoor Indoor Outdoor OutdoorCapacity Unit U
System Cross MatchCooling Only High Wall Heat Pump High WallNominal Indoor Indoor Outdoor Outdoor Nominal Indoor Indoor Outdoor OutdoorCapacity Unit U
System & Unit Specifications – Section 11ProductProductCooling Only System SpecificationsHeat Pump System SpecificationsUnit Specifications
Cooling Only System SpecificationsHigh WallNominal Indoor Outdoor ARI ARI Sound Rating (dBa)Capacity Unit Unit Capacity CFM SEER EER Indoor Indo
Cooling Only System SpecificationsHigh WallNominal Indoor Outdoor ARI ARI Sound Rating (dBa)Capacity Unit Unit Capacity CFM SEER EER Indoor Indo
Cooling Only System SpecificationsHigh WallNominal Indoor Outdoor ARI ARI Sound Rating (dBa)Capacity Unit Unit Capacity CFM SEER EER Indoor Indo
Cooling Only System SpecificationsHigh WallNominal Indoor Outdoor ARI ARI Sound Rating (dBa)Capacity Unit Unit Capacity CFM SEER EER Indoor Indo
Cooling Only System SpecificationsHigh WallNominal Indoor Outdoor ARI ARI Sound Rating (dBa)Capacity Unit Unit Capacity CFM SEER EER Indoor Indo
Cooling Only System SpecificationsHigh WallNominal Indoor Outdoor ARI ARI Sound Rating (dBa)Capacity Unit Unit Capacity CFM SEER EER Indoor Indo
Heat Pump System SpecificationsHigh WallNominal Indoor Outdoor ARI Capacities ARI Sound Rating (dBa)Capacity Unit Unit C/O H/P CFM SEER EER
APPLICATION DATA 1. Unit selection Select equipment to either match or be slightly less than anticipated peak cooling load. This provides better humi
Heat Pump System SpecificationsHigh WallNominal Indoor Outdoor ARI Capacities ARI Sound Rating (dBa)Capacity Unit Unit C/O H/P CFM SEER EER
Heat Pump System SpecificationsHigh WallNominal Indoor Outdoor ARI Capacities ARI Sound Rating (dBa)Capacity Unit Unit C/O H/P CFM SEER EER
Heat Pump System SpecificationsHigh WallNominal Indoor Outdoor ARI Capacities ARI Sound Rating (dBa)Capacity Unit Unit C/O H/P CFM SEER EER
Heat Pump System SpecificationsHigh WallNominal Indoor Outdoor ARI Capacities ARI Sound Rating (dBa)Capacity Unit Unit C/O H/P CFM SEER EER
Heat Pump System SpecificationsHigh WallNominal Indoor Outdoor ARI Capacities ARI Sound Rating (dBa)Capacity Unit Unit C/O H/P CFM SEER EER
Unit SpecificationsVert Vert Max Tube Connections DimensionsModel Voltage MCA MOCP Lift Drop Tube Liquid Vapor Width H
Condenser Only Ratings – Section 12ApplicationApplicationHDCHDL
Condenser Only RatingsSST Air Temperature Entering Condenser (F)(F) 55 65 75 85 95 105 115 12538HDC018TCG19.7 18.0 16.4 14.8 13.3 11.8 10.4 9.030 SDT7
Condenser Only RatingsSST Air Temperature Entering Condenser (F)(F) 55 65 75 85 95 105 115 12538HDC036TCG33.6 32.1 30.5 28.7 25.7 23.1 20.6 18.330 SDT
38HDL CONDENSER-ONLY RATINGSSee Legend on next page. Click here to view the next page of condenser-only performance data.SST(F)AIR TEMPERATURE ENTERI
HIGH WALL UNITS — These units should be positioned as high as possible on the wall for best air circulation. Allow adequate clearances above the unit
38HDL CONDENSER-ONLY RATINGS (cont) LEGENDSST(F)AIR TEMPERATURE ENTERING CONDENSER (F)55 65 75 85 95 105 115 12538HDL0
Duct Free Systems - Performance Data & Expanded RatingsCooling Only High Wall Heat Pump High WallIndoor Outdoor Net System Indoor Outdoor Net Net
Performance Data & Expanded Ratings - Systems Index TableMulti Split 4 Ton 38HDS048 Click here to return to System Index Table. I
COOLINGCAPACITIESSYSTEM1*—HIGHWALLSYSTEM(38AN009WITH40QNB009)Temp (F)Air EnteringCondenser(Edb)AirEnteringEvaporator—Cfm/BF184/0.08 200/0.09 215/0.10A
COOLINGCAPACITIES(cont)SYSTEM2*—HIGHWALLSYSTEM(38AN012WITH40QNB012)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/BF245/0.12 280/0.14
COOLINGCAPACITIES(cont)SYSTEM3*—HIGHWALLSYSTEM(38HDC018WITH40QNB018)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/BF360/0.12 414/0.1
COOLINGCAPACITIES(cont)SYSTEM4*—HIGHWALLSYSTEM(38HDC024WITH40QNB024)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/BF456/0.04 502/0.0
COOLINGCAPACITIES(cont)SYSTEM5*—CEILING-SUSPENDEDSYSTEM(38HDC018WITH40QAB024†)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/BF320/0.
COOLINGCAPACITIES(cont)SYSTEM6*—CEILING-SUSPENDEDSYSTEM(38HDC024WITH40QAB024)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/BF400/0.0
COOLINGCAPACITIES(cont)SYSTEM7*—CEILING-SUSPENDEDSYSTEM(38HDC030WITH40QAB036)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/BF640/0.0
FAN COIL UNITS CONDITION 40QN 40QA 40QK 40CG 40CS 40HD Maximum Room Temperature (F) 84 84 95 Min
COOLINGCAPACITIES(cont)SYSTEM8*—CEILING-SUSPENDEDSYSTEM(38HDC036WITH40QAB036)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/BF640/0.0
COOLINGCAPACITIES(cont)SYSTEM9*—53QAB048CEILING-SUSPENDEDSYSTEM(38HDC048WITH40QAB048)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/B
COOLINGCAPACITIES(cont)SYSTEM10*—CEILING-SUSPENDEDSYSTEM(38HDC060WITH40QAB060)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/BF1040/0
COOLINGCAPACITIES(cont)SYSTEM11*—IN-CEILINGCASSETTESYSTEM(38HDC018WITH40QKB024)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/BF375/0
COOLINGCAPACITIES(cont)SYSTEM12*—IN-CEILINGCASSETTESYSTEM(38HDC024WITH40QKB036)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/BF635/0
COOLINGCAPACITIES(cont)SYSTEM13*—IN-CEILINGCASSETTESYSTEM(38HDC030WITH40QKB036)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/BF635/0
COOLINGCAPACITIES(cont)SYSTEM14*—IN-CEILINGCASSETTESYSTEM(38HDC036WITH40QKB036)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/BF635/0
COOLING CAPACITIESSYSTEM 15* – 38HDL018 WITH 40QNB024 LEGEND Rating ConditionNot recommended for long-term operation*Clic
COOLING CAPACITIES (cont)SYSTEM 16* – 38HDL024 WITH 40QNB024 LEGEND Rating ConditionNot recommended for long-term operation*Click
COOLING CAPACITIES (cont)SYSTEM 17* – 38HDL018 WITH 40QAB024ƒ LEGEND Rating ConditionNot recommended for long-term operation*Clic
11.Freshairandducting a. Theceiling-suspendedfancoilunitsmaybringinupto30%freshair.Thepercentageofairallowableiscalculated based on the unit hig
COOLING CAPACITIES (cont)SYSTEM 18* – 38HDL024 WITH 40QAB024 LEGEND Rating ConditionNot recommended for long-term operati
COOLING CAPACITIES (cont)SYSTEM 19* – 38HDL030 WITH 40QAB036 LEGEND Rating ConditionNot recommended for long-term operat
COOLING CAPACITIES (cont)SYSTEM 20* – 38HDL036 WITH 40QAB036 LEGEND Rating ConditionNot recommended for long-term operati
COOLING CAPACITIES (cont)SYSTEM 21* – 38HDL048 WITH 40QAB048 LEGEND Rating ConditionNot recommended for long-term operat
COOLING CAPACITIES (cont)SYSTEM 22* – 38HDL060 WITH 40QAB060 LEGEND Rating ConditionNot recommended for long-term operat
COOLING CAPACITIES (cont)SYSTEM 23* – 38HDL018 WITH 40QKB024 LEGEND Rating ConditionNot recommended for long-term operat
COOLING CAPACITIES (cont)SYSTEM 24* – 38HDL024 WITH 40QKB036 LEGEND Rating ConditionNot recommended for long-term operat
COOLING CAPACITIES (cont)SYSTEM 25* – 38HDL030 WITH 40QKB036 LEGENDRating ConditionNot recommended for long-term operati
COOLING CAPACITIES (cont)SYSTEM 26* – 38HDL036 WITH 40QKB036 LEGEND Rating ConditionNot recommended for long-term operat
COOLINGCAPACITIESSYSTEM27C*—HIGHWALLSYSTEM(38BK009WITH40QNE009)TEMP (F)AIR ENTERINGOUTDOOR UNIT(Edb)AIR ENTERING INDOOR UNIT — CFM/BF214/0.10 233/0.11
Duct Free Systems - Electrical Data - 40 Series High Wall Units Model Voltage Voltage Fan Heater Power MinimumV-Ph-60Hz Min Max FLA k
COOLINGCAPACITIES(cont)SYSTEM28C*—HIGHWALLSYSTEM(38BK012WITH40QNE012)TEMP (F)AIR ENTERINGOUTDOOR UNIT(Edb)AIR ENTERING INDOOR UNIT — CFM/BF245/0.12 28
COOLINGCAPACITIES(cont)SYSTEM29C*—HIGHWALLSYSTEM(38BK018WITH40QNE018)TEMP (F)AIR ENTERINGOUTDOOR UNIT(Edb)AIR ENTERING INDOOR UNIT — CFM/BF376/0.14 40
COOLINGCAPACITIES(cont)SYSTEM30C*—HIGHWALLSYSTEM(38BK024WITH40QNE024)TEMP (F)AIR ENTERINGOUTDOOR UNIT(Edb)AIR ENTERING INDOOR UNIT — CFM/BF446/0.04 48
COOLINGCAPACITIES(cont)SYSTEM31C*—CEILING-SUSPENDEDSYSTEM(38QR-C018WITH40QAE024)TEMP (F)AIR ENTERINGOUTDOOR UNIT(Edb)AIR ENTERING INDOOR UNIT — CFM/BF
COOLINGCAPACITIES(cont)SYSTEM32C*—CEILING-SUSPENDEDSYSTEM(38QR-C024WITH 40QAE024)TEMP (F)AIR ENTERNGOUTDOOR UNIT(Edb)AIR ENTERING INDOOR UNIT — CFM
COOLINGCAPACITIES(cont)SYSTEM33C*—CEILING-SUSPENDEDSYSTEM(38QR-C030WITH40QAE036)TEMP (F)AIR ENTERINGOUTDOOR UNIT(Edb)AIR ENTERING INDOOR UNIT — CFM/BF
COOLINGCAPACITIES(cont)SYSTEM34C*—CEILING-SUSPENDEDSYSTEM(38QR-C036SINGLE-PHASEUNITWITH40QAE036)TEMP (F)AIR ENTERINGOUTDOOR UNIT(Edb)AIR ENTERING INDO
COOLINGCAPACITIES(cont)SYSTEM35C*—CEILING-SUSPENDEDSYSTEM(38QR-C0363-PHASEUNITWITH40QAE036)TEMP (F)AIR ENTERINGOUTDOOR UNIT(Edb)AIR ENTERING INDOOR UN
COOLINGCAPACITIES(cont)SYSTEM36C*—CEILING-SUSPENDEDSYSTEM(38QR-C048WITH40QAE048)TEMP (F)AIR ENTERINGOUTDOOR UNIT(Edb)AIR ENTERING INDOOR UNIT — CFM/BF
COOLINGCAPACITIES(cont)SYSTEM37C*—CEILING-SUSPENDEDSYSTEM(38QR-C060WITH40QAE060)TEMP (F)AIR ENTERINGOUTDOOR UNIT(Edb)AIR ENTERING INDOOR UNIT — CFM/BF
Duct Free Systems - Electrical Data - 40 Series Under Ceiling UnitsModel Voltage Voltage Fan Heater Power MinimumV-Ph-60Hz Min Max FL
COOLINGCAPACITIES(cont)SYSTEM38C*—IN-CEILINGCASSETTESYSTEM(38QR-C018WITH40QKE024)TEMP (F)AIR ENTERINGOUTDOOR UNIT(Edb)AIR ENTERING INDOOR UNIT — CFM/B
COOLINGCAPACITIES(cont)SYSTEM39C*—IN-CEILINGCASSETTESYSTEM(38QR-C024WITH40QKE036)TEMP (F)AIR ENTERINGOUTDOOR UNIT(Edb)AIR ENTERING INDOOR UNIT — CFM/B
COOLINGCAPACITIES(cont)SYSTEM40C*—IN-CEILINGCASSETTESYSTEM(38QR-C030WITH40QKE036)TEMP (F)AIR ENTERINGOUTDOOR UNIT(Edb)AIR ENTERING INDOOR UNIT — CFM/B
COOLINGCAPACITIES(cont)SYSTEM41C*—IN-CEILINGCASSETTESYSTEM(38QR-C036SINGLE-PHASEUNITWITH40QKE048)TEMP (F)AIR ENTERINGOUTDOOR UNIT(Edb)AIR ENTERING IND
COOLINGCAPACITIES(cont)SYSTEM42C*—IN-CEILINGCASSETTESYSTEM(38QR-C0363-PHASEUNITWITH40QKE048)TEMP (F)AIR ENTERINGOUTDOOR UNIT(Edb)AIR ENTERING INDOOR U
INSTANTANEOUSANDINTEGRATEDHEATINGRATINGSSYSTEM27H*—HIGHWALLSYSTEM(38BK009WITH40QNE009)TEMP (F)AIRENTERINGINDOOR UNITAIRENTERINGINDOOR UNIT(CFM)AIR TEM
INSTANTANEOUSANDINTEGRATEDHEATINGRATINGS(cont)SYSTEM28H*—HIGHWALLSYSTEM(38BK012WITH40QNE012)TEMP (F)AIRENTERINGINDOOR UNITAIRENTERINGINDOOR UNIT(CFM)A
INSTANTANEOUSANDINTEGRATEDHEATINGRATINGS(cont)SYSTEM29H*—HIGHWALLSYSTEM(38BK018WITH40QNE018)TEMP (F)AIRENTERINGINDOOR UNITAIRENTERINGINDOOR UNIT(CFM)A
INSTANTANEOUS ANDINTEGRATEDHEATINGRATINGS(cont)SYSTEM30H*—HIGHWALLSYSTEM(38BK024WITH40QNE024)TEMP (F)AIRENTERINGINDOOR UNITAIRENTERINGINDOOR UNIT(CFM)
INSTANTANEOUSANDINTEGRATEDHEATINGRATINGS(cont)SYSTEM31H*—CEILING-SUSPENDEDSYSTEM(38QR-C018WITH40QAE024)TEMP (F)AIRENTERINGINDOOR UNITAIRENTERINGINDOOR
Duct Free Systems - Electrical Data - 40 Series Console UnitsModel Voltage Voltage Fan Heater Power MinimumV-Ph-60Hz Min Max FLA kW F
INSTANTANEOUSANDINTEGRATEDHEATINGRATINGS(cont)SYSTEM32H*—CEILING-SUSPENDEDSYSTEM(38QR-C024WITH40QAE024)TEMP (F)AIRENTERINGINDOOR UNITAIRENTERINGINDOOR
INSTANTANEOUSANDINTEGRATEDHEATINGRATINGS(cont)SYSTEM33H*—CEILING-SUSPENDEDSYSTEM(38QR-C030WITH40QAE036)TEMP (F)AIRENTERINGINDOOR UNITAIRENTERINGINDOOR
INSTANTANEOUSANDINTEGRATEDHEATINGRATINGS(cont)SYSTEM34H*—CEILING-SUSPENDEDSYSTEM(38QR-C036SINGLE-PHASEUNITWITH40QAE036)TEMP (F)AIRENTERINGINDOOR UNITA
INSTANTANEOUSANDINTEGRATEDHEATINGRATINGS(cont)SYSTEM35H*—CEILING-SUSPENDEDSYSTEM(38QR-C0363-PHASEUNITWITH40QAE036)TEMP (F)AIRENTERINGINDOOR UNITAIRENT
INSTANTANEOUSANDINTEGRATEDHEATINGRATINGS(cont)SYSTEM36H*—CEILING-SUSPENDEDSYSTEM(38QR-C048WITH40QAE048)TEMP (F)AIRENTERINGINDOOR UNITAIRENTERINGINDOOR
INSTANTANEOUSANDINTEGRATEDHEATINGRATINGS(cont)SYSTEM37H*—CEILING-SUSPENDEDSYSTEM(38QR-C060WITH40QAE060)TEMP (F)AIRENTERINGINDOOR UNITAIRENTERINGINDOOR
INSTANTANEOUS ANDINTEGRATEDHEATINGRATINGS(cont)SYSTEM38H*—IN-CEILINGCASSETTESYSTEM(38QR-C018WITH40QKE024)TEMP (F)AIRENTERINGINDOOR AIRAIRENTERINGINDOO
INSTANTANEOUSANDINTEGRATEDHEATINGRATINGS(cont)SYSTEM39H*—IN-CEILINGCASSETTESYSTEM(38QR-C024WITH40QKE036)TEMP (F)AIRENTERINGINDOOR UNITAIRENTERINGINDOO
INSTANTANEOUSANDINTEGRATEDHEATINGRATINGS(cont)SYSTEM40H*—IN-CEILINGCASSETTESYSTEM(38QR-C030WITH40QKE036)TEMP (F)AIRENTERINGINDOOR UNITAIRENTERINGINDOO
INSTANTANEOUSANDINTEGRATEDHEATINGRATINGS(cont)SYSTEM41H*—IN-CEILINGCASSETTESYSTEM(38QR-C036SINGLE-PHASEUNITWITH40QKE048)TEMP (F)AIRENTERINGINDOOR UNIT
Duct Free Systems - Electrical Data - 40 Series Cassette UnitsModel Voltage Voltage Fan Heater Power MinimumV-Ph-60Hz Min Max FLA kW
INSTANTANEOUSANDINTEGRATEDHEATINGRATINGS(cont)SYSTEM42H*—IN-CEILINGCASSETTESYSTEM(38QR-C0363-PHASEUNITWITH40QKE048)TEMP (F)AIRENTERINGINDOOR UNITAIREN
COOLINGCAPACITIESTABLENO.43*—38HDS024(or1Circuitof38HDS048System)CONDENSINGUNITWITHTWO40QKB024IN-CEILINGCASSETTEUNITSTEMP (F)AIR ENTERINGCONDENSER(Edb
COOLINGCAPACITIES(cont)TABLENO.44*—38HDS024(or1Circuitof38HDS048System)CONDENSINGUNITWITHTWO40QAB024†CEILING-SUSPENDEDUNITSTEMP (F)AIR ENTERINGCONDENS
COOLINGCAPACITIES(cont)TABLENO.45*—38HDS024(or1Circuitof38HDS048System)CONDENSINGUNITWITHTWO40QNB018HIGHWALLUNITSTEMP (F)AIR ENTERINGCONDENSER(Edb)AIR
COOLINGCAPACITIES(cont)TABLENO.46*—38HDS024(or1Circuitof38HDS048System)CONDENSINGUNITWITHONE40QAB024†CEILING-SUSPENDEDUNITANDONE40QKB024IN-CEILINGCASS
COOLINGCAPACITIES(cont)TABLENO.47*—38HDS024(or1Circuitof38HDS048System)CONDENSINGUNITWITHONE40QKB024IN-CEILINGCASSETTEUNITANDONE40QNB018HIGHWALLUNITTE
COOLINGCAPACITIES(cont)TABLENO.48*—38HDS024(or1Circuitof38HDS048System)CONDENSINGUNITWITHONE40QAB024†CEILING-SUSPENDEDUNITANDONE40QNB018HIGHWALLUNITTE
COOLINGCAPACITIES(cont)TABLENO.52*—38HDS024(or1Circuitof38HDS048System)CONDENSINGUNITWITHONE40QNB024HIGHWALLUNITTEMP (F)AIR ENTERINGCONDENSER(Edb)AIR
COOLINGCAPACITIES(cont)TABLENO.53*—38HDS024(or1Circuitof38HDS048System)CONDENSINGUNITWITHONE40QAB024CEILING-SUSPENDEDUNITTEMP (F)AIR ENTERINGCONDENSER
COOLINGCAPACITIES(cont)TABLENO.54*—38HDS024(or1Circuitof38HDS048System)CONDENSINGUNITWITHONE40QKB036IN-CEILINGCASSETTEUNITTEMP (F)AIR ENTERINGCONDENSE
Duct Free Systems - Electrical Data - 40 Series Satellite Units Model Voltage Voltage Fan Heater Power MinimumV-Ph-60Hz Min Max F
COOLINGCAPACITIESTABLE NO. 55 - 42WKN004EnteringWaterTemp (F)WaterTempRise (F)Entering Air (F) — dry bulb72 80Entering Air (F) — wet bulb63 67 71 63 6
COOLINGCAPACITIES(cont)TABLE NO. 57 - 42WKN010—2-TUBEEnteringWaterTemp (F)WaterTempRise (F)Entering Air (F) — dry bulb72 80Entering Air (F) — wet bulb
COOLINGCAPACITIES(cont)TABLE NO. 59 - 42WKN016EnteringWaterTemp (F)WaterTempRise (F)Entering Air (F) — dry bulb72 80Entering Air (F) — wet bulb63 67 7
COOLINGCAPACITIES(cont)TABLE NO. 61 - 42WKN020—4-TUBEEnteringWaterTemp (F)WaterTempRise (F)Entering Air (F) — dry bulb72 80Entering Air (F) — wet bulb
Duct Free Systems - Piston/Charge CombinationsCooling Only High Wall Heat Pump High WallIndoor Outdoor AccuRater Charge Indoor Outdoor AccuRater AccuR
Duct Free Systems - Piston/Charge CombinationsCooling Only High Wall Heat Pump High WallIndoor Outdoor AccuRater Charge Indoor Outdoor AccuRater AccuR
Duct Free Systems - Piston/Charge CombinationsCooling Only High Wall Heat Pump High WallIndoor Outdoor AccuRater Charge Indoor Outdoor AccuRater AccuR
Duct Free Systems - Piston/Charge CombinationsCooling Only High Wall Heat Pump High WallIndoor Outdoor AccuRater Charge Indoor Outdoor AccuRater AccuR
Duct Free Systems - Piston/Charge CombinationsCooling Only High Wall Heat Pump High WallIndoor Outdoor AccuRater Charge Indoor Outdoor AccuRater AccuR
Refrigerant and Long Line Applications– Section 15ApplicationApplicationAN009/012 & BK009/01238HDC38HDL38HDS38QRC & 38BK018/02438 C & S Se
Maintenance/RepairApplicationProductInstallationInstallationApplicationProduct??HELPHELPDuct-Free Systems DigestDuct-Free Systems DigestMaintenance/Re
Duct Free Systems - Electrical Data - CondensersModel Voltage Voltage Compressor Fan Power SupplyV-Ph-60Hz Min Max RLA LRA FLA MCA MOCP FLA38
Refrigerant Lines – AN009/012 & BK009/012 1. The AN009/012 & BK009/012 are shipped with a full charge of R-22 refrigerant. Since all refrig
Refrigerant Lines – 38HDC1. The 38HDC units are shipped with a full charge of R-22 refrigerant based on the smallest charge combination.2. All cha
Long Line Applications – 38 HDC (continued)7. Changes in piston size. The metering device for long line applications must be adjusted to compensate f
Refrigerant Lines - 38HDL1. The 38HDL units are shipped with a full charge of R-22 refrigerant based on the smallest charge combination.2. All charges
Long Line Applications - 38HDL (continued)7. Changes in piston size. The metering device for long line applications must be adjusted to compensate f
Refrigerant Lines – 38HDS1. The 38HDS units are shipped with a full charge of R-22 refrigerant.2. All charges, line sizes and capacities are based o
Refrigerant Lines – 38QRC & 38BK018/0241. The 38QR & BK018/024 units are shipped with a holding charge of R-22 refrigerant.2. All charges,
Long Line Applications – 38QRC & 38BK018/024 (continued)7. Changes in piston size. The metering device for long line applications must be adjuste
Refrigerant Lines – 38CG, CS, SB, & SC 1. The 38CG, CS, SB, & SC series condensers are shipped with a full charge of R-22 refrigerant. Sinc
6. Lowered configuration: (Drop) Indoor unit below outdoor unit Diagram #4 a. The maximum elevation difference and the maximum equivalent length of
Duct Free Systems - System ChargesCooling Only High Wall Heat Pump High Wall Heat Cool Under Ceiling COOLING WITH ELECTRIC HEATIndoor Outdoor System I
Table #1 - Line Length's (Maximum)"B""C""A"ModelLiftDropTubeNote #1 Note #2Lgth38AN-009/012 30' 30' 50&ap
Table #2 - Fitting Losses in Equivalent FeetTube Size O.D. (in)90 deg Short Radius90 deg Long Radius45 deg Short Radius5/8 1.6 1.0 0.83/4 1.8 1.2 0.97
Table #3 - Effective Capacity LossNominalStdLongPercent of cooling capacity lossCapacityVaporVaporLineLine *50 ft75 ft100 ft125 ft150 ft175 ft200 ft18
Table #4 - Calculation of Outdoor Piston Number Outdoor Unit Above Indoor UnitFeetPiston Change0-50 051-75 +476-100 +6101-125 +8
Table #5 - Common Piston SizesAccuraterChatleffAccuraterChatleff- 32 65 65- 33 67 6735 35 - 68- 36 70 70- 37 - 7138 38 73 7339 - 7440 40 76 7641 78 78
GROUND LEVELBASEMENTDiagram #1 * Not required for AN/BK009/012 –38 CG, SC, CS, SBSolenoid*"A"
GROUND LEVELBASEMENTSolenoid*"A"Diagram #2 * Not required for AN/BK009/012 –38 CG, SC, CS, SB
GROUND LEVELTRAP"B"Solenoid*Diagram #3 *Not required for AN/BK009/012 –38 CG, SC, CS, SB
Solenoid*"C"Diagram #4 * Not required for AN/BK009/012 – 38 CG, SC, CS, SB
SELECTION PROCEDURE (With Example) Rev “A” 09/19/01 I Determine the type of fan coil, which best suits the application (refer to S
Duct Free Systems - System ChargesCooling Only High Wall Heat Pump High Wall Heat Cool Under Ceiling COOLING WITH ELECTRIC HEATIndoor Outdoor System I
Drawings – Section 17ApplicationApplication40QN - 00940QN - 012 Cooling Only &
DIMENSIONAL DRAWING, BASE UNIT – 40QN009, 012 FAN COIL UNITSUNIT40QNWEIGHT A B CLb Kg in. mm in. mm in. mm009 18.7 8.5 33.46 850 11.02 280 6.29 160012
DIMENSIONAL DRAWING, BASE UNIT – 40QN018, 024 FAN COIL UNITSUNIT40QNWEIGHT018 39 Lb [17.5 Kg]024 43 Lb [19.5 Kg]NOTES:1. Dimensions in [ ] are in mill
40QA BaseUnitDimensionsNOTES:1. Dimensions in [ ] are in millimeters.2. Direction of airflow.3. Standard unit clearances are as follows:•09on top and r
UNIT40QK-OPERATING WEIGHTLb Kg024 61.6 28NOTES:1. indicates airflow.2. Dimensions in [ ] are in millimeters.3. Service clearance is 2 ft on control box
UNIT40QK–OPERATING WEIGHTLb Kg036 105.8 48048* 118.0 53*OWO heat pump fan coil units only.NOTES:1. Indicates airflow.2. Dimensions in [ ] are in millim
4Fig. 3 — 40HD036,048 Dimensional DrawingNOTES:1. Dimensions in [ ] are in millimeters.2. Center of gravity.3. Direction of airflow.4. Optional dir
Drawings – Section 17ApplicationApplication38 AN 00938 AN - 012 38 HDC 018
Duct Free Systems - System ChargesCooling Only High Wall Heat Pump High Wall Heat Cool Under Ceiling COOLING WITH ELECTRIC HEATIndoor Outdoor System I
DIMENSIONALDRAWING,BASEUNIT—38HDSCONDENSINGUNITSUNITABCDEFGHFt-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm024 2-11⁄86
DIMENSIONAL DRAWING, BASE UNIT – 38BK018, 024 HEAT PUMP UNITSUNITAB CDEFft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm018 2-11⁄8638.2 3-0
DIMENSIONAL DRAWING, BASE UNIT – 38QR HEAT PUMP UNITSUNITABCDEFGHJKLMOPERATINGWEIGHTft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in.
AccuRater It is extremely important that all refrigerant lines and the AccuRater metering device be insulated on heat pumps. On cooling only units
Fig. 14 – AccuRater Metering Device at Service Valve (Bypass Type Components) Fig. 13 – AccuRater Metering Device in Liquid Line (Bypass type Compo
Charge Verification – Section 19InstallationInstallation38HDC, HDL, QR, CG, CS38 HDS SB, SC (MULTISPLIT)
REFRIGERANT CHARGING: WARNING: To prevent personal injury, wear safety glasses and gloves when handling refrigerant. Do not overcharge system compress
Duct Free Systems - System ChargesCooling Only High Wall Heat Pump High Wall Heat Cool Under Ceiling COOLING WITH ELECTRIC HEATIndoor Outdoor System I
REFRIGERANT CHARGING (Multi Split) WARNING: To prevent personal injury, wear safety glasses and gloves when handling refrigerant. Do not overcharge s
Table 8 – Required Liquid Line Temperatures Table 7 – Required Unit Subcooling Figure 14 – Vapor Supply Line Measurement Locations (048 Unit Shown)
Controls – Section 20InstallationInstallationHigh WallUnder Ceiling, Cassette, & Satellite38HDSConsole
Controls — systems using high wall fan coils 40QNB/QNE control system The 40QN unit is equipped with a microprocessor control, which operates the sy
• Maximum Dehumidification Mode — When the dehumidification mode is selected, the indoor fan will operate continuously at the selected speed if the s
• Awake Mode — The awake timer will turn the unit on when the timer reaches zero minutes. The unit will start in the same mode and at the same selecte
*Minimum unit run time starts when outdoor coil temperature drops below 34 F, then accumulates runtime regardless of coil temperature.ElectronicContro
Controls — systems using Under Ceiling, Cassette or Satellite fan coils Automatic air sweep All Under Ceiling units are equipped with an automatic air
Duct Free Systems - System ChargesCooling Only High Wall Heat Pump High Wall Heat Cool Under Ceiling COOLING WITH ELECTRIC HEATIndoor Outdoor System I
DFB switches the unit back to normal heating operation. If the DFT remains closed the DFB switches the unit back to heating operation after 10 minutes
Controls - 38HDS Unit operation NOTE: AUTO fan mode is used as the unit operation example for ALL fan coil units in this section. Contact your local C
the 38HDS microprocessor if the other refrigerant circuit is still operating. The outdoor fan only stops when both compressors are off. Refer to 38HD
ThermostatInstallationInstallationOperationPhotographs and illustrations
3 AIR CONDITIONER OPERATION MODE Your Carrier Duct Free air conditioner operates in four modes:The air conditioner cools, dries, and filters the roo
4 • When transmitting a command from the remote controller,point the transmitter toward the receiver on the right side of theair conditioner.• The a
5 INSERTING BATTERIES IN THE REMOTE CONTROLLER Before using the remote controller you must insert two 1.5VAAA Alkaline batteries, as follows:• Slide
6 • Press the On/Off button 3 to transmit your selections to theair conditioner1. If you choose to place the airflow deflector in a fixed posi-tion
7 • Scroll through the Timer periods as explained in the previoussection • Choose the SLEEP Timer period• Enter the desired Start/Stop times (SLEEP
8 When the air conditioner is OFF: • Press DELAY button. The clock advances one hour, while theword START and the number 3 flash.• Each additional p
Duct Free Systems - System ChargesCooling Only High Wall Heat Pump High Wall Heat Cool Under Ceiling COOLING WITH ELECTRIC HEATIndoor Outdoor System I
9 MORE ON NEXT PAGE airborne particles. More frequent cleaning may be neces-sary depending on indoor
53DFST2-NP 53DFS250-SL 53DFS250-FS Fig #3
Installation Diagrams – Section 22InstallationInstallation40 QN 009 & 01240 QN 018 & 024
TYPICAL INSTALLATION — HIGH-WALL SYSTEMS, 9,000 AND 12,000 BTUH(Cooling-Only System Shown)LEGENDNEC — National Electrical Code*Standard.†Field supplie
TYPICAL INSTALLATION — HIGH-WALL SYSTEMS, 18,000 AND 24,000 BTUH(Cooling Only System Shown)LEGENDNEC — National Electrical CodePipingLine Voltage24 VT
Installation Diagrams – Section 22InstallationInstallation40 QA40 C
TYPICAL INSTALLATION — CEILING-SUSPENDED SYSTEMSLEGENDf — PhaseNEC — National Electrical CodePipingLine Voltage24 VThermistor*Standard.†Accessory item
FIELD SUPPLIEDFUSEDDISCONNECTAND WIRINGPER NECWIRELESSCONTROLLERFIELD SUPPLIED WEATHERPROOFFUSED DISCONNECT AND WIRINGPER NECINSULATEDLIQUID LINEOUTD
Installation Diagrams – Section 22InstallationInstallation40 QK40 HD
TYPICAL INSTALLATION — IN-CEILING CASSETTE SYSTEMSLEGENDf — PhaseNEC — National Electrical CodePipingLine Voltage24 V*Standard.†Accessory item.**Field
Duct Free SystemsHigh Wall Features and AccessoriesOutdoor Section/Indoor SectionFeatureAN/QNBBK/QNEBK/QNHBK/QNHHDC/QNBHDL/QNBHDS/QNBAll009
FIELD SUPPLIEDTYPE L REFRIGERANTTUBINGFIELD SUPPLIEDFILTER DRIERFIELD SUPPLIED24 V CONTROLWIRINGFIELD SUPPLIEDCONDENSATEDRAIN LINETO OPEN DRAINFIELD
Service – Section 23InstallationInstallation40 QN – High Wall40 QA – Under Ceiling40 CG and CS – Console40 HD – Satellite40 QK – Cassette
SERVICE – High Wall Systems WARNING: When servicing unit, turn off all electric power to unit to avoid shock hazard or injury from rotating parts. C
Compressor Short Cycling Protection There is a time delay of 3 minutes between compressor turning off and turning back on. Indoor Coil Freeze Protec
SERVICE Under Ceiling, Cassette, Console, & Satellite Fan Coils WARNING: When servicing unit, turn off all electric power to unit to avoid shock
Service – Section 23InstallationInstallation38 HDC, 38 QR, & BK 018, 02438 HDS38 HDL38 CG, CS, SC, & SB
SERVICE – 38HDC, 38QR, & 38BK018,024 WARNING: Before performing recommended maintenance, be sure unit main power switch is turned off. Failure t
NOTE: If pressure switch needs to be replaced, there is a Schrader valve located under the switch so that system will not need to be evacuated. CRANK
Discharge Temperature Switch (DTS) Heat Pump Only Switch used only on sizes 030 and 036 with scroll compressors, senses high discharge temperature lev
Duct Free SystemsUnder Ceiling Features and AccessoriesFeature Under Ceiling Outdoor/IndoorHDC/QAB HDL/QAB HDS/QAB QR/QAEAccumulator Standa
SERVICE – 38HDL WARNING: Before performing recommended maintenance, be sure unit main power switch is turned off. Failure to do so may result in elec
Fig. 11 – Condenser Fan Mounting Positions
SERVICE – Multi Split WARNING: Before performing recommended maintenance, be sure unit main power switch is turned off, and be sure all disconnects f
LOW-PRESSURE SWITCH This switch, mounted on the vapor return line, has fixed non-adjustable settings. To check pressure switch, attach pressure gage t
Figure 13 – Condenser-Fan Mounting Positions
SERVICE – 38CG, CS, SB, & SC WARNING: Before performing recommended maintenance, be sure unit main power switch is turned off. Failure to do so m
Start-Up Instructions – Section 24InstallationInstallation40 QNCheck List
START-UP – High Wall Systems Complete the following checks and the Start-Up checklist before system start-up. Refer to outdoor unit installation, sta
Start-Up Instructions – Section 24InstallationInstallation40 C – Console40 QA – Under CeilingCheck List
Duct Free SystemsConsole Features and AccessoriesFeature Console Outdoor/Indoor38CG/40CG 38CS/40CS 38SC/40CG 38SB/40CSAccumulator N/A N/A N
START-UP – Under Ceiling Systems WARNING: Never operate unit without a filter or with grille removed; damage to the unit or personal injury may resul
START-UP – Console Systems WARNING: Never operate unit without a filter or with grille removed; damage to the unit or personal injury may result. Mak
Start-Up Instructions – Section 24InstallationInstallation40 QKCheck List
START-UP - Cassette Units Make the following checks and complete the Start-Up Checklist before system start-up. Refer to outdoor unit Installation, S
Start-Up Instructions – Section 24InstallationInstallation40 HDCheck List
START-UP - Satellite Units Make the following checks and complete the Start-Up Checklist before system start-up. Refer to outdoor unit Installation,
Start-Up Instructions – Section 24InstallationInstallation38 HDC38 HDL38 HDS38 QR38 AN/BK 009 & 012Check List
START-UP - Multi-Split LEAK TEST Field piping and all tubing connections must be leak tested by the pressure method. Use R-22 at approximately 25 psi
START-UP – 38HDC, 38HDL, & 38QR NOTE: All outdoor units with a reciprocating compressor have a crankcase heater. Heater should be energized for a
START-UP CHECKLIST Outdoor Unit: Model Number ________________ Serial Number ____________________ Indoor Unit: Model Number __________________
ARI* Capacities High Wall ApplicationsIndoor Outdoor Std. Net Cooling Total SEER EER Heating Heating Heating Heating HeatingSection Section CFM BTUH
Duct Free SystemsCassette Features and AccessoriesFeature Outdoor Section/Indoor SectionHDC/QKBHDL/QKBHDS/QKBQR/QKEAccumulator
CHECK MOUNTING OF SUBBASE TO WALL, IS IT TIGHT (DO NOT APPLY EXCESSIVE FORCE TO MOUNTING SCREW)? (Y/N) _____ Units with Wireless Remote Controller CH
Wire Diagrams (Under Development)InstallationInstallation40QNB009 to 38AN00940QNB012 to 38AN01240QNB018 to 38HDC018
Wire Diagrams (Under Development)InstallationInstallation40QAB024-3 to 38HDC018-340QAB024-3 to 38HDL018-340QAB024-3 to 38HDC024-340QAB024-3 to 38HDL02
Wire Diagrams (Under Development)InstallationInstallation40QKB024-3 to 38HDC018-340QKB024-3 to 38HDL018-340QKB036-3 to 38HDC024-340QKB036-3 to 38HDL02
Cleaning & Maintenance – Section 26Maintenance/RepairMaintenance/Repair40QN
40 QN CLEANINGANDMAINTENANCETo avoid the possibility of electric shock, before per-forming any cleaning and maintenance operations al-ways turn off po
To Clean Indoor Unit Front Panel — If the frontpanel of the unit becomes dirty or smudged, wipe the out-side of the front panel with a soft dry cloth.
Cleaning & Maintenace – Section 26Maintenance/RepairMaintenance/Repair40 QA40 CG, CS
40 QA CLEANINGANDMAINTENANCETo avoid the possibility of electric shock, before per-forming any cleaning and maintenance operations, al-ways turn off p
Table 8 – Cleaning and Maintenance ScheduleTASK MONTHLY QUARTERLY YEARLYINDOOR UNITClean Air Filters XClean Drain Pipe XClean Condensate Drain Pan XCl
Duct Free SystemsSatellite Features and AccessoriesFeature Outdoor Section/Indoor SectionHDC/40HD HDL/40HD QR/40HDAccumulator Standard
40 CG, CS CARE AND MAINTENANCE Step 1 – Maintenance (Outdoor Unit) WARNING Before performing recommended maintenance, be sure unit main power switch
Cleaning & Maintenance – Section 26Maintenance/RepairMaintenance/Repair40 QK
40 QK SERVICE AND MAINTENANCERemove unit grille, filter, and condensate pan for clean-ing, lubricating, or replacing parts.To avoid personal injury or
Cleaning & Maintenance – Section 26Maintenance/RepairMaintenance/Repair40 HD
40 HD CLEANING AND MAINTENANCE To avoid the possibility of electrical shock, before performing any cleaning and maintenance operations, always turn o
Cleaning & Maintenance – Section 26Maintenance/RepairMaintenance/Repair38 HDC38 HDL38 HDS38 QR38 AN38 BK38 CG, CS, SB, SC
38 HDC, 38 HDL, 38 QR MAINTENANCE WARNING Before performing recommended maintenance, be sure unit main power switch is turned off. Failure to do so
38 HDS MAINTENANCE WARNING Before performing recommended maintenance, be sure unit main power switch is turned off. Failure to do so may result in e
38 AN, 38 BK CLEANINGANDMAINTENANCETo avoid the possibility of electric shock, before per-forming any cleaning and maintenance operations al-ways turn
To Clean Indoor Unit Front Panel — If the frontpanel of the unit becomes dirty or smudged, wipe the out-side of the front panel with a soft dry cloth.
Accessories – Field Installed Low Ambient Kit: The Low Ambient Kit is a solid state head pressure controller designed to control condenser fan cyclin
38 CG, CS, SB, SC CARE AND MAINTENANCE Step 1 – Maintenance (Outdoor Unit) WARNING Before performing recommended maintenance, be sure unit main powe
Troubleshooting & Fault Codes – Section 27Maintenance/RepairMaintenance/Repair40 QN – Troubleshooting40 QN – Fault Codes
HWError Code.doc MORE ON NEXT PAGE 2/09/01 Troubleshooting
HWError Code.doc 02/09/01 • Check CN1 plug for voltage If voltage is recorded at the CN1 plug and LED does not flash, replace board. Insufficient
HWError Code.doc MORE ON NEXT PAGE 02/09/01 High Wall Dia
HWError Code.doc 02/09/01 7 Outdoor Air thermistor malfunction If the following occurs with thermistor: Short condition: greater or = 194 deg F
Troubleshooting & Fault Codes – Section 27Maintenance/RepairMaintenance/Repair40 QA – TroubleshootingThermostat – see Controls40 CG, CS Troublesho
TROUBLESHOOTINGIf the under-ceiling fan coil unit fails to start or operateproperly, sometimes the problem is minor and can be handledwithout a servic
FAULT CODES Table 6 – Indicator Lamps Troubleshooting LAMP STATUS INDICATION CORRECTIVE ACTION POWER flashes 10 seconds after A/C start-up (with or
TROUBLESHOOTING Table 7 – General Troubleshooting Chart (Page 1 of 2; Go to Page 2) SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION a. Power supply to uni
Filter Rack Package – A fully assembled 2” Filter Rack and 1” T.A.W. filter with side access Multi-zone Adapter – Duct collars, internal insulation,
Table 7 – General Troubleshooting Chart (Page 2 of 2; Return to Page 1) SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION Water accumulates and overflows fro
Troubleshooting & Fault Codes – Section 27Maintenance/RepairMaintenance/Repair40 QK – TroubleshootingThermostat – see Controls
Trouble Shooting – Cassette If any of the original wire furnished must be replaced, it must be replaced with type 90 deg C or its equivalent. Wire i
Troubleshooting & Fault Codes – Section 27Maintenance/RepairMaintenance/Repair40 HD – TroubleshootingThermostat – see Controls
Trouble Shooting – Satellite If any of the original wire furnished must be replaced, it must be replaced with type 90 deg C or its equivalent. Wire
Troubleshooting & Fault Codes – Section 27Maintenance/RepairMaintenance/Repair38 HDC – Troubleshooting38 HDL – Troubleshooting38 HDS – Troubleshoo
TROUBLESHOOTING CHART — COOLING CYCLENC — Normally Closed*Heat pump units only.
LEGENDHPS — High-Pressure SwitchLLSV — Liquid (Vapor Supply) Line Solenoid ValveLPS — Low-Pressure SwitchTXV — Thermostatic Expansion ValveTROUBLESHOO
TROUBLESHOOTING CHART — HEATING CYCLE(Heat Pump Units Only)LEGENDCAP — CapillaryNC — Normally ClosedODT — Outdoor ThermostatTEMP — Temperature
Charcoal Filter Kit: The charcoal (carbon) filter kit is available for High Wall fan coils. This accessory improves indoor air quality by removing
TROUBLESHOOTING Table 6 – Indicator Lamps Troubleshooting LAMP STATUS INDICATION CORRECTIVE ACTION POWER flashes 10 seconds after A/C start-up (wi
TROUBLESHOOTING Table 7 – General Troubleshooting Chart (Page 1 of 2; Go to Page 2) SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION a. Power supply to uni
Table 7 – General Troubleshooting Chart (Page 2 of 2; Return to Page 1) SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION Water accumulates and overflows fro
Condensate pumps provide lift capability per the tablebelow:High Wall 009 1ft to 10ft AccessoryHigh Wall 012-024 3ft to 25 ft AccessoryUnder ceiling 2
Dimensional DrawingOPENSIZEBACKOPENINGS2345676A(in.) 9.1 13.4 17.7 22.1 26.4 30.7(mm) 230 340 450 560 670 780B(in.) 11.2 15.5 19.85 24.2 28.
Guide Specifications – Section 6ProductProductHigh-Wall Heat Pump UnitsHigh-Wall Cooling Only UnitsCeiling-Suspended Cooling Only UnitsCeiling Suspend
Guide Specifications High-Wall Heat Pump Units HVAC Guide Specifications Size range: ¾ to 2 Tons Cooling Capacity Carrier Model Number: 40QNE/H &a
D. Coil: Coil shall be copper tube with aluminum fins and galvanized steel tube sheets. Fins shall be bonded to the tubes by mechanical expansion.
ARI* CapacitiesUnder Ceiling ApplicationsIndoor Outdoor Std. Net Cooling Total SEER EER Heating Heating Heating Heating HeatingSection Section CFM BTU
G. Filters: Unit shall have filter track with factory-supplied cleanable filters. H. Electrical Requirements: Unit shall operate on 115 v (009), 208
Guide Specifications High-Wall Cooling Only Units HVAC Guide Specifications Size range: ¾ to 2 Tons Cooling Capacity Carrier Model Number:
D. Coil: Coil shall be copper tube with aluminum fins and galvanized steel tube sheets. Fins shall be bonded to the tubes by mechanical expansion.
H. Electrical Requirements: Unit shall operate on 115-v (009 & 012), or 208/230 v (012-024), 60 Hz power supply as specified on the equipment sche
Guide Specifications Ceiling Suspended Cooling Only Units HVAC Guide Specifications Size range: 1 ½ to 5 Tons Cooling Capacity Carrier Model Numb
E. Motors: Motors shall be permanently lubricated ball bearing with inherent overload protection. Fan motors shall be 3-speed. F. Controls: Controls
J. Special Features (Field Installed): Certain features are not applicable when the features designated by * are specified. For assistance in amendi
Guide Specifications Ceiling Suspended Heat Pump Units HVAC Guide Specifications Size range: 1 ½ to 5 Tons Cooling Capacity Carrier Model Number
Note: The units use the AccuRater piston refrigerant metering device in the indoor unit (for cooling) and at the outdoor unit liquid line service val
I. Operating Characteristics: ARI Capacities Sound Rating (dBa) Indoor Unit Outdoor Unit C/O Btuh H/P Btuh ARI CFM Air* Entering Condenser Air* Ent
ARI* CapacitiesConsole ApplicationsIndoor Outdoor Std. Net Cooling Total SEER EER Heating Heating Heating Heating HeatingSection Section CFM BTUH kW H
1 Guide Specifications Console/Ceiling Suspended Cooling Only System Heat Pump System (With Supplemental Electric Heat) Multi-Zone System (Coolin
2 1.04 WARRANTY One-year parts, 5-year compressor limited warranty Part 2 – Product 2.01 EQUIPMENT A. Unit Cabinet: Outdoor cabinet shall be z
3 MORE ON NEXT PAGE 5. Filter needs cleaning status indication. 6. Automatic airsweep control to provide on or off activ
4 I. Special Capabilities (Field Installed): 1. Fresh Air Intake: A field installed grille to provide for outdoor ventilation air when indoor unit
Guide Specifications In-Ceiling Cassette Cooling Only Units HVAC Guide Specifications Size range: 1 ½ to 3 Tons Cooling Capacity Carrier Model N
D. Coil: Coil shall be copper tube with aluminum fins and galvanized steel tube sheets. Fins shall be bonded to the tubes by mechanical expansion. A
K. Special Features (Field Installed): 1. Fresh Air Intake Kit: Kit shall include filter and duct connections to provide for outdoor ventilation ai
Guide Specifications In-Ceiling Cassette Heat Pump Units HVAC Guide Specifications Size range: 1 ½ to 3 Tons Cooling Capacity Carrier Model Numb
D. Coil: Coil shall be copper tube with aluminum fins and galvanized steel tube sheets. Fins shall be bonded to the tubes by mechanical expansion.
K. Special Features (Field Installed): 1. Fresh Air Intake Kit: Kit shall include filter and duct connections to provide for outdoor ventilation
ARI* Capacities In Ceiling Cassette ApplicationsIndoor Outdoor Std. Net Cooling Total SEER EER Heating Heating Heating Heating HeatingSection Section
Guide Specifications Outdoor Heat Pump Only Units Commercial Condensing Units HVAC Guide Specifications Size range: ¾ to 5 Tons Cooling Capacity C
Part 2 – Products 2.01 EQUIPMENT A. General: Factory assembled, single piece, air-cooled outdoor unit. Contained within the unit enclosure shall be
E. Outdoor Coil: Coil shall be constructed of aluminum fins mechanically bonded to internally enhanced, seamless copper tubes which are cleaned, dehyd
2. Liquid Solenoid Valve: This electronically operated shutoff valve shall close and open in response to compressor operation. The valve should be
Guide Specifications Outdoor Cooling Only Units Commercial (AN/HDC) Light Commercial (HDL) Condensing Units HVAC Guide Specifications Size range:
Part 2 – Products 2.01 EQUIPMENT A. General: Factory assembled, single piece, air-cooled outdoor unit. Contained within the unit enclosure shall be
F. Refrigeration Components: Refrigerant circuit components shall include brass external liquid line service valve with service gage port connections,
2. Liquid Solenoid Valve: This electronically operated shutoff valve shall close and open in response to compressor operation. The valve should be
Guide Specifications Satellite Systems Cooling Only Units HVAC Guide Specifications Size range: 2, 3, & 4 Tons Cooling Capacity Carrier Model
E. Motors: Motors shall be permanently lubricated ball bearing with inherent overload protection. Fan motors shall be 3-speed. F. Internal Condensa
ARI* Capacities Hydronic Cassette ApplicationsUnit Pipe Std. Net Cooling Sensible Heating Gallons PressureSize Version CFM (Btuh) Cooling (Btuh) Per
K. Special Features (Field Installed): Electronic Programmable Thermostat- Thermostat shall be commercial grade and shall provide 7-day, 4-event sc
38 Series Model Number Nomenclature38 xx xxx xVoltageAir Cooled Condenser 1=115-1-603=208/230-1-605=208/230-3-60Unit Type 6=460-3-60AN - Cooling Only
Physical Data : High Wall – Section 8ProductProductCooling and Heat Pump Models
Duct Free Systems - Physical Data - 40 Series High Wall UnitsCooling and Heat Pump ModelsQNB009*** QNB012-1*** QNB012-3*** QNB018** QNB024** QNE009* Q
Physical Data : Under Ceiling/Console -- Section 8ProductProductCooling Only and Heat Pump Models – Under CeilingCooling Only and Heat Pump Models – C
Duct Free Systems - Physical Data - 40 Series Under Ceiling UnitsQAB018^ QAB024 QAB036 QAB048 QAB060 QAE018^ QAE024 QAE036 QAE048 QAE06
Duct Free Systems - Physical Data - 40 Series Console Units40CG018 40CG024 40CG030 40CS018 40CS024 40CS030Nominal Capacity (
Physical Data : Cassette – Section 8ProductProductCooling and Heat Pump ModelsHydronic Cassette
Duct Free Systems - Physical Data - 40 Series Cassette UnitsCooling And Heat Pump ModelsQKB024 QKB036* QKB036 QKE024 QKE036 QKE048Nominal C
Duct Free Systems - Physical Data - Hydronic CassetteUnit 42WKN 004 008 010 016 020Pipe Versio
ARI* Capacities Multi Split Applications Page 1 of 2; Go to Page 2Nom
Physical Data : Satellite – Section 8ProductProductCooling Only and Heat Pump Models
Duct Free Systems - Physical Data - 40 Series Satellite UnitsCooling Models40HD024 40HD036 40HD048Nominal Capacity (Tons)2 3.0 4.0Operating Weight88
Physical Data : Condenser – Section 8ProductProduct38 Series AN & BK Condensers38 Series HDC Condensers38 Series HDL Condensers38 Series QRC Conde
Duct Free Systems - Physical Data - 38 Series AN & BK CondensersCooling Only and Heat Pump ModelsAN009 * AN012-1 * AN012-3 *
Duct Free Systems - Physical Data - 38 Series HDC CondensersCooling Only ModelsHDC018 HDC024 HDC030 HDC036-3 HDC036-5/6 HDC048-3
Duct Free Systems - Physical Data - 38 Series HDL CondensersCooling Only ModelsHDL018 HDL024 HDL030 HDL036301 HDL036311 HDL048 HD
Duct Free Systems - Physical Data - 38 Series QRC CondensersHeat Pump ModelsQR018C QR024C QR030C QR036C-3 QR036C-5/6 QR048C-3 QR0
Duct Free Systems - Physical Data - 38 Series HDS CondensersCooling Only ModelsHDS024 HDS048Nominal Capacity (Tons)2.0 4.0Operati
Duct Free Systems - Physical Data - 38CG, CS, SB, & SC Series CondensersCooling Only & Heat Pump Models38CG018 38CG024 38CG030 38CS018 38CS024
Sound Data – Section 9ProductProductHigh WallUnder CeilingConsoleCassetteSatelliteCondenser
ARI* Capacities Multi Split Applications Page 2 of 2; Go to Page 1Nom
Sound Data "High Wall" Fan Coils (A Weighed)Model Sound Sound Fan Sound Power Data Octave Band (dBa)Pressure (dBa) Power (dBa) Speed 125 2
Sound Data "Under Ceiling" Fan Coils (A Weighted)Model Sound Sound Fan Sound Power Data Octave Band (dBa)Pressure (dBa) Power (dBa) Speed
Sound Data "Console" Fan Coils (A Weighted)Model Sound Sound Fan Sound Power Data Octave Band (dBa)Pressure (dBa) Power (dBa) Speed 125 2
Sound Data "Cassette" Fan Coils (A Weighted)Model Sound Sound Fan Sound Power Data Octave Band (dBa)Pressure (dBa) Power (dBa) Speed 125
Sound Data "Hydronic Cassette" Fan Coils (A Weighted)Model Sound Sound Fan Sound Power Data Octave Band (dBa)Pressure (dBa) Power (dBa) Sp
Sound Data "Satellite" Fan Coils (A Weighted)Model Sound Sound Fan Sound Power Data Octave Band (dBa)Pressure (dBa) Power (dBa) Speed 125
Sound Data "Condensers" (A Weighted)Model Sound Sound Sound Fan Sound Power Data Octave Band (dBa)Power #1(dBa) Power #2(dBa) Pessure (dBa
System Cross MatchCooling Only High Wall Heat Pump High WallNominal Indoor Indoor Outdoor Outdoor Nominal Indoor Indoor Outdoor OutdoorCapacity Unit U
System Cross MatchCooling Only High Wall Heat Pump High WallNominal Indoor Indoor Outdoor Outdoor Nominal Indoor Indoor Outdoor OutdoorCapacity Unit U
System Cross MatchCooling Only High Wall Heat Pump High WallNominal Indoor Indoor Outdoor Outdoor Nominal Indoor Indoor Outdoor OutdoorCapacity Unit U
Comments to this Manuals